[Code of Federal Regulations]
[Title 7, Volume 11]
[Revised as of January 1, 2003]
From the U.S. Government Printing Office via GPO Access
[CITE: 7CFR1755.200]

[Page 417-445]
 
                          TITLE 7--AGRICULTURE
 
    CHAPTER XVII--RURAL UTILITIES SERVICE, DEPARTMENT OF AGRICULTURE
 
PART 1755--TELECOMMUNICATIONS STANDARDS AND SPECIFICATIONS FOR MATERIALS, EQUIPMENT AND CONSTRUCTION--Table of Contents
 
Sec. 1755.200  RUS standard for splicing copper and fiber optic cables.

    (a) Scope. (1) This section describes approved methods for splicing 
plastic insulated copper and fiber optic cables. Typical applications of 
these methods include aerial, buried, and underground splices.
    (2) American National Standard Institute/National Fire Protection 
Association (ANSI/NFPA) 70, 1993 National Electrical Code (NEC) 
referenced in this section is incorporated by reference by RUS. This 
incorporation by reference was approved by the Director of the Federal 
Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. A copy of 
the ANSI/NFPA 1993 NEC standard is available for inspection during 
normal business hours at RUS, room 2845, U.S. Department of Agriculture, 
Washington, DC 20250-1500 or at the Office of the Federal Register, 800 
North Capitol Street, NW., suite 700, Washington, DC. Copies are 
available from NFPA, Batterymarch Park, Quincy, Massachusetts 02269, 
telephone number 1 (800) 344-3555.
    (3) American National Standard Institute/Institute of Electrical and 
Electronics Engineers, Inc. (ANSI/IEEE), 1993 National Electrical Safety 
Code (NESC) referenced in this section is incorporated by reference by 
RUS. This incorporation by reference was approved by the Director of the 
Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. A 
copy of the ANSI/IEEE 1993 NESC standard is available for inspection 
during normal business hours at RUS, room 2845, U.S. Department of 
Agriculture, Washington, DC 20250-1500 or at the Office of the Federal 
Register, 800 North Capitol Street, NW., suite 700, Washington, DC. 
Copies are available from IEEE Service Center, 455 Hoes Lane, 
Piscataway, New Jersey 08854, telephone number 1 (800) 678-4333.
    (b) General. (1) Only Rural Utilities Service (RUS) accepted filled 
cable and splicing materials shall be used on outside plant projects 
financed by RUS.
    (2) The installation instructions provided by the manufacturer of 
splicing materials shall be followed except where those instructions 
conflict with the procedures specified in this section.

[[Page 418]]

    (3) Precautions shall be taken to prevent the ingress of moisture 
and other contaminants during all phases of the splicing installation. 
When an uncompleted splice must be left unattended, it shall be sealed 
to prevent the ingress of moisture and other contaminants.
    (4) Minor sheath damage during construction may be repaired if the 
repair is completed immediately and approved by the borrower's resident 
project representative. Minor damage is typically repaired by:
    (i) Scuffing the cable sheath associated with the damaged area;
    (ii) Applying several layers of DR tape over the scuffed and damaged 
area;
    (iii) Applying several layers of plastic tape over the DR tape; and
    (iv) If damage is severe enough to rupture the cable shield, a 
splice closure shall be installed.
    (5) All splice cases installed on RUS toll trunk and feeder cables 
shall be filled, whether aerial, buried, or underground.
    (c) Splicing considerations for copper cables--(1) Preconstruction 
testing. It is desirable that each reel of cable be tested for grounds, 
opens, shorts, crosses, and shield continuity before the cable is 
installed. However, manufacturer supplied test results are acceptable. 
All cable pairs shall be free from electrical defects.
    (2) Handling precautions. The cable manufacturer's instructions 
concerning pulling tension and bending radius shall be observed. Unless 
the cable manufacturer's recommendation is more stringent, the minimum 
bending radius shall be 10 times the cable diameter for copper cables 
and 20 times the cable diameter for fiber optic cables.
    (3) Cable sheath removal. (i) The length of cable sheath to be 
removed shall be governed by the type of splicing hardware used. Follow 
the splice case manufacturer's recommendations. For pedestals or large 
pair count splice housings, consider removing enough cable sheath to 
allow the conductors to extend to the top of the pedestal and then to 
hang downward to approximately 15 centimeters (cm) (6 inches (in.)) 
above the baseplate.
    (ii) Caution shall be exercised to avoid damaging the conductor 
insulation when cutting through the cable shield and removing the 
shield. Sharp edges and burrs shall be removed from the cut end of the 
shield.
    (4) Shield bonding and grounding. For personnel safety, the shields 
of the cables to be spliced shall be bonded together and grounded before 
splicing activities are started. (See paragraphs (g)(2), and (g)(5)(i) 
through (g)(5)(iii) of this section for final bonding and grounding 
provisions.)
    (5) Binder group identification. (i) Color coded plastic tie wraps 
shall be placed loosely around each binder group of cables before 
splicing operations are attempted. The tie wraps shall be installed as 
near the cable sheath as practicable and shall conform to the same color 
designations as the binder ribbons. Twisted wire pigtails shall not be 
used to identify binder groups due to potential transmission 
degradation.
    (ii) The standard insulation color code used to identify individual 
cable pairs within 25-pair binder groups shall be as shown in Table 1:

