Sec. 236.57  Shunt and fouling wires.

    (a) Except as provided in paragraph (b) of this section, shunt wires 
and fouling wires hereafter installed or replaced shall consist of at 
least two discrete conductors, and each shall be of sufficient 
conductivity and maintained in such condition that the track relay will 
be in deenergized position, or device that functions as a track relay 
will be in its most restrictive state, when the circuit is shunted.
    (b) This rule does not apply to shunt wires where track or control 
circuit is opened by the switch circuit controller.

[49 FR 3383, Jan. 26, 1984]