[Code of Federal Regulations]
[Title 10, Volume 3]
[Revised as of January 1, 2001]
From the U.S. Government Printing Office via GPO Access
[CITE: 10CFR435.106]

[Page 549-553]
 
                            TITLE 10--ENERGY
 
                    CHAPTER II--DEPARTMENT OF ENERGY
 
PART 435--ENERGY CONSERVATION VOLUNTARY PERFORMANCE STANDARDS FOR NEW BUILDINGS; MANDATORY FOR FEDERAL BUILDINGS--Table of Contents
 
Subpart A--Voluntary Performance Standards for New Commercial and Multi-
 Family High Rise Residential Buildings; Mandatory for Federal Buildings
 
Sec. 435.106  Electric power and distribution.

                              6.1  General

    6.1.1  This section contains minimum requirements for all building 
electrical systems, except required emergency systems.
    6.1.2  A building shall be considered in compliance with this 
section if the minimum requirements of section 6.3 are met.

                        6.2  Principles of Design

    6.2.1  Electric Distribution Systems
    6.2.1.1  Transformers and generating units shall be sized as close 
as possible to the actual anticipated load (i.e., oversizing is to be 
avoided so that fixed thermal losses are minimized).
    6.2.1.2  Distribution of electric power at the highest practical 
voltage and load selection at the maximum power factor consistent with 
safety shall be considered. The use of distribution system transformers 
shall be minimized.
    6.2.1.3  Tenant submetering can be one of the most cost-effective 
energy conservation measures available. A large portion of the energy 
use in tenant facilities occurs simply because there is no economic 
incentive to conserve.

                        6.3  Minimum Requirements

    6.3.1  Electrical Distribution System
    6.3.1.1  All commercial or multi-family high rise residential 
buildings, having designed connected electric service over 250 kVA, 
shall have electrical energy consumption check metered on the basis of 
usage category or tenant occupancy, depending on conditions defined 
below. For buildings that are occupied by multiple tenants, the metering 
shall be per tenant, if the tenant has a connected load of 100 kVA or 
more. HVAC and service hot water systems, shared among tenants, need not 
meet this requirement but shall be separately metered.
    6.3.1.2  The electrical power feeders for each facility for which 
check-metering is required shall be by tenant and shall be subdivided in 
accordance with the following categories:
    6.3.1.2.1  Lighting and receptacle outlets;
    6.3.1.2.2  HVAC and service water heating systems and equipment; and
    6.3.1.2.3  Special occupant equipment or systems of more than 20 kW, 
such as elevators, computer rooms, kitchens, printing equipment, and 
baling presses.
    6.3.1.2.4  Exception to Section 6.3.1.2:
    (a) 10% or less of the loads on a feeder may be from another usage 
category.
    6.3.1.3  The power feeders for each category shall contain portable 
or permanent submetering prior to or within any primary or secondary 
distribution panels. Such provisions shall include a separate 
compartment or panel of adequate size and design to house the necessary 
voltage and current transformers. An accessible means of attaching 
clamp-on meters or split-core current transformers shall be provided.
    6.3.1.4  The locations of these points of measurement may be central 
or distributed throughout the building, as

[[Page 550]]

appropriate to the layout of the building. A minimum arrangement shall 
provide a safe method for access to the enclosures through which feeder 
conductors pass, and have sufficient space to attach clamp-on or split-
core current transformers. These enclosures may be separate compartments 
or combined with electrical cabinets serving another function. 
Enclosures so furnished shall be identified by available measuring 
function. A preferred arrangement would include kWh meters and demand 
registers, or a means to transmit such information to a building energy 
management control system.
    6.3.1.5  In multiple-tenant buildings, where designed connected 
electrical service is over 250 kVA, each tenant space having a total 
connected load of more than 100 kVA shall have provision made to permit 
check-metering of the total tenant load. If the building is served by a 
common HVAC system, the HVAC loads need not be check metered for each 
tenant.

