[Code of Federal Regulations]
[Title 24, Volume 5]
[Revised as of April 1, 2001]
From the U.S. Government Printing Office via GPO Access
[CITE: 24CFR3280.306]

[Page 130-131]
 
                 TITLE 24--HOUSING AND URBAN DEVELOPMENT
 
 CHAPTER XX--OFFICE OF ASSISTANT SECRETARY FOR HOUSING--FEDERAL HOUSING 
        COMMISSIONER, DEPARTMENT OF HOUSING AND URBAN DEVELOPMENT
 
PART 3280--MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARDS--Table of Contents
 
           Subpart D--Body and Frame Construction Requirements
 
Sec. 3280.306  Windstorm protection.

    (a) Provisions for support and anchoring systems. Each manufactured 
home shall have provisions for support/anchoring or foundation systems 
that, when properly designed and installed, will resist overturning and 
lateral movement (sliding) of the manufactured home as imposed by the 
respective design loads. For Wind Zone I, the design wind loads to be 
used for calculating resistance to overturning and lateral movement 
shall be the simultaneous application of the wind loads indicated in 
Sec. 3280.305(c)(1)(i), increased by a factor of 1.5. The 1.5 factor of 
safety for Wind Zone I is also to be applied simultaneously to both the 
vertical building projection, as horizontal wind load, and across the 
surface of the full roof structure, as uplift loading. For Wind Zones II 
and III, the resistance shall be determined by the simultaneous 
application of the horizontal drag and uplift wind loads, in accordance 
with Sec. 3280.305(c)(1)(ii). The basic allowable stresses of materials 
required to resist overturning and lateral movement shall not be 
increased in the design and proportioning of these members. No 
additional shape or location factors need to be applied in the design of 
the tiedown system. The dead load of the structure may be used to resist 
these wind loading effects in all Wind Zones.
    (1) The provisions of this section shall be followed and the support 
and anchoring systems shall be designed by a Registered Professional 
Engineer or Architect.
    (2) The manufacturer of each manufactured home is required to make 
provision for the support and anchoring systems but is not required to 
provide the anchoring equipment or stabilizing devices. When the 
manufacturer's installation instructions provide for the main frame 
structure to be used as the points for connection of diagonal ties, no 
specific connecting devices need be provided on the main frame 
structure.
    (b) Contents of instructions. (1) The manufacturer shall provide 
printed instructions with each manufactured home specifying the location 
and required capacity of stabilizing devices on which the design is 
based. The manufacturer shall provide drawings and specifications 
certified by a registered professional engineer or architect indicating 
at least one acceptable system of anchoring, including the details of 
required straps or cables, their end connections, and all other devices 
needed to transfer the wind loads from the manufactured home to an 
anchoring or foundation system.
    (2) For anchoring systems, the instructions shall indicate:
    (i) The minimum anchor capacity required;
    (ii) That anchors should be certified by a professional engineer, 
architect, or a nationally recognized testing laboratory as to their 
resistance, based on the maximum angle of diagonal tie and/or vertical 
tie loading (see paragraph (c)(3) of this section) and angle of anchor 
installation, and type of soil in which the anchor is to be installed;
    (iii) That ground anchors should be embedded below the frost line 
and be at

[[Page 131]]

least 12 inches above the water table; and
    (iv) That ground anchors should be installed to their full depth, 
and stabilizer plates should be installed to provide added resistance to 
overturning or sliding forces.
    (v) That anchoring equipment should be certified by a registered 
professional engineer or architect to resist these specified forces in 
accordance with testing procedures in ASTM Standard Specification D3953-
91, Standard Specification for Strapping, Flat Steel and Seals.
    (c) Design criteria. The provisions made for anchoring systems shall 
be based on the following design criteria for manufactured homes.
    (1) The minimum number of ties provided per side of each home shall 
resist design wind loads required in Sec. 3280.305(c)(1).
    (2) Ties shall be as evenly spaced as practicable along the length 
of the manufactured home, with not more than two (2) feet open-end 
spacing on each end.
    (3) Vertical ties or straps shall be positioned at studs. Where a 
vertical tie and a diagonal tie are located at the same place, both ties 
may be connected to a single anchor, provided that the anchor used is 
capable of carrying both loadings, simultaneously.
    (4) Add-on sections of expandable manufactured homes shall have 
provisions for vertical ties at the exposed ends.
    (d) Requirements for ties. Manufactured homes in Wind Zone I require 
only diagonal ties. These ties shall be placed along the main frame and 
below the outer side walls. All manufactured homes designed to be 
located in Wind Zones II and III shall have a vertical tie installed at 
each diagonal tie location.
    (e) Protection requirements. Protection shall be provided at sharp 
corners where the anchoring system requires the use of external straps 
or cables. Protection shall also be provided to minimize damage to 
siding by the cable or strap.
    (f) Anchoring equipment--load resistance. Anchoring equipment shall 
be capable of resisting an allowable working load equal to or exceeding 
3,150 pounds and shall be capable of withstanding a 50 percent overload 
(4,725 pounds total) without failure of either the anchoring equipment 
or the attachment point on the manufactured home.
    (g) Anchoring equipment--weatherization. Anchoring equipment exposed 
to weathering shall have a resistance to weather deterioration at least 
equivalent to that provided by a coating of zinc on steel of not less 
than 0.30 ounces per square foot of surface coated, and in accordance 
with the following:
    (1) Slit or cut edges of zinc-coated steel strapping do not need to 
be zinc coated.
    (2) Type 1, Finish B, Grade 1 steel strapping, 1-1/4 inches wide and 
0.035 inches in thickness, certified by a registered professional 
engineer or architect as conforming with ASTM Standard Specification 
D3953-91, Standard Specification for Strapping, Flat Steel, and Seals.

[40 FR 58752, Dec. 18, 1975. Redesignated at 44 FR 20679, Apr. 6, 1979, 
as amended at 52 FR 4583, Feb. 12, 1987; 59 FR 2473, Jan. 14, 1994]