[Code of Federal Regulations]
[Title 49, Volume 2]
[Revised as of October 1, 2002]
From the U.S. Government Printing Office via GPO Access
[CITE: 49CFR178.57]

[Page 810-816]
 
                        TITLE 49--TRANSPORTATION
 
 CHAPTER I--RESEARCH AND SPECIAL PROGRAMS ADMINISTRATION, DEPARTMENT OF 
                             TRANSPORTATION
 
PART 178--SPECIFICATIONS FOR PACKAGINGS--Table of Contents
 
                 Subpart C--Specifications for Cylinders
 
Sec. 178.57  Specification 4L welded insulated cylinders.

    (a) Type, size, service pressure, and design service temperature. A 
DOT 4L cylinder is a fusion welded insulated cylinder with a water 
capacity (nominal) not over 1,000 pounds water capacity and a service 
pressure of at least 40 but

[[Page 811]]

not greater than 500 psig conforming to the following requirements:
    (1) For liquefied hydrogen service, the cylinders must be designed 
to stand on end, with the axis of the cylindrical portion vertical.
    (2) The design service temperature is the coldest temperature for 
which a cylinder is suitable. The required design service temperatures 
for each cryogenic liquid is as follows:

------------------------------------------------------------------------
             Cryogenic liquid                Design service temperature
------------------------------------------------------------------------
Argon.....................................  Minus 320  deg.F or colder.
Helium....................................  Minus 452  deg.F or colder.
Hydrogen..................................  Minus 42 3  deg.F or colder.
Neon......................................  Minus 411  deg.F or colder.
Nitrogen..................................  Minus 320  deg.F or colder.
Oxygen....................................  Minus 320  deg.F or colder.
------------------------------------------------------------------------

    (b) Material. Material use in the construction of this specification 
must conform to the following:
    (1) Inner containment vessel (cylinder). Designations and limiting 
chemical compositions of steel authorized by this specification must be 
as shown in table 1 in paragraph (o) of this section.
    (2) Outer jacket. Steel or aluminum may be used subject to the 
requirements of paragraph (o)(2) of this section.
    (c) Identification of material. Material must be identified by any 
suitable method.
    (d) Manufacture. Cylinders must be manufactured using equipment and 
processes adequate to ensure that each cylinder produced conforms to the 
requirements of this subpart and to the following requirements:
    (1) No defect is permitted that is likely to weaken the finished 
cylinder appreciably. A reasonably smooth and uniform surface finish is 
required. The shell portion must be a reasonably true cylinder.
    (2) The heads must be seamless, concave side to the pressure, 
hemispherical or ellipsoidal in shape with the major diameter not more 
than twice the minor diameter. Minimum thickness of heads may not be 
less than 90 percent of the required thickness of the sidewall. The 
heads must be reasonably true to shape, have no abrupt shape changes, 
and the skirts must be reasonably true to round.
    (3) The surface of the cylinder must be insulated. The insulating 
material must be fire resistant. The insulation on non-evacuated jackets 
must be covered with a steel jacket not less than 0.060-inch thick or an 
aluminum jacket not less than 0.070 inch thick, so constructed that 
moisture cannot come in contact with the insulating material. If a 
vacuum is maintained in the insulation space, the evacuated jacket must 
be designed for a minimum collapsing pressure of 30 psig differential 
whether made of steel or aluminum. The construction must be such that 
the total heat transfer, from the atmosphere at ambient temperature to 
the contents of the cylinder, will not exceed 0.0005 Btu per hour, per 
Fahrenheit degree differential in temperature, per pound of water 
capacity of the cylinder. For hydrogen, cryogenic liquid service, the 
total heat transfer, with a temperature differential of 520 Fahrenheit 
degrees, may not exceed that required to vent 30 SCF of hydrogen gas per 
hour.
    (4) For a cylinder having a design service temperature colder than 
minus 320  deg.F, a calculation of the maximum weight of contents must 
be made and that weight must be marked on the cylinder as prescribed in 
Sec. 178.35.
    (5) Welding procedures and operations must be qualified in 
accordance with CGA Pamphlet C-3 (incorporated by reference; see 
Sec. 171.7 of this subchapter). In addition, an impact test of the weld 
must be performed in accordance with paragraph (l) of this section as 
part of the qualification of each welding procedure and operator.
    (e) Welding. Welding of the cylinder must be as follows:
    (1) All seams of the cylinder must be fusion welded. A means must be 
provided for accomplishing complete penetration of the joint. Only butt 
or joggle butt joints for the cylinder seams are authorized. All joints 
in the cylinder must have reasonably true alignment.
    (2) All attachments to the sidewalls and heads of the cylinder must 
be by fusion welding and must be of a weldable material complying with 
the impact requirements of paragraph (l) of this section.
    (3) For welding the cylinder, each procedure and operator must be 
qualified in accordance with the sections of CGA Pamphlet C-3 
(incorporated by reference; see Sec. 171.7 of this subchapter)