         Table 1--Cable Pair Identification Within Binder Groups
------------------------------------------------------------------------
                                                    Color
             Pair No.              -------------------------------------
                                            Tip               Ring
------------------------------------------------------------------------
1.................................  White.............  Blue.
2.................................  White.............  Orange.
3.................................  White.............  Green.
4.................................  White.............  Brown.
5.................................  White.............  Slate.
6.................................  Red...............  Blue.
7.................................  Red...............  Orange.
8.................................  Red...............  Green.
9.................................  Red...............  Brown.
10................................  Red...............  Slate.
11................................  Black.............  Blue.
12................................  Black.............  Orange.
13................................  Black.............  Green.
14................................  Black.............  Brown.
15................................  Black.............  Slate.
16................................  Yellow............  Blue.
17................................  Yellow............  Orange.
18................................  Yellow............  Green.
19................................  Yellow............  Brown.
20................................  Yellow............  Slate.
21................................  Violet............  Blue.
22................................  Violet............  Orange.
23................................  Violet............  Green.
24................................  Violet............  Brown.
25................................  Violet............  Slate.
------------------------------------------------------------------------

    (iii) The standard binder ribbon color code used to designate 25-
pair binder

[[Page 419]]

groups within 600-pair super units shall be as shown in Table 2:

               Table 2--Cable Binder Group Identification
------------------------------------------------------------------------
                                                              Group pair
            Group No.                  Color of bindings         count
------------------------------------------------------------------------
1................................  White-Blue...............       1-25
2................................  White-Orange.............      26-50
3................................  White-Green..............      51-75
4................................  White-Brown..............      76-100
5................................  White-Slate..............     101-125
6................................  Red-Blue.................     126-150
7................................  Red-Orange...............     151-175
8................................  Red-Green................     176-200
9................................  Red-Brown................     201-225
10...............................  Red-Slate................     226-250
11...............................  Black-Blue...............     251-275
12...............................  Black-Orange.............     276-300
13...............................  Black-Green..............     301-325
14...............................  Black-Brown..............     326-350
15...............................  Black-Slate..............     351-375
16...............................  Yellow-Blue..............     376-400
17...............................  Yellow-Orange............     401-425
18...............................  Yellow-Green.............     426-450
19...............................  Yellow-Brown.............     451-475
20...............................  Yellow-Slate.............     476-500
21...............................  Violet-Blue..............     501-525
22...............................  Violet-Orange............     526-550
23...............................  Violet-Green.............     551-575
24...............................  Violet-Brown.............     576-600
------------------------------------------------------------------------

    (iv) Super-unit binder groups shall be identified in accordance with 
Table 3:

                    Table 3--Super-Unit Binder Colors
------------------------------------------------------------------------
                Pair numbers                         Binder color
------------------------------------------------------------------------
1-600......................................  White.
601-1200...................................  Red.
1201-1800..................................  Black.
1801-2400..................................  Yellow.
2401-3000..................................  Violet.
3001-3600..................................  Blue.
3601-4200..................................  Orange.
4201-4800..................................  Green.
4801-5400..................................  Brown.
5401-6000..................................  Slate.
------------------------------------------------------------------------

    (v) Service pairs in screened cables shall be identified in 
accordance with Table 4:

           Table 4--Screened Cable Service Pair Identification
------------------------------------------------------------------------
                                                    Color
         Service pair No.          -------------------------------------
                                            Tip               Ring
------------------------------------------------------------------------
1.................................  White.............  Red.
2.................................  White.............  Black.
3.................................  White.............  Yellow.
4.................................  White.............  Violet.
                                    Red...............  Black.
6.................................  Red...............  Yellow.
7.................................  Red...............  Violet.
8.................................  Black.............  Yellow.
9.................................  Black.............  Violet.
------------------------------------------------------------------------

    (6) Cleaning conductors. It is not necessary to remove the filling 
compound from cable conductors before splicing. However, it is 
permissible to wipe individual conductors with clean paper towels or 
clean cloth rags. No cleaning chemicals, etc., shall be used. Caution 
shall be exercised to maintain individual cable pair and binder group 
identity. Binder group identity shall be maintained by using color coded 
plastic tie wraps. Individual pair identification shall be maintained by 
carefully twisting together the two conductors of each pair.
    (7) Expanded plastic insulated conductor (PIC) precautions. Solid 
PIC and expanded (foam or foam skin) PIC are spliced in the same manner, 
using the same tools and materials and, in general, should be treated 
the same. However, the insulation on expanded PIC is much more fragile 
than solid PIC. Twisting or forming expanded PIC into extremely compact 
splice bundles and applying excessive amounts of tension when tightening 
tie wraps causes shiners and, thus shall be avoided.
    (8) Splice connectors. (i) Only RUS accepted filled splice 
connectors shall be used on outside plant projects financed by RUS.
    (ii) Specialized connectors are available for splicing operations 
such as butt splices, in line splices, bridge taps, clearing and 
capping, and multiple pair splicing operations. The splice connector 
manufacturer's recommendations shall be followed concerning connector 
selection and use.
    (iii) Caution shall be exercised to maintain conductor and pair 
association both during and after splicing operations.
    (iv) Splicing operations that involve pairs containing working 
services shall utilize splice connectors that permit splicing without 
the interruption of service.
    (9) Piecing out conductors. Conductors may be pieced-out to provide 
additional slack or to repair damaged conductors. However, the 
conductors shall be pieced-out with conductors having the same gauge and 
type and color of insulation. The conductors used for piecing-out shall 
be from cables having RUS acceptance.