                           6.3.2  Transformers

    6.3.2.1  All permanently wired transformers, that are part of the 
building electrical distribution system, except utility-owned 
transformers, shall be selected to minimize the combination of no-load, 
part-load, and full-load losses, without compromising the electrical 
system operating and reliability requirements.
    6.3.2.2  If the total capacity of the transformers exceeds 300 kVA, 
a calculation of total estimated annual operating costs of the 
transformer losses shall be made. This calculation shall be based on 
estimated hours of transformer operation at projected part-load and 
full-load conditions, and the associated transformer core and coil 
losses. If appropriate data for projecting this calculation is 
unavailable, use Form 6.3-1 ``Transformer Loss Calculation Estimate'' as 
a basis for making the estimate. The calculations made in accordance 
with this section shall be used to compare among types of transformers 
and configurations available to the designer to balance energy costs 
with necessary operating flexibility, reliability (redundancy), and 
safety. The projected annual energy costs for the losses of the selected 
arrangement shall be retained as part of the electrical design 
documentation.

[[Page 551]]

[GRAPHIC] [TIFF OMITTED] TC04OC91.207

    6.3.3  Electric Motors
    6.3.3.1  All permanently wired polyphase motors of 1 hp or more 
serving the building, shall meet the requirements of this section. 
Motors expected to operate more than 500 hours per year shall have a 
minimum acceptable nominal full-load motor efficiency no less than that 
shown in Table 6.3-1.
    6.3.3.1.1  Table 6.3-1 applies to motors having nominal 1200, 1800, 
or 3600 RPM; with open, drip-proof, or TEFC enclosures. Other motor 
types are exempted from the minimum efficiency requirements of these 
standards.
    6.3.3.1.2  Motor efficiency ratings shall be based on a 
statistically valid quality control procedure conforming

[[Page 552]]

with ANSI/IEEE 112-1984, Test Method B (Dynamometer) using NEMA MG 1-
1987 (MG 1-12.54 and MG 1-12.55) for motors below 500 hp. For motors 500 
hp and above, ANSI/IEEE 112-1984, Test Method B or Method F (Equivalent 
Circuit Calculation), shall be used.
    6.3.3.1.3  Values listed in Table 6.3-1 are nominal efficiencies. 
Minimum motor efficiencies shall not be less than the corresponding 
values provided in NEMA MG 1-12.54.
[GRAPHIC] [TIFF OMITTED] TC04OC91.208

    6.3.3.1.4  Motor efficiency shall be tested using a statistically 
valid quality control procedure conforming with the IEEE 112A, Test 
Method B (1978) (Dynmometer) fan motors E below 500 hp, or Test Method F 
(1978) (Equivalent Circuit Calculation) based on no-load measurements 
for motors 500 hp and larger.
    6.3.3.2  Motor nameplates shall list the minimum and the nominal 
full-load motor efficiencies and the full-load power factor.
    6.3.3.3  Full-load motor power factor for three-phase motors can be 
calculated from nameplate data by Equation 6.3-1:

% Power Factor=(hp  x  745  x  100)/(nominal efficiency  x  full-load 
          amps  x  rated voltage  x 30.5).

                             Equation 6.3-1

    6.3.3.4  Motor horsepower rating shall not exceed 125% of the 
calculated maximum load being served, or the next larger standard motor 
size if a

[[Page 553]]

standard rating does not fall within this range.
    6.3.4  Operation and Maintenance of Electrical Systems
    6.3.4.1  The designer shall specify that building owners be provided 
with written information that provides basic data relating to the 
design, operation, and maintenance of the electrical distribution system 
for the building. This shall include:
    6.3.4.1.1  a single-line diagram of the ``as-built'' building 
electrical system;
    6.3.4.1.2  schematic diagrams of electrical control systems (other 
than HVAC, covered elsewhere);
    6.3.4.1.3  manufacturers' operating and maintenance manuals on 
active electrical equipment; and
    6.3.4.1.4  the Transformer Loss Calculation Estimate if required by 
Section 6.3.2.2.