[[Page 812]]

that apply. In addition, impact tests of the weld must be performed in 
accordance with paragraph (l) of this section as part of the 
qualification of each welding procedure and operator.
    (4) Brazing, soldering and threading are permitted only for joints 
not made directly to the cylinder body. Threads must comply with the 
requirements of paragraph (h) of this section.
    (f) Wall thickness. The minimum wall thickness of the cylinder must 
be such that the calculated wall stress at the minimum required test 
pressure may not exceed the least value of the following:
    (1) 45,000 psi.
    (2) One-half of the minimum tensile strength across the welded seam 
determined in paragraph (l) of this section.
    (3) One-half of the minimum tensile strength of the base metal 
determined as required in paragraph (j) of this section.
    (4) The yield strength of the base metal determined as required in 
paragraph (l) of this section.
    (5) Further provided that wall stress for cylinders having 
longitudinal seams may not exceed 85 percent of the above value, 
whichever applies.
    (6) Calculation must be made by the following formula:

S = [P(1.3D2 + 0.4d2)] / (D2 - 
    d2)

where:

S = wall stress in pounds psi;
P = minimum test pressure prescribed for pressure test in psig;
D = outside diameter in inches;
d = inside diameter in inches.

    (g) Heat treatment. Heat treatment is not permitted.
    (h) Openings in cylinder. Openings in cylinders must conform to the 
following:
    (1) Openings are permitted in heads only. They must be circular and 
may not exceed 3 inches in diameter or one third of the cylinder 
diameter, whichever is less. Each opening in the cylinder must be 
provided with a fitting, boss or pad, either integral with, or securely 
attached to, the cylinder body by fusion welding. Attachments to a 
fitting, boss or pad may be made by welding, brazing, mechanical 
attachment, or threading.
    (2) Threads must comply with the following:
    (i) Threads must be clean-cut, even, without checks and cut to 
gauge.
    (ii) Taper threads to be of a length not less than that specified 
for NPT.
    (iii) Straight threads must have at least 4 engaged threads, tight 
fit and calculated shear strength at least 10 times the test pressure of 
the cylinder. Gaskets, which prevent leakage and are inert to the 
hazardous material, are required.
    (i) Pressure test. Each cylinder, before insulating and jacketing, 
must be examined under a pressure of at least 2 times the service 
pressure maintained for at least 30 seconds without evidence of leakage, 
visible distortion or other defect. The pressure gauge must permit 
reading to an accuracy of 1 percent.
    (j) Physical test. A physical test must be conducted to determine 
yield strength, tensile strength, and elongation as follows:
    (1) The test is required on 2 specimens selected from material of 
each heat and in the same condition as that in the completed cylinder.
    (2) Specimens must conform to the following:
    (i) A gauge length of 8 inches with a width not over 1\1/2\ inches, 
a gauge length of 2 inches with width not over 1\1/2\ inches, or a gauge 
length at least 24 times thickness with a width not over 6 times 
thickness (authorized when cylinder wall is not over \1/16\ inch thick).
    (ii) The specimen, exclusive of grip ends, may not be flattened. 
Grip ends may be flattened to within one inch of each end of the reduced 
section.
    (iii) When size of the cylinder does not permit securing straight 
specimens, the specimens may be taken in any location or direction and 
may be straightened or flattened cold by pressure only, not by blows. 
When specimens are so taken and prepared, the inspector's report must 
show in connection with record of physical tests detailed information in 
regard to such specimens.
    (iv) Heating of a specimen for any purpose is not authorized.
    (3) The yield strength in tension must be the stress corresponding 
to a permanent strain of 0.2 percent of the gauge length. The following 
conditions apply:

[[Page 813]]

    (i) The yield strength must be determined by either the ``offset'' 
method or the ``extension under load'' method as prescribed in ASTM E 8 
(incorporated by reference; see Sec. 171.7 of this subchapter).
    (ii) In using the ``extension under load'' method, the total strain 
(or ``extension under load''), corresponding to the stress at which the 
0.2 percent permanent strain occurs may be determined with sufficient 
accuracy by calculating the elastic expansion of the gauge length under 
appropriate load and adding thereto 0.2 percent of the gauge length. 
Elastic extension calculations must be based on the elastic modulus of 
the material used. In the event of controversy, the entire stress-strain 
diagram must be plotted and the yield strength determined from the 0.2 
percent offset.
    (iii) For the purpose of strain measurement, the initial strain 
reference must be set while the specimen is under a stress of 12,000 psi 
and the strain indicator reading being set at the calculated 
corresponding strain.
    (iv) Cross-head speed of the testing machine may not exceed \1/8\ 
inch per minute during yield strength determination.
    (k) Acceptable results for physical tests. Physical properties must 
meet the limits specified in paragraph (o)(1), table 1, of this section, 
for the particular steel in the annealed condition. The specimens must 
show at least a 20 percent elongation for a 2-inch gage length. Except 
that the percentage may be reduced numerically by 2 for each 7,500 psi 
increment of tensile strength above 100,000 psi to a maximum of 5 such 
increments. Yield strength and tensile strength must meet the 
requirements of paragraph (o)(1), table 1, of this section.
    (l) Tests of welds. Welds must be tested as follows:
    (1) Tensile test. A specimen must be cut from one cylinder of each 
lot of 200 or less, or welded test plate. The welded test plate must be 
of one of the heats in the lot of 200 or less which it represents, in 
the same condition and approximately the same thickness as the cylinder 
wall except that it may not be of a lesser thickness than that required 
for a quarter size Charpy impact specimen. The weld must be made by the 
same procedures and subjected to the same heat treatment as the major 
weld on the cylinder. The specimen must be taken across the major seam 
and must be prepared in accordance with and must meet the requirements 
of CGA Pamphlet C-3 (incorporated by reference; see Sec. 171.7 of this 
subchapter). Should this specimen fail to meet the requirements, 
specimens may be taken from two additional cylinders or welded test 
plates from the same lot and tested. If either of the latter specimens 
fails to meet the requirements, the entire lot represented must be 
rejected.
    (2) Guided bend test. A ``root'' bend test specimen must be cut from 
the cylinder or welded test plate, used for the tensile test specified 
in paragraph (l)(1) of this section and from any other seam or 
equivalent welded test plate if the seam is welded by a procedure 
different from that used for the major seam. Specimens must be taken 
across the particular seam being tested and must be prepared and tested 
in accordance with and must meet the requirements of CGA Pamphlet C-3 
(incorporated by reference; see Sec. 171.7 of this subchapter).
    (3) Alternate guided-bend test. This test may be used and must be as 
specified in CGA Pamphlet C-3 (incorporated by reference; see Sec. 171.7 
of this subchapter). The specimen must be bent until the elongation at 
the outer surface, adjacent to the root of the weld, between the lightly 
scribed gage lines a to b, is at least 20 percent, except that this 
percentage may be reduced for steels having a tensile strength in excess 
of 100,000 psig, as provided in paragraph (c) of this section.
    (4) Impact tests. One set of three impact test specimens (for each 
test) must be prepared and tested for determining the impact properties 
of the deposited weld metal--
    (i) As part of the qualification of the welding procedure.
    (ii) As part of the qualification of the operators.
    (iii) For each ``heat'' of welding rodor wire used.

