[Code of Federal Regulations]
[Title 30, Volume 1]
[Revised as of July 1, 2002]
From the U.S. Government Printing Office via GPO Access
[CITE: 30CFR18.53]

[Page 105-107]
 
                       TITLE 30--MINERAL RESOURCES
 
  CHAPTER I--MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR
 
PART 18--ELECTRIC MOTOR-DRIVEN MINE EQUIPMENT AND ACCESSORIES--Table of Contents
 
             Subpart B--Construction and Design Requirements
 
Sec. 18.53  High-voltage longwall mining systems.

    (a) In each high-voltage motor-starter enclosure, with the exception 
of a controller on a high-voltage shearer, the disconnect device 
compartment, control/communications compartment, and motor contactor 
compartment must be separated by barriers or partitions to prevent 
exposure of personnel to energized high-voltage conductors or parts. In 
each motor-starter enclosure on a high-voltage shearer, the high-voltage 
components must be separated from lower voltage components by barriers 
or partitions to prevent exposure of personnel to energized high-voltage 
conductors or parts. Barriers or partitions must be constructed of 
grounded metal or nonconductive insulating board.
    (b) Each cover of a compartment in the high-voltage motor-starter 
enclosure containing high-voltage components must be equipped with at 
least two interlock switches arranged to automatically deenergize the 
high-voltage components within that compartment when the cover is 
removed.
    (c) Circuit-interrupting devices must be designed and installed to 
prevent automatic reclosure.
    (d) Transformers with high-voltage primary windings that supply 
control voltages must incorporate grounded electrostatic (Faraday) 
shielding between the primary and secondary windings. The shielding must 
be connected to equipment ground by a minimum No. 12 AWG grounding 
conductor. The secondary nominal voltage must not exceed 120 volts, line 
to line.
    (e) Test circuits must be provided for checking the condition of 
ground-wire monitors and ground-fault protection without exposing 
personnel to energized circuits. Each ground-test circuit must inject a 
primary current of 50 percent or less of the current rating of the 
grounding resistor through the current transformer and cause each 
corresponding circuit-interrupting device to open.
    (f) Each motor-starter enclosure, with the exception of a controller 
on a high-voltage shearer, must be equipped with a disconnect device 
installed to deenergize all high-voltage power conductors extending from 
the enclosure when the device is in the ``open'' position.
    (1) When multiple disconnect devices located in the same enclosure 
are used to satisfy the above requirement they must be mechanically 
connected to provide simultaneous operation by one handle.
    (2) The disconnect device must be rated for the maximum phase-to-
phase voltage and the full-load current of the circuit in which it is 
located, and installed so that--
    (i) Visual observation determines that the contacts are open without 
removing any cover;
    (ii) The load-side power conductors are grounded when the device is 
in the ``open'' position;
    (iii) The device can be locked in the ``open'' position;
    (iv) When located in an explosion-proof enclosure, the device must 
be designed and installed to cause the current to be interrupted 
automatically prior to the opening of the contacts; and
    (v) When located in a non-explosion-proof enclosure, the device must 
be designed and installed to cause the current to be interrupted 
automatically prior to the opening of the contacts, or the device must 
be capable of interrupting the full-load current of the circuit.
    (g) Control circuits for the high-voltage motor starters must be 
interlocked with the disconnect device so that--
    (1) The control circuit can be operated with an auxiliary switch in 
the

[[Page 106]]

``test'' position only when the disconnect device is in the open and 
grounded position; and
    (2) The control circuit can be operated with the auxiliary switch in 
the ``normal'' position only when the disconnect switch is in the closed 
position.
    (h) A study to determine the minimum available fault current must be 
submitted to MSHA to ensure adequate protection for the length and 
conductor size of the longwall motor, shearer and trailing cables.
    (i) Longwall motor and shearer cables with nominal voltages greater 
than 660 volts must be made of a shielded construction with a grounded 
metallic shield around each power conductor.
    (j) High-voltage motor and shearer circuits must be provided with 
instantaneous ground-fault protection of not more than 0.125-amperes. 
Current transformers used for this protection must be of the single-
window type and must be installed to encircle all three phase 
conductors.
    (k) Safeguards against corona must be provided on all 4,160 voltage 
circuits in explosion-proof enclosures.
    (l) The maximum pressure rise within an explosion-proof enclosure 
containing high-voltage switchgear must be limited to 0.83 times the 
design pressure.
    (m) High-voltage electrical components located in high-voltage 
explosion-proof enclosures must not be coplanar with a single plane 
flame-arresting path.
    (n) Rigid insulation between high-voltage terminals (Phase-to-Phase 
or Phase-to-Ground) must be designed with creepage distances in 
accordance with the following table:

                                           Minimum Creepage Distances
----------------------------------------------------------------------------------------------------------------
                                              Minimum creepage distances (inches) for comparative tracking index
                                 Points of                              (CTI) range \1\
    Phase to phase voltage        measure    -------------------------------------------------------------------
                                                 CTI[ge]500     380[le]CTI<500   175[le]CTI<380      CTI<175
----------------------------------------------------------------------------------------------------------------
2,400........................  0-0                       1.50             1.95             2.40             2.90
                               0-G                       1.00             1.25             1.55             1.85
4,160........................  0-0                       2.40             3.15             3.90             4.65
                               0-G                       1.50             1.95             2.40            2.90
----------------------------------------------------------------------------------------------------------------
\1\ Assumes that all insulation is rated for the applied voltage or higher.