[[Page 420]]

    (10) Splice organization. Spliced pair bundles shall be arranged in 
firm lay-ups with minimum conductor tension in accordance with the 
manufacturer's instructions.
    (11) Binder tape. Perforated nonhygroscopic and nonwicking binder 
tape should be applied to splices housed in filled splice cases. The 
binder tape allows the flow of filling compound while holding the splice 
bundles near the center of the splice case to allow adequate coverage of 
filling compound.
    (12) Cable tags. Cables shall be identified by a tag indicating the 
cable manufacturer's name, cable size, date of placement, and generic 
route information. Information susceptible to changes caused by future 
cable throws and rearrangements should not be included. Tags on load 
coil stubs shall include the serial number of the coil case, the 
manufacturer's name, and the inductance value.
    (13) Screened cable. Screened PIC cable is spliced in the same 
manner as nonscreened PIC cable. However, special considerations are 
necessary due to differences in the cable design. The transmit and 
receive bundles of the cable shall be separated and one of the bundles 
shall be wrapped with shielding material in accordance with the cable 
manufacturer's recommendations. When acceptable to the cable 
manufacturer, it is permissible to use either the scrap screening tape 
removed from the cable during the sheath opening process provided the 
screening tape is edge coated or new pressure sensitive aluminum foil 
tape over polyethylene tape.
    (14) Service wire connections. (i) Buried service wires may be 
spliced directly to cable conductors inside pedestals using the same 
techniques required for branch cables. Buried service wires may also be 
terminated on terminal blocks inside pedestals in areas where high 
service order activity or fixed count cable administration policies 
require terminal blocks. However, only RUS accepted terminal blocks 
equipped with grease or gel filled terminations to provide moisture and 
corrosion resistance shall be used.
    (ii) Only filled terminal blocks having RUS acceptance shall be used 
on aerial service wire connections.
    (15) Copper cable testing. Copper cable testing shall be performed 
in accordance with RUS Bulletin 345-63, ``RUS Standard for Acceptance 
Tests and Measurements of Telephone Plant,'' PC-4, (Incorporated by 
reference at Sec. 1755.97).
    (16) Cable acceptance. Installed cable shall be tested and pass the 
inventory and acceptance testing specified in the Telephone System 
Construction Contract (Labor and Materials), RUS Form 515. The tests and 
inspections shall be witnessed by the borrower's resident project 
representative. All conductors shall be free from grounds, shorts, 
crosses, splits, and opens.
    (d) Splice arrangements for copper cables--(1) Service distribution 
closures. (i) Ready access closures permit cable splicing activities and 
the installation of filled terminal blocks for service wire connections 
in the same closure. Ready access designs shall allow service 
technicians direct access to the cable core as well as the terminal 
block.
    (ii) Fixed count terminals shall restrict service technician access 
to the cable core. Predetermined cable pairs shall be spliced to the 
terminal leads or stub cable in advance of service assignments.
    (2) Aerial splices. Aerial splice cases accommodate straight 
splices, branch splices, load coils, and service distribution terminals. 
Aerial splicing arrangements having more than 4 cables spliced in the 
same splice case are not recommended. Stub cabling to a second splice 
case to avoid a congested splice is acceptable.
    (3) Buried splices. (i) Direct buried splice cases accommodate 
straight splices, branch splices, and load coils. Direct buried splices 
shall be filled and shall be used only when above ground splicing in 
pedestals is not practicable.
    (ii) A treated plank or equivalent shall be placed 15 cm (6 in.) 
above the buried splice case to prevent damage to the splice case from 
future digging. Where a firm base for burying a splice cannot be 
obtained, a treated plank or equivalent shall be placed beneath the 
splice case.
    (iii) Each buried splice shall be identified for future locating. 
One method of marking the splice point is the use

[[Page 421]]

of a warning sign. Another method is the burying of an electronic 
locating device.
    (4) BD-type pedestals. (i) BD-type pedestals are housings primarily 
intended to house, organize, and protect cable terminations 
incorporating splice connectors, ground lugs, and load coils. Activities 
typically performed in pedestals are cable splicing, shield bonding and 
grounding, loading, and connection of subscriber service drops.
    (ii) The recommended splice capacities for BD-type pedestals are 
shown in Table 5. However, larger size pedestals are permissible if 
service requirements dictate their usefulness. Table 5 is as follows:

