Sec. 236.107  Ground tests.

    (a) Except as provided in paragraph (b) of this section, a test for 
grounds on each energy bus furnishing power to circuits, the functioning 
of which affects the safety of train operation, shall be made when such 
energy bus is placed in service, and shall be made at least once every 
three months thereafter.
    (b) The provisions of this rule shall not apply to track circuit 
wires, common return wires of grounded common single-break circuits, or 
alternating

[[Page 496]]

current power distribution circuits grounded in the interest of safety.

[49 FR 3384, Jan. 26, 1984]