[Code of Federal Regulations] [Title 24, Volume 5] [Revised as of April 1, 2001] From the U.S. Government Printing Office via GPO Access [CITE: 24CFR3280.103] [Page 113-114] TITLE 24--HOUSING AND URBAN DEVELOPMENT CHAPTER XX--OFFICE OF ASSISTANT SECRETARY FOR HOUSING--FEDERAL HOUSING COMMISSIONER, DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT PART 3280--MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS--Table of Contents Subpart B--Planning Considerations Sec. 3280.103 Light and ventilation. (a) Lighting. Each habitable room shall be provided with exterior windows and/or doors having a total glazed area of not less than 8 percent of the gross floor area. (1) Kitchens, bathrooms, toilet compartments, laundry areas, and utility rooms may be provided with artificial light in place of windows. (2) Rooms and areas may be combined for the purpose of providing the required natural lighting provided that at least one half of the common wall area is open and unobstructed, and the open area is at least equal to 10 percent of the combined floor area or 25 square feet whichever is greater. (b) Whole house ventilation. Each manufactured home shall be capable of providing a minimum of 0.35 air changes per hour continuously or at an equivalent hourly average rate. The following criteria shall be adhered to. (1) Natural infiltration and exfiltration shall be considered as providing 0.25 air changes per hour. (2) The remaining ventilation capacity of 0.10 air change per hour or its hourly average equivalent shall be calculated using 0.035 cubic feet per minute per square foot of interior floor space. This ventilation capacity shall be in addition to any openable window area. (3) The remaining ventilation capacity may be provided by: a mechanical system, or a passive system, or a combination passive and mechanical system. The ventilation system or provisions shall not create a positive pressure in Uo value Zones 2 and 3 or a negative pressure condition in Uo value Zone 1. Mechanical systems shall be balanced. Combination passive and mechanical systems shall have adequately sized inlets or exhaust to release any unbalanced pressure. Passive systems shall have inlets and exhaust of sufficient size to alleviate unbalance pressure conditions under normal conditions. Temporary imbalances due to gusting or high winds are permitted. (4) The ventilation system or provision shall exchange air directly with the exterior of the home, except it shall not draw or expel air with the space underneath the home. The ventilation system or provision shall not draw or expel air into the floor, wall, or ceiling/roof systems even if those systems are vented. (5) The ventilation system or a portion thereof may be integral with the homes heating or cooling system. The system shall be capable of operating independently of the heating or cooling modes. A ventilation system that is integral with the heating or cooling system shall be listed as part of the heating and cooling system or listed as suitable for use therewith. (6) A mechanical ventilation system, or mechanical portion thereof, shall be provided with a manual control and may be provided with automatic timers or humidistats. (7) Substantiation of the ventilation capacity to provide 0.10 ACH shall be provided for a mechanical system, or a passive system, or a combination passive and mechanical system. (c) Additional ventilation. (1) At least half of the minimum required glazed area in paragraph (a) of this section shall be openable directly to the outside of the manufactured home for unobstructed ventilation. These same ventilation requirements apply to rooms combined in accordance with Sec. 3280.103(a)(2). (2) Kitchens shall be provided with a mechanical ventilation system that is capable of exhausting 100 cfm to the outside of the home. The exhaust fan shall be located as close as possible to the range or cook top, but in no case farther than 10 feet horizontally from the range or cook top. (3) Each bathroom and separate toilet compartment shall be provided with a mechanical ventilation system capable of exhausting 50 cfm to the outside [[Page 114]] of the home. A separate toilet compartment may be provided with 1.5 square feet of openable glazed area in place of mechanical ventilation, except in Uo value Zone 3. [58 FR 55003, Oct. 25, 1993]