                          TITLE 7--AGRICULTURE
 
    CHAPTER XVII--RURAL UTILITIES SERVICE, DEPARTMENT OF AGRICULTURE
 
PART 1724--ELECTRIC ENGINEERING, ARCHITECTURAL SERVICES AND DESIGN POLICIES AND PROCEDURES--Table of Contents
 
                    Subpart E--Electric System Design
 
Sec. 1724.50  Compliance with National Electrical Safety Code (NESC).


    The provisions of this section apply to all borrower electric system 
facilities regardless of the source of financing.
    (a) A borrower shall ensure that its electric system, including all 
electric distribution, transmission, and generating facilities, is 
designed, constructed, operated, and maintained in accordance with all 
applicable provisions of the most current and accepted criteria of the 
National Electrical Safety Code (NESC) and all applicable and current 
electrical and safety requirements of any State or local governmental 
entity. Copies of the NESC may be obtained from the Institute of 
Electrical and Electronic Engineers, Inc., 445 Hoes Lane, Piscataway, NJ 
08855. This requirement applies to the borrower's electric system 
regardless of the source of financing.
    (b) Any electrical standard requirements established by RUS are in 
addition to, and not in substitution for or a modification of, the most 
current and accepted criteria of the NESC and any applicable electrical 
or safety requirements of any State or local governmental entity.
    (c) Overhead distribution circuits shall be constructed with not 
less than the Grade C strength requirements as described in Section 26, 
Strength Requirements, of the NESC when subjected to the loads specified 
in NESC Section 25, Loadings for Grades B and C. Overhead transmission 
circuits shall be constructed with not less than the Grade B strength 
requirements as described in NESC Section 26.