[Code of Federal Regulations] [Title 49, Volume 3] [Revised as of October1, 2002] From the U.S. Government Printing Office via GPO Access [CITE: 49CFR193.2615] [Page 105] TITLE 49--TRANSPORTATION CHAPTER I--RESEARCH AND SPECIAL PROGRAMS ADMINISTRATION, DEPARTMENT OF TRANSPORTATION (CONTINUED) PART 193--LIQUEFIED NATURAL GAS FACILITIES: FEDERAL SAFETY STANDARDS--Table of Contents Subpart G--Maintenance Sec. 193.2615 Isolating and purging. (a) Before personnel begin maintenance activities on components handling flammable fluids which are isolated for maintenance, the component must be purged in accordance with a procedure which meets the requirements of AGA ``Purging Principles and Practices,'' unless the maintenance procedures under Sec. 193.2605 provide that the activity can be safely performed without purging. (b) If the component or maintenance activity provides an ignition source, a technique in addition to isolation valves (such as removing spool pieces or valves and blank flanging the piping, or double block and bleed valving) must be used to ensure that the work area is free of flammable fluids.