(o) Explosion-proof motor-starter enclosures must be designed to 
establish the minimum free distance (MFD) between the wall or cover of 
the enclosure and uninsulated electrical conductors inside the enclosure 
in accordance with the following table:

                                    High-Voltage Minimum Free Distances (MFD)
----------------------------------------------------------------------------------------------------------------
                                                Steel MFD (in)                       Aluminum MFD (in)
     Wall/cover thickness (in)     -----------------------------------------------------------------------------
                                       A \1\        B \2\        C \3\          A            B            C
----------------------------------------------------------------------------------------------------------------
\1/4\.............................          2.8          4.3          5.8       \4\ NA       \4\ NA       \4\ NA
\3/8\.............................          1.8          2.3          3.9          8.6         12.8         18.1
\1/2\.............................        * 1.2          2.0          2.7          6.5          9.8         13.0
\5/8\.............................        * 0.9          1.5          2.1          5.1          7.7         10.4
\3/4\.............................        * 0.6        * 1.1          1.6          4.1          6.3          8.6
1.................................          (*)        * 0.6        * 1.0          2.9          4.5         6.2
----------------------------------------------------------------------------------------------------------------
Note *: The minimum electrical clearances must still be maintained.
\1\ Column A specifies the MFD for enclosures that have available 3-phase bolted short-circuit currents of
  10,000 amperes rms or less.
\2\ Column B specifies the MFD for enclosures that have a maximum available 3-phase bolted short-circuit
  currents greater than 10,000 and less than or equal to 15,000 amperes rms.
\3\ Column C specifies the MFD for enclosures that have a maximum available 3-phase bolted short-circuit
  currents greater than 15,000 and less than or equal to 20,000 amperes rms.
\4\ Not Applicable--MSHA doesn't allow aluminum wall or covers to be \1/4\ inch or less in thickness (Section
  18.31).

(1) For values not included in the table, the following formulas on 
which the table is based may be used to determine the minimum free 
distance.
(i) Steel Wall/Cover:

[[Page 107]]

[GRAPHIC] [TIFF OMITTED] TR11MR02.001

    (ii) Aluminum Wall/Cover:
    [GRAPHIC] [TIFF OMITTED] TR11MR02.002
    

Where C is 1.4 for 2,400 volt systems or 3.0 for 4,160 volt systems, 
Isc is the 3-phase short circuit current in amperes of the 
system, t is the clearing time in seconds of the outby circuit-
interrupting device and d is the thickness in inches of the metal wall/
cover adjacent to an area of potential arcing.
    (2) The minimum free distance must be increased by 1.5 inches for 
4,160 volt systems and 0.7 inches for 2,400 volt systems when the 
adjacent wall area is the top of the enclosure. If a steel shield is 
mounted in conjunction with an aluminum wall or cover, the thickness of 
the steel shield is used to determine the minimum free distances.
    (p) The following static pressure test must be performed on each 
prototype design of explosion-proof enclosures containing high-voltage 
switchgear prior to the explosion tests. The static pressure test must 
also be performed on every explosion-proof enclosure containing high-
voltage switchgear, at the time of manufacture, unless the manufacturer 
uses an MSHA accepted quality assurance procedure covering inspection of 
the enclosure. Procedures must include a detailed check of parts against 
the drawings to determine that the parts and the drawings coincide and 
that the minimum requirements stated in part 18 have been followed with 
respect to materials, dimensions, configuration and workmanship.
    (1) Test procedure. (i) The enclosure must be internally pressurized 
to at least the design pressure, maintaining the pressure for a minimum 
of 10 seconds.
    (ii) Following the pressure hold, the pressure must be removed and 
the pressurizing agent removed from the enclosure.
    (2) Acceptable performance. (i) The enclosure during pressurization 
must not exhibit--
    (A) Leakage through welds or casting; or
    (B) Rupture of any part that affects the explosion-proof integrity 
of the enclosure.
    (ii) The enclosure following removal of the pressurizing agents must 
not exhibit--
    (A) Visible cracks in welds;
    (B) Permanent deformation exceeding 0.040 inches per linear foot; or
    (C) Excessive clearances along flame-arresting paths following 
retightening of fastenings, as necessary.

[67 FR 10999, Mar. 11, 2002]