[Code of Federal Regulations]
[Title 49, Volume 3]
[Revised as of October1, 2002]
From the U.S. Government Printing Office via GPO Access
[CITE: 49CFR193.2441]

[Page 100]
 
                        TITLE 49--TRANSPORTATION
 
 CHAPTER I--RESEARCH AND SPECIAL PROGRAMS ADMINISTRATION, DEPARTMENT OF 
                       TRANSPORTATION (CONTINUED)
 
PART 193--LIQUEFIED NATURAL GAS FACILITIES: FEDERAL SAFETY STANDARDS--Table of Contents
 
                          Subpart E--Equipment
 
Sec. 193.2441  Control center.

    Each LNG plant must have a control center from which operations and 
warning devices are monitored as required by this part. A control center 
must have the following capabilities and characteristics:
    (a) It must be located apart or protected from other LNG facilities 
so that it is operational during a controllable emergency.
    (b) Each remotely actuated control system and each automatic 
shutdown control system required by this part must be operable from the 
control center.
    (c) Each control center must have personnel in continuous attendance 
while any of the components under its control are in operation, unless 
the control is being performed from another control center which has 
personnel in continuous attendance.
    (d) If more than one control center is located at an LNG Plant, each 
control center must have more than one means of communication with each 
other center.
    (e) Each control center must have a means of communicating a warning 
of hazardous conditions to other locations within the plant frequented 
by personnel.

[[Page 101]]