            Table 5--Splice Capacities for BD-Type Pedestals
------------------------------------------------------------------------
                                                          Maximum load
                                    Maximum straight       splice pair
                                  splice pair capacity   capacity using
                                    using single pair      single pair
          Pedestal type               connectors or       connectors or
                                  multiple pair splice    multiple pair
                                         modules         splice modules
                                                          (see note 1)
------------------------------------------------------------------------
BD3, BD3A.......................  100 Pair............  50 Pair.
BD4, BD4A.......................  200 Pair............  100 Pair.
BD5, BD5A.......................  600 Pair............  300 Pair.
BD7.............................  1200 Pair...........  600 Pair.
BD14, BD14A.....................  100 Pair............  50 Pair.
BD15, BD15A.....................  400 Pair............  200 Pair.
BD16, BD16A.....................  600 Pair............  300 Pair.
------------------------------------------------------------------------
Note 1: This table refers to load coil cases that are to be direct
  buried with stub cables extending into the pedestal for splicing.
  Requirements involving individual coil arrangements inside the
  pedestal should be engineered on a case-by-case basis.

    (iii) Special distribution pedestals having a divider plate for 
mounting filled terminal blocks are available. Distribution pedestals 
are also equipped with service wire channels for installation of buried 
service wires without disturbing the cabling and gravel inside the base 
of the pedestal. Distribution pedestals are recommended in locations 
where the connection of service wires is required.
    (5) Large pair count splice housings. Large pair count splice 
housings are recommended for areas not suitable for man- holes. The 
recommended capacities are shown in Table 6:

           Table 6--Splice Capacities for Large Count Housings
------------------------------------------------------------------------
                                                          Maximum load
                                   Maximum straight       splice pair
                                 splice pair capacity    capacity using
                                  using single pair       single pair
         Housing type               connectors or        connectors or
                                 multiple pair splice    multiple pair
                                       modules           splice modules
                                                          (see note 1)
------------------------------------------------------------------------
BD 6000.......................  6,000 Pair...........  3,000 Pair.
BD 8000.......................  8,000 Pair...........  4,000 Pair.
BD 10000......................  10,000 Pair..........  5,000 Pair.
------------------------------------------------------------------------

    (6) Pedestal restricted access inserts. Restricted access inserts 
may be used to protect splices susceptible to unnecessary handling where 
subsequent work activities are required or expected to occur after 
splices have been completed. Restricted access inserts also provide 
moisture protection in areas susceptible to temporary flooding. A 
typical restricted access insert is shown in Figure 1:

[[Page 422]]

[GRAPHIC] [TIFF OMITTED] TR26JA95.002

    (7) Serving Area Interface (SAI) Systems. SAI systems provide the 
cross-connect point between feeder and distribution cables. Connection 
of feeder to distribution pairs is accomplished by placing jumpers 
between connecting blocks. Only RUS accepted connecting blocks having 
grease or gel filled terminations to provide moisture and corrosion 
resistance shall be used.
    (8) Buried cable splicing arrangements. Typical buried cable 
splicing arrangements are illustrated in Figures 2 through 5:

[[Page 423]]

[GRAPHIC] [TIFF OMITTED] TR26JA95.003


[[Page 424]]


[GRAPHIC] [TIFF OMITTED] TR26JA95.004


[[Page 425]]


[GRAPHIC] [TIFF OMITTED] TR26JA95.005


[[Page 426]]


[GRAPHIC] [TIFF OMITTED] TR26JA95.006

    (9) Underground splices (manholes). Underground splice cases 
accommodate straight splices, branch splices, and load coils. 
Underground splices shall be filled.
    (10) Central office tip cable splices. (i) Filled cable or filled 
splices are not recommended for use inside central offices, except in 
cable vault locations. Outside plant cable sheath and cable filling 
compound are susceptible to fire and will support combustion. Fire, 
smoke, and gases generated by these materials during burning are 
detrimental to telephone switching equipment.
    (ii) Tip cables should be spliced in a cable vault. However, as a 
last resort, tip cables may be spliced inside a central office if flame 
retardant splice cases or a noncombustible central office splice housing 
is used to contain the splice.
    (iii) Splices inside the central office shall be made as close as 
practical to

[[Page 427]]

the point where the outside plant cables enter the building. Except in 
cable vault locations, outside plant cables within the central office 
shall be wrapped with fireproof tape or enclosed in noncombustible 
conduit.
    (e) Splicing considerations for fiber optic cables--(1) Connection 
characteristics. Splicing efficiency between optical fibers is a 
function of light loss across the fiber junctions measured in decibels 
(dB). A loss of 0.2 dB in a splice corresponds to a light transmission 
efficiency of approximately 95.5 percent.
    (2) Fiber core alignment. Fiber splicing techniques shall be 
conducted in such a manner that the cores of the fibers will be aligned 
as perfectly as possible to allow maximum light transmission from one 
fiber to the next. Without proper alignment, light will leave the fiber 
core and travel through the fiber cladding. Light outside the fiber core 
is not a usable light signal. Core misalignment is illustrated in Figure 
6:
[GRAPHIC] [TIFF OMITTED] TR26JA95.007

