[Code of Federal Regulations]
[Title 7, Volume 11]
[Revised as of January 1, 2003]
From the U.S. Government Printing Office via GPO Access
[CITE: 7CFR1755.506]

[Page 546-555]
 
                          TITLE 7--AGRICULTURE
 
    CHAPTER XVII--RURAL UTILITIES SERVICE, DEPARTMENT OF AGRICULTURE
 
PART 1755--TELECOMMUNICATIONS STANDARDS AND SPECIFICATIONS FOR MATERIALS, EQUIPMENT AND CONSTRUCTION--Table of Contents
 
Sec. 1755.506  Aerial wire services

    (a) Aerial services of one through six pairs shall consist of 
Service Entrance Aerial (SEA) assembly units, in accordance with RUS 
Bulletin 1753F-153 (RUS Form 515d), Specifications and Drawings for 
Service Installations at Customer Access Locations. The wire used for 
aerial services shall conform to the requirements of Secs. 1755.700 
through 1755.704, RUS specification for aerial service wires, and shall 
be RUS accepted or RUS technically accepted. Copies of RUS Bulletin 
1753F-153 are available upon request from RUS/USDA, 1400 Independence 
Avenue, SW., STOP 1522, Washington, DC 20250-1522, FAX (202) 720-4120.
    (b) If aerial wire services are to be connected to aerial cable 
pairs, the NIDs or fused primary station protectors and grounds shall be 
installed and connected before the aerial service wires are attached to 
the customer's structure.
    (c) Kinks or splices shall not be permitted in aerial service wire 
spans.
    (d) Aerial service wires shall be run in accordance with the 
construction drawings contained in Sec. 1755.510 and shall conform to 
all clearance requirements of the ANSI/NFPA 70-1999, NEC[reg], and ANSI/
IEEE C2-1997, NESC, or local laws or ordinances, whichever are the most 
stringent. The National Electrical Code[reg] and NEC[reg] are registered 
trademarks of the National Fire Protection Association, Inc., Quincy, MA 
02269. The ANSI/NFPA 70-1999, NEC[reg], and ANSI/IEEE C2-1997, NESC, are 
incorporated by reference in accordance with 5 U.S.C. 552(a) and 1 CFR 
part 51. Copies of ANSI/NFPA 70-1999, NEC[reg], are available from NFPA, 
1 Batterymarch Park, P.O. Box 9101, Quincy, Massachusetts 02269-9101, 
telephone number 1 (800) 344-3555. Copies of ANSI/IEEE C2-1997, NESC, 
are available from IEEE Service Center, 455 Hoes Lane, Piscataway, New 
Jersey 08854, telephone number 1 (800) 678-4333. Copies of ANSI/NFPA 70-
1999, NEC[reg], and ANSI/IEEE C2-1997, NESC, are

[[Page 547]]

available for inspection during normal business hours at RUS, room 2905, 
U.S. Department of Agriculture, 1400 Independence Avenue, SW., STOP 
1598, Washington, DC 20250-1598 or at the Office of the Federal 
Register, 800 North Capitol Street, NW., Suite 700, Washington, DC.
    (e) Aerial service wire shall be installed using the maximum 
practicable sag consistent with the required ground clearance and good 
construction practices. In no event shall the minimum sags be less than 
the values shown on construction drawing 505 contained in Sec. 1755.510 
for various span lengths and loading areas provided. Span lengths shall 
not exceed 250 ft (76 m).
    (f) To reduce vibration and galloping, aerial service wire shall be 
twisted one complete turn for each 10 ft (3 m) of span length at the 
time of installation.
    (g) The methods of attaching aerial service wires at poles shall be 
as illustrated in construction drawings 503-2 and 504 contained in 
Sec. 1755.510.
    (h) Horizontal and vertical climbing spaces on poles used jointly 
with power circuits shall be provided in conformance with the 
requirements of Rule 236 of ANSI/IEEE C2-1997, NESC.
    (i) Not more than four aerial service wires shall be distributed 
from any one 7/16 in. (10 mm) drive hook, or more than two aerial 
service wires from any one 5/16 in. (8 mm) drive hook. Aerial service 
wires and drive hooks shall be arranged so that the load does not pull 
the drive hook out of the pole. When more than one drive hook is 
required, the drive hooks shall be staggered with a minimum separation 
of 1 in. (25.4 mm) horizontally on centers and 1.5 in. (40 mm) 
vertically on centers. If drive hooks are placed within 3 in. (76 mm) of 
the top of the pole and on the opposite side of the pole's 
circumference, a vertical separation of at least 3 in. (76 mm) shall be 
provided. A drive hook shall not be placed on the top of a pole or stub 
pole.
    (j) When connecting aerial service wires to cable pairs at 
terminals, sufficient slack shall be provided so that each aerial 
service wire shall reach any binding post position as shown on 
construction drawing 312-1 contained in Sec. 1755.