[Code of Federal Regulations] [Title 30, Volume 1] [Revised as of July 1, 2002] From the U.S. Government Printing Office via GPO Access [CITE: 30CFR18.42] [Page 102] TITLE 30--MINERAL RESOURCES CHAPTER I--MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR PART 18--ELECTRIC MOTOR-DRIVEN MINE EQUIPMENT AND ACCESSORIES--Table of Contents Subpart B--Construction and Design Requirements Sec. 18.42 Explosion-proof distribution boxes. (a) A cable passing through an outside wall(s) of a distribution box shall be conducted either through a packing gland or an interlocked plug and receptacle. (b) Short-circuit protection shall be provided for each branch circuit connected to a distribution box. The current-carrying capacity of the specified connector shall be compatible with the automatic circuit-interrupting device. (c) Each branch receptacle shall be plainly and permanently marked to indicate its current-carrying capacity and each receptacle shall be such that it will accommodate only an appropriate plug. (d) Provision shall be made to relieve mechanical strain on all connectors to distribution boxes.