    (3) Splice loss. (i) Splice loss can also be caused by fiber defects 
such as nonidentical core diameters, cores not in center of the fiber, 
and noncircular cores. Such defects are depicted in Figure 7:

[[Page 428]]

[GRAPHIC] [TIFF OMITTED] TR26JA95.008

    (ii) Undesirable splice losses are caused by poor splicing 
techniques including splicing irregularities such as improper cleaves 
and dirty splices. Typical cleave problems are illustrated in Figure 8:

[[Page 429]]

[GRAPHIC] [TIFF OMITTED] TR26JA95.009

    (4) Handling precautions. The following precautions shall be 
observed:
    (i) Avoid damaging the cable during handling operations prior to 
splicing. Minor damage may change the transmission characteristics of 
the fibers to the extent that the cable section will have to be 
replaced;
    (ii) The cable manufacturer's recommendations concerning pulling 
tension shall be observed. The maximum pulling tension for most fiber 
optic cable is 2669 newtons (600 pound-force);
    (iii) The cable manufacturer's recommendations concerning bending 
radius shall be observed. Unless the cable manufacturer's recommendation 
is more stringent, the minimum bending radius for fiber optic cable 
shall be 20 times the cable diameter;
    (iv) The cable manufacturer's recommendations concerning buffer tube 
bending radius shall be observed. Unless the cable manufacturer's 
recommendation is more stringent, the minimum bending radius for buffer 
tubes is usually between 38 millimeters (mm) (1.5 in.) and 76 mm (3.0 
in.). The bending limitations on buffer tubes are intended to prevent 
kinking. Buffer tube kinking may cause excessive optical loss or fiber 
breakage; and
    (v) Handle unprotected glass fibers carefully to avoid introducing 
flaws such as scratched or broken fibers.
    (5) Personnel safety. The following safety precautions shall be 
observed:
    (i) Safety glasses shall be worn when handling glass fibers;

[[Page 430]]

    (ii) Never view open-ended fibers with the naked eye or a magnifying 
device. Improper viewing of a fiber end that is transmitting light may 
cause irreparable eye damage; and
    (iii) Dispose of bare scrap fibers by using the sticky side of a 
piece of tape to pick up and discard loose fiber ends. Fiber scraps 
easily penetrate the skin and are difficult to remove.
    (6) Equipment requirements. (i) Fiber optic splices shall be made in 
areas where temperature, humidity, and cleanliness can be controlled. 
Both fusion and mechanical splicing techniques may require a splicing 
vehicle equipped with a work station that will allow environmental 
control.
    (ii) Both fusion and mechanical splicing techniques are permitted on 
RUS financed projects. When using the mechanical splicing technique, 
only RUS accepted mechanical fiber optic splice connectors can be used.
    (iii) Fusion splicing machines shall be kept in proper working 
condition. Regular maintenance in accordance with the machine 
manufacturer's recommendations shall be observed.
    (iv) Mechanical splicing tools shall be in conformance with the tool 
manufacturer's recommendations.
    (v) An optical time domain reflectometer (OTDR) shall be used for 
testing splices. The OTDR shall be stationed at the central office or 
launch point for testing individual splices as they are made and for 
end-to-end signature tests for the fiber optic link.
    (vi) An optical power meter shall be used for end-to-end cable 
acceptance tests.
    (vii) A prerequisite for the successful completion of a fiber optic 
splicing endeavor is the presence of a talk circuit between the splicing 
technician in the splicing vehicle and the operator of the OTDR in the 
central office. The splicing technician and the OTDR operator shall have 
access to communications with each other in order to inform each other 
as to:
    (A) Which splices meet the loss objectives;
    (B) The sequence in which buffer tubes and fibers are to be selected 
for subsequent splicing operations; and
    (C) The timing required for the performance of OTDR testing to 
prevent making an OTDR test at the same time a splice is being fused.
    (7) Cable preparation. (i) Engineering work prints shall prescribe 
the cable slack needed at splice points to reach the work station inside 
the splicing vehicle. Consideration should be given to the slack 
required for future maintenance activity as well as initial construction 
activities. The required slack may be different for each splice point, 
depending on the site logistics. However, the required slack is seldom 
less than 15 meters (50 feet). The amount of slack actually used shall 
be recorded for each splice point to assist future maintenance and 
restoration efforts.
    (ii) The splice case manufacturer's recommendations concerning the 
amount of cable sheath to be removed shall be followed to facilitate 
splicing operations. The length of the sheath opening shall be 
identified with a wrap of plastic tape.
    (iii) If the cable contains a rip cord, the cable jacket shall be 
ring cut approximately 15 cm (6 in.) from the end and the 15 cm (6 in.) 
of cable jacket shall be removed to expose the rip cord. The rip cord 
shall be used to slit the jacket to the tape mark.
    (iv) If the cable does not contain a rip cord, the cable jacket 
shall be slit using a sheath splitter. No cuts shall be made into the 
cable core nor shall the buffer tubes be damaged.
    (v) If the cable contains an armor sheath, the outer jacket shall be 
opened along the slit and the jacket shall be removed exposing the armor 
sheath. The armor shall be separated at the seam and pulled from the 
cable exposing the inner jacket. The armor shall be removed making 
allowances for a shield bond connector. The inner sheath shall be slit 
using a sheath splitter or rip cord. The cable core shall not be damaged 
nor shall there be any damage to the buffer tubes. The jacket shall be 
peeled back and cut at the end of the slit. The exposed buffer tubes 
shall not be cut, kinked, or bent.
    (vi) After the cable sheath has been removed, the binder tape shall 
be removed from the cable. The cable shall not be crushed or deformed.
    (vii) The buffer tubes shall be unstranded one at a time. The buffer 
tubes shall not be kinked.

