[Federal Register Volume 75, Number 245 (Wednesday, December 22, 2010)]
[Rules and Regulations]
[Pages 80292-80293]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2010-32119]


-----------------------------------------------------------------------

DEPARTMENT OF ENERGY

10 CFR Part 431

[Docket Number EERE-2008-BT-TP-0008]
RIN 1904-AB71


Energy Conservation Program: Energy Conservation Standards for 
Electric Motors

AGENCY: Office of Energy Efficiency and Renewable Energy, Department of 
Energy.

ACTION: Final rule; technical correction.

-----------------------------------------------------------------------

SUMMARY: The U.S. Department of Energy (DOE) published a final rule on 
March 23, 2009, promulgating energy conservation standards for certain 
electric motors as prescribed in the Energy Policy and Conservation 
Act, as amended by the Energy Independence and Security Act. This 
document is being issued to correct the energy efficiency levels that 
DOE promulgated for NEMA Design B general purpose electric motors that, 
due to a drafting error, are not consistent with statutory 
requirements.

DATES: This technical correction is effective as of December 22, 2010.

FOR FURTHER INFORMATION CONTACT: Mr. James Raba, U.S. Department of 
Energy, Office of Energy Efficiency and Renewable Energy, Building 
Technologies Program, EE-2J, 1000 Independence Avenue, SW., Washington, 
DC 20585-0121. Telephone: (202) 586-8654. E-mail: [email protected].
    In the Office of the General Counsel, contact Ms. Ami Grace-Tardy, 
U.S. Department of Energy, Office of the General Counsel, GC-71, 1000 
Independence Avenue, SW., Washington, DC 20585. Telephone: (202) 586-
5709. E-mail: [email protected].

SUPPLEMENTARY INFORMATION:

I. Background

    The Energy Policy and Conservation Act (EPCA), as amended by 
section 313(b)(1)(B) of the Energy Independence and Security Act (EISA 
2007), requires each National Electrical Manufacturers Association 
(NEMA) Design B, general purpose electric motor with a power rating of 
more than 200 horsepower, but not greater than 500 horsepower, 
manufactured (alone or as a component of another piece of equipment) 
after December 19, 2010, to have a nominal full load efficiency that is 
not less than the values in NEMA Standard MG-1 (2006) Table 12-11. (42 
U.S.C. 6313(b)(2)(D)) DOE codified this requirement at 10 CFR 
431.25(f). 74 FR 12058 (March 23, 2009)
    It was recently discovered that the efficiency levels under 10 CFR 
431.25(f), for NEMA Design B, six-pole open motors rated 250, 300, and 
350 horsepower are not consistent with the EISA 2007 levels as 
prescribed. Today's final rule conforms these efficiency levels with 
EPCA, as amended by EISA 2007, by replacing the nominal full load 
efficiency of ``94.5'' with ``95.4.''

II. Need for Correction

    As published, the nominal full load efficiency table at 10 CFR 
431.25(f) contains three values that deviate from the requirements 
established by EPCA, as amended by EISA 2007. To correct this error, 
DOE is amending 10 CFR 431.25(f) to replace the current table with a 
corrected table of values. In light of the statutory requirement, the 
change addressed by today's document is technical in nature. In 
addition, because DOE does not have the discretion to deviate from 
these statutorily-prescribed requirements, DOE finds that there is good 
cause under 5 U.S.C. 553(b)(B) to not issue a separate notice to 
solicit public comment on the changes contained in this document. 
Issuing a separate notice to solicit public comments would be 
impractical, unnecessary, and contrary to the public interest.

List of Subjects in 10 CFR part 431

    Administrative practice and procedure, Energy conservation, 
Reporting and recordkeeping requirements.

    Issued in Washington, DC, on December 15, 2010.
Cathy Zoi,
Assistant Secretary, Energy Efficiency and Renewable Energy.

0
For the reasons stated in the preamble, DOE amends 10 CFR Part 431 as 
set forth below.

PART 431--ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND 
INDUSTRIAL EQUIPMENT

0
1. The authority citation for part 431 continues to read as follows:

    Authority:  42 U.S.C. 6291-6317.

0
2. Section 431.25 is amended by revising paragraph (f) to read as 
follows:


Sec.  431.25  Energy conservation standards and effective dates.

* * * * *
    (f) Each NEMA Design B general purpose electric motor with a power 
rating of more than 200 horsepower, but not greater than 500 
horsepower, manufactured (alone or as a component of another piece of 
equipment), on or after December 19, 2010, shall have a nominal full 
load efficiency that is not less than the following:

[[Page 80293]]



                                         Full-Load Efficiencies of NEMA Design B General Purpose Electric Motors
--------------------------------------------------------------------------------------------------------------------------------------------------------
                                                                                       Nominal full load efficiency
                                                 -------------------------------------------------------------------------------------------------------
                Motor horsepower                            Open motors  (number of poles)                    Enclosed motors  (number of poles)
                                                 -------------------------------------------------------------------------------------------------------
                                                       8            6            4            2            8            6            4            2
--------------------------------------------------------------------------------------------------------------------------------------------------------
250.............................................         94.5         95.4         95.4         94.5         94.5         95.0         95.0         95.4
300.............................................  ...........         95.4         95.4         95.0  ...........         95.0         95.4         95.4
350.............................................  ...........         95.4         95.4         95.0  ...........         95.0         95.4         95.4
400.............................................  ...........  ...........         95.4         95.4  ...........  ...........         95.4         95.4
450.............................................  ...........  ...........         95.8         95.8  ...........  ...........         95.4         95.4
500.............................................  ...........  ...........         95.8         95.8  ...........  ...........         95.8         95.4
--------------------------------------------------------------------------------------------------------------------------------------------------------

* * * * *
[FR Doc. 2010-32119 Filed 12-21-10; 8:45 am]