[[Page 814]]

    (iv) For each 1,000 feet of weld made with the same heat of welding 
rod or wire.
    (v) All impact test specimens must be of the charpy type, keyhole or 
milled U-notch, and must conform in all respects to ASTM E 23 
(incorporated by reference; see Sec. 171.7 of this subchapter). Each set 
of impact specimens must be taken across the weld and have the notch 
located in the weld metal. When the cylinder material thickness is 2.5 
mm or thicker, impact specimens must be cut from a cylinder or welded 
test plate used for the tensile or bend test specimens. The dimension 
along the axis of the notch must be reduced to the largest possible of 
10 mm, 7.5 mm, 5 mm or 2.5 mm, depending upon cylinder thickness. When 
the material in the cylinder or welded test plate is not of sufficient 
thickness to prepare 2.5 mm impact test specimens, 2.5 mm specimens must 
be prepared from a welded test plate made from \1/8\ inch thick material 
meeting the requirements specified in paragraph (o)(1), table 1, of this 
section and having a carbon analysis of .05 minimum, but not necessarily 
from one of the heats used in the lot of cylinders. The test piece must 
be welded by the same welding procedure as used on the particular 
cylinder seam being qualified and must be subjected to the same heat 
treatment.
    (vi) Impact test specimens must be cooled to the design service 
temperature. The apparatus for testing the specimens must conform to 
requirements of ASTM Standard E 23 (incorporated by reference; see 
Sec. 171.7 of this subchapter). The test piece, as well as the handling 
tongs, must be cooled for a length of time sufficient to reach the 
service temperature. The temperature of the cooling device must be 
maintained within a range of plus or minus 3  deg.F. The specimen must 
be quickly transferred from the cooling device to the anvil of the 
testing machine and broken within a time lapse of not more than six 
seconds.
    (vii) The impact properties of each set of impact specimens may not 
be less than the values in the following table:

------------------------------------------------------------------------
                                                     Minimum
                                                      impact    Minimum
                                                      value      impact
                                                     required    value
                                                     for avg.  permitted
                 Size of specimen                    of each     on one
                                                      set of   only of a
                                                      three      set of
                                                    specimens    three
                                                    (ft.-lb.)  (ft.-lb.)
------------------------------------------------------------------------
10 mmx10 mm.......................................       15         10
10 mmx7.5 mm......................................       12.5        8.5
10 mmx5 mm........................................       10          7.0
10 mmx2.5 mm......................................        5          3.5
------------------------------------------------------------------------

    (viii) When the average value of the three specimens equals or 
exceeds the minimum value permitted for a single specimen and the value 
for more than one specimen is below the required average value, or when 
the value for one specimen is below the minimum value permitted for a 
single specimen, a retest of three additional specimens must be made. 
The value of each of these retest specimens must equal or exceed the 
required average value. When an erratic result is caused by a defective 
specimen, or there is uncertainty in test procedure, a retest is 
authorized.
    (m) Radiographic examination. Cylinders must be subject to a 
radiographic examination as follows:
    (1) The techniques and acceptability of radiographic inspection must 
conform to the standards set forth in CGA Pamphlet C-3 (incorporated by 
reference; see Sec. 171.7 of this subchapter).
    (2) One finished longitudinal seam must be selected at random from 
each lot of 100 or less successively produced and be radiographed 
throughout its entire length. Should the radiographic examination fail 
to meet the requirements of paragraph (m)(1) of this section, two 
additional seams of the same lot must be examined, and if either of 
these fail to meet the requirements of (m)(1) of this section, only 
those passing are acceptable.
    (n) Rejected cylinders. Reheat treatment of rejected cylinders is 
authorized. Subsequent thereto, cylinders must pass all prescribed tests 
to be acceptable. Welds may be repaired by suitable methods of fusion 
welding.
    (o) Authorized materials of construction. Authorized materials of 
construction are as follows:

[[Page 815]]

    (1) Inner containment vessel (cylinder). Electric furnace steel of 
uniform quality must be used. Chemical analysis must conform to ASTM A 
240/A 240M (incorporated by reference; see Sec. 171.7 of this 
subchapter), Type 304 stainless steel. Chemical analysis must conform to 
ASTM A240, Type 304 Stainless Steel. A heat of steel made under table 1 
and table 2 in this paragraph (o)(1) is acceptable, even though its 
check chemical analysis is slightly out of the specified range, if it is 
satisfactory in all other respects, provided the tolerances shown in 
table 3 in this paragraph (o)(1) are not exceeded. The following 
chemical analyses and physical properties are authorized:

                      Table 1--Authorized Materials
------------------------------------------------------------------------
                                           Chemical analysis, limits in
              Designation                            percent
------------------------------------------------------------------------
Carbon \1\.............................  0.08 max.
Manganese..............................  2.00 max.
Phosphorus.............................  0.045 max.
Sulphur................................  0.030 max.
Silicon................................  1.00 max.
Nickel.................................  8.00-10.50.
Chromium...............................  18.00-20.00.
Molybdenum.............................  None.
Titanium...............................  None.
Columbium..............................  None.
------------------------------------------------------------------------
\1\ The carbon analysis must be reported to the nearest hundredth of one
  percent.


                      Table 2--Physical Properties
------------------------------------------------------------------------
                                                               Physical
                                                              properties
                                                              (annealed)
------------------------------------------------------------------------
Tensile strength, p.s.i. (minimum)..........................    75,000
Yield strength, p.s.i. (minimum)............................    30,000
Elongation in 2 inches (minimum) percent....................        30.0
Elongation other permissible gauge lengths (minimum) percent        15.0
------------------------------------------------------------------------


                                       Table 3--Check Analysis Tolerances
----------------------------------------------------------------------------------------------------------------
                                                                                                      Tolerance
                                                                                                      over the
                                                                                                       maximum
               Elements                             Limit or specified range (percent)                limit or
                                                                                                      under the
                                                                                                       minimum
                                                                                                        limit
----------------------------------------------------------------------------------------------------------------
Carbon...............................  To 0.030, incl.............................................         0.005
                                       Over 0.30 to 0.20, incl....................................         0.01
Manganese............................  To 1.00 incl...............................................          .03
                                       Over 1.00 to 3.00, incl....................................         0.04
Phosphorus \1\.......................  To 0.040, incl.............................................         0.005
                                       Over 0.040 to 0.020 incl...................................         0.010
Sulphur..............................  To .40 incl................................................         0.005
Silicon..............................  To 1.00, incl..............................................         0.05
Nickel...............................  Over 5.00 to 10.00, incl...................................         0.10
                                       Over 10.00 to 20.00, incl..................................         0.15
Chromium.............................  Over 15.00 to 20.00, incl..................................         0.20
----------------------------------------------------------------------------------------------------------------
\1\ Rephosphorized steels not subject to check analysis for phosphorus.

    (2) Outer jacket. (i) Nonflammable cryogenic liquids. Cylinders 
intended for use in the transportation of nonflammable cryogenic liquid 
must have an outer jacket made of steel or aluminum.
    (ii) Flammable cryogenic liquids. Cylinders intended for use in the 
transportation of flammable cryogenic liquid must have an outer jacket 
made of steel.
    (p) Markings. (1) Markings must be stamped plainly and permanently 
on shoulder or top head of jacket or on a permanently attached plate or 
head protective ring.
    (2) The letters ``ST'', followed by the design service temperature 
(for example, ST-423F), must be marked on cylinders having a design 
service temperature of colder than minus 320  deg.F only. Location to be 
just below the DOT mark.
    (3) The maximum weight of contents, in pounds (for example, ``Max. 
Content 51 ''), must be marked on cylinders having a design 
service temperature colder than minus 320  deg.F only. Location to be 
near symbol.
    (4) Special orientation instructions must be marked on the cylinder 
(for example, THIS END UP), if the cylinder is used in an orientation 
other

[[Page 816]]

than vertical with openings at the top of the cylinder.
    (5) If the jacket of the cylinder is constructed of aluminum, the 
letters ``AL'' must be marked after the service pressure marking. 
Example: DOT-4L150 AL.
    (6) Except for serial number and jacket material designation, each 
marking prescribed in this paragraph (p) must be duplicated on each 
cylinder by any suitable means.
    (q) Inspector's report. In addition to the information required by 
Sec. 178.35, the inspector's reports must contain information on:
    (1) The jacket material and insulation type;
    (2) The design service temperature

(  deg.F); and
    (3) The impact test results, on a lot basis.

[Amdt. 178-114, 61 FR 25942, May 23, 1996, as amended at 66 FR 45386-
45388, Aug. 28, 2001; 67 FR 51653, Aug. 8, 2002]