[[Page 431]]

    (viii) If the cable is equipped with a strength member, the strength 
member shall be cut to the length recommended by the splice case 
manufacturer.
    (ix) Each buffer tube shall be inspected for kinks, cuts, and flat 
spots. If damage is detected, an additional length of cable jacket shall 
be removed and all of the buffer tubes shall be cut off at the point of 
damage.
    (x) The cable preparation sequence shall be repeated for the other 
cable end.
    (8) Shield bonding and grounding. For personnel safety, the shields 
and metallic strength members of the cables to be spliced shall be 
bonded together and grounded before splicing activities are started. 
(See paragraphs (g)(4), and (g)(5)(i) through (g)(5)(iii) of this 
section for final bonding and grounding provisions).
    (9) Fiber optic color code. The standard fiber optic color code for 
buffer tubes and individual fibers shall be as shown in Table 7:

             Table 7.--Fiber and Buffer Tube Identification
------------------------------------------------------------------------
     Buffer tube and fiber No.                      Color
------------------------------------------------------------------------
 1.................................  Blue.
 2.................................  Orange.
 3.................................  Green.
 4.................................  Brown.
 5.................................  Slate.
 6.................................  White.
 7.................................  Red.
 8.................................  Black.
 9.................................  Yellow.
10.................................  Violet.
11.................................  Rose.
12.................................  Aqua.
13.................................  Blue/Black Tracer.
14.................................  Orange/Black Tracer.
15.................................  Green/Black Tracer.
16.................................  Brown/Black Tracer.
17.................................  Slate/Black Tracer.
18.................................  White/Black Tracer.
19.................................  Red/Black Tracer.
20.................................  Black/Yellow Tracer.
21.................................  Yellow/Black Tracer.
22.................................  Violet/Black Tracer.
23.................................  Rose/Black Tracer.
24.................................  Aqua/Black Tracer.
------------------------------------------------------------------------

    (10) Buffer tube removal. (i) The splice case manufacturer's 
recommendation shall be followed concerning the total length of buffer 
tube to be removed. Identify the length to be removed with plastic tape.
    (ii) Experiment with a scrap buffer tube to determine the cutting 
tool adjustment required to ring cut a buffer tube without damaging the 
fibers.
    (iii) Buffer tubes shall be removed by carefully ring cutting and 
removing approximately 15 to 46 cm (6 to 18 in.) of buffer tube at a 
time. The process shall be repeated until the required length of buffer 
tube has been removed, including the tape identification marker.
    (11) Coated fiber cleaning. (i) Each coated fiber shall be cleaned. 
The cable manufacturer's recommendations shall be followed concerning 
the solvent required to clean the coated fibers. Reagent grade isopropyl 
alcohol is a commonly used cleaning solvent.
    (ii) A tissue or cotton ball shall be soaked in the recommended 
cleaning solvent and the coated fibers shall be carefully wiped one at a 
time using a clean tissue or cotton ball for each coated fiber. Caution 
shall be exercised to avoid removing the coloring agent from the fiber 
coating.
    (12) Fiber coating removal. (i) Fiber coatings shall be removed. In 
accordance with the splicing method used, the splice case manufacturer's 
recommendation shall be followed concerning the length of fiber coating 
to be removed.
    (ii) The recommended length of fiber coating shall be removed only 
on the two fibers to be spliced. Fiber coating removal shall be 
performed on a one-fiber-at-a-time basis as each splice is prepared.
    (13) Bare fiber cleaning. After the fiber coating has been removed, 
the bare fibers shall be cleaned prior to splicing. Each fiber shall be 
wiped with a clean tissue or cotton ball soaked with the cleaning 
solvent recommended by the cable manufacturer. The bare fiber shall be 
wiped one time to minimize fiber damage. Aggressive wiping of bare fiber 
shall be avoided as it lowers the fiber tensile strength.
    (14) Fiber cleaving. Cleaving tools shall be clean and have sharp 
cutting edges to minimize fiber scratches and improper cleave angles. 
Cleaving tools that are recommended by the manufacturer of the splicing 
system shall be used.
    (15) Cleaved fiber handling. The cleaved and cleaned fiber shall not 
be allowed to touch other objects and

[[Page 432]]

shall be inserted into the splicing device.
    (16) Completion of the splice. (i) In accordance with the method of 
splicing selected by the borrower, the splice shall be completed by 
either fusing the splice or by applying the mechanical connector.
    (ii) Each spliced fiber shall be routed through the organizer tray 
one at a time as splices are completed. The fibers shall be organized 
one at a time to prevent tangled spliced fibers. The splice case 
manufacturer's recommendation shall be followed concerning the splice 
tray selection.
    (17) Fiber optic testing. Fiber optic testing shall be performed in 
accordance with RUS Bulletin 345-63, ``RUS Standard for Acceptance Tests 
and Measurements of Telephone Plant,'' PC-4, (Incorporated by reference 
at Sec. 1755.97).
    (18) Cable acceptance. Installed cable shall be tested and pass the 
inventory and acceptance testing specified in the Telephone System 
Construction Contract (Labor and Materials), RUS Form 515. The tests and 
inspections shall be witnessed by the borrower's resident project 
representative.
    (f) Splice arrangements for fiber optic cables--(1) Aerial splices. 
Cable slack at aerial splices shall be stored either on the messenger 
strand, on the pole, or inside a pedestal at the base of the pole. A 
typical arrangement for the storage of slack cable at aerial splices is 
shown in Figure 9:

[[Page 433]]

[GRAPHIC] [TIFF OMITTED] TR26JA95.010

    (2) Buried splices. Buried splices shall be installed in handholes 
to accommodate the splice case and the required splicing slack. An 
alternative to the handhole is a pedestal specifically designed for 
fiber optic splice cases. Typical arrangements for buried cable splices 
are shown in Figures 10 and 11:

[[Page 434]]

[GRAPHIC] [TIFF OMITTED] TR26JA95.011


[[Page 435]]


[GRAPHIC] [TIFF OMITTED] TR26JA95.012

    (3) Underground manhole splices. Underground splices shall be stored 
in manholes on cable hooks and racks fastened to the manhole wall. The 
cable slack shall be stored on cable hooks and racks as shown in Figure 
12:

[[Page 436]]

[GRAPHIC] [TIFF OMITTED] TR26JA95.013

    (4) Central office cable entrance. (i) Filled cable or filled 
splices are not recommended for use inside central offices except in 
cable vault locations. Outside plant cable sheath and cable filling 
compound are susceptible to fire and will support combustion. Fire, 
smoke, and gases generated by these materials during burning are 
detrimental to telephone switching equipment.
    (ii) As a first choice, the outside plant fiber optic cable shall be 
spliced to an all-dielectric fire retardant cable in a cable vault with 
the all-dielectric cable extending into the central office and 
terminating inside a fiber patch panel.
    (iii) As a second choice, the outside plant cable may be spliced 
inside the central office if a flame retardant fiber optic splice case 
or a noncombustible central office splice housing equipped with 
organizer trays is used to contain the splice.
    (iv) In cases referenced in paragraphs (f)(4)(ii) and (f)(4)(iii) of 
this section, as a minimum the fire retardant all-dielectric cable used 
to provide the connection between the cable entrance splice and the 
fiber patch panel shall be listed as Communication Riser Cable (Type 
CMR) in accordance with Sections 800-50 and 800-51(b) of the 1993 
National Electrical Code.
    (v) Splices inside the central office shall be made as close as 
practicable to

[[Page 437]]

the point where the outside plant cables enter the building. Except in 
cable vault locations, outside plant cables within the central office 
shall be wrapped with fireproof tape or enclosed in noncombustible 
conduit.
    (g) Bonding and grounding fiber optic cable, copper cable, and 
copper service wire--(1) Bonding. Bonding is electrically connecting two 
or more metallic items of telephone hardware to maintain a common 
electrical potential. Bonding may involve connections to another 
utility.
    (2) Copper cable shield bond connections. (i) Cable shields shall be 
bonded at each splice location. Only RUS accepted cable shield bond 
connectors shall be used to provide bonding and grounding connections to 
metallic cable shields. The shield bond connector manufacturer's 
instructions shall be followed concerning installation and use.
    (ii)(A) Shield bonding conductors shall be either stranded or 
braided tinned copper wire equivalent to a minimum No. 6 American Wire 
Gauge (AWG) and shall be RUS accepted. The conductor connections shall 
be tinned or of a compatible bimetallic design to avoid corrosion 
problems associated with dissimilar metals. The number of shield bond 
connectors required per pair size and gauge shall be as shown in Table 
8:

        Table 8.--Shield Bond Connectors per Pair Size and Gauge
------------------------------------------------------------------------
                            Pair size and gauge                 No. of
             ------------------------------------------------   shield
   19 AWG                                                        bond
                  22 AWG          24 AWG          26 AWG      connectors
------------------------------------------------------------------------
       0-25           0-100           0-150           0-200            1
      50-100        150-300         200-400         300-600            2
     150-200        400-600         600-900         900-1500           3
     300-600        900-1200       1200-2100       1800-3600           4
------------------------------------------------------------------------

    (B) It is permissible to strap across the shield bond connectors of 
several cables with a single length of braided wire. However, both ends 
of the braid shall be terminated on the pedestal ground bracket to 
provide a bonding loop. Shield bond connection methods for individual 
cables are shown in Figures 13 through 15, and the bonding of several 
cables inside a pedestal using the bonding loop is shown in Figure 16:

[[Page 438]]

[GRAPHIC] [TIFF OMITTED] TR26JA95.014


[[Page 439]]


[GRAPHIC] [TIFF OMITTED] TR26JA95.015


[[Page 440]]


[GRAPHIC] [TIFF OMITTED] TR26JA95.016


[[Page 441]]


[GRAPHIC] [TIFF OMITTED] TR26JA95.017

    (3) Buried service wire shield bond connections. Buried service wire 
shields shall be connected to the pedestal bonding and grounding system. 
Typical buried service wire installations are shown in Figures 17 and 
18. In addition to the methods referenced in Figures 17 and 18, the 
shields of buried service wires may also be connected to the pedestal 
bonding and grounding system using buried service wire bonding harnesses 
listed on Page 3.3.1, Item ``gs-b,'' of RUS Bulletin 1755I-100. RUS 
Bulletin 1755I-100 may be purchased from the

[[Page 442]]

Superintendent of Documents, U.S. Government Printing Office, 
Washington, DC 20402. When those harnesses are used they shall be 
installed in accordance with the manufacturer's instructions. Figures 17 
and 18 are as follows:
[GRAPHIC] [TIFF OMITTED] TR26JA95.018


[[Page 443]]


[GRAPHIC] [TIFF OMITTED] TR26JA95.019

    (4) Fiber optic cable bond connections. (i) The cable shield and 
metallic strength members shall be bonded at each splice location. Only 
RUS accepted fiber optic cable shield bond connectors shall be used to 
provide bonding connections to the metallic cable shields. The shield 
bond connector manufacturer's instructions shall be followed concerning 
installation and use.
    (ii) Shield bonding conductors shall be either stranded or braided 
tinned copper wire equivalent to a minimum No. 6 American Wire Gauge 
(AWG) and shall be RUS accepted. The conductor connections shall be 
tinned or of a compatible bimetallic design to avoid corrosion problems 
associated with dissimilar metals.
    (5) Grounding. (i) Grounding is electrically connecting metallic 
telephone hardware to a National Electrical Safety Code (NESC) 
acceptable grounding electrode. Acceptable grounding electrodes are 
defined in the Rule 99A of the NESC.

[[Page 444]]

    (ii) The conductor used for grounding metallic telephone hardware 
shall be a minimum No. 6 AWG solid, bare, copper conductor.
    (iii) For copper and fiber optic cable plant, all cable shields, all 
metallic strength members, and all metallic hardware shall be:
    (A) Grounded at each splice location to a driven grounding electrode 
(ground rod) of:
    (1) At least 1.5 meters (5 feet) in length where the local frost 
level is normally less than 0.30 meters (1 foot) deep; or
    (2) At least 2.44 meters (8 feet) in length where the local frost 
level is normally 0.30 meters (1 foot) or deeper; and
    (B) Bonded to a multi-grounded power system neutral when the splice 
is within 1.8 meters (6 feet) of access to the grounding system of the 
multi-grounded neutral system. Bonding to the multi-grounded neutral of 
a parallel power line may help to minimize telephone interference on 
long exposures with copper cable plant. Consideration, thus, should be 
given to completing such bonds, at least four (4) times each mile, when 
splices are greater than 1.8 meters (6 feet) but less than 4.6 meters 
(15 feet) from access to the multi-grounded neutral.
    (6) Bonding and grounding splice cases. (i) Splice cases are 
equipped with bonding and grounding devices to ensure that cable shields 
and metallic strength members maintain electrical continuity during and 
after cable splicing operations. The splice case manufacturer's 
recommendations shall be followed concerning the bonding and grounding 
procedures. Conductors used for bonding shall be either stranded or 
braided tinned copper wire equivalent to 6 AWG. Conductors used for 
grounding shall be a solid, bare, copper wire equivalent to minimum No. 
6 AWG.
    (ii) Buried splice cases installed in either handholes or pedestals 
shall be grounded such that the cable shield grounds are attached to a 
common ground connection that will allow the lifting of a ground on the 
cable shield in either direction to permit efficient cable locating 
procedures. As a first choice, buried grounding conductor(s) shall be 
bare. However, if two or more grounding conductors are buried in the s 
they shall be insulated to avoid shorts when a locating tone is applied.
    (iii) A typical bonding and grounding method for fiber optic splices 
is shown in Figure 19:

[[Page 445]]

[GRAPHIC] [TIFF OMITTED] TR26JA95.020

    (7) Bonding and grounding central office cable entrances. The RUS 
Telecommunications Engineering and Construction Manual (TE&CM) Section 
810 provides bonding and grounding guidance for central office cable 
entrances. Splicing operations shall not be attempted before all 
metallic cable shield and strength members are bonded and grounded.

[60 FR 5097, Jan. 26, 1995; 60 FR 9079, Feb. 16, 1995]

[[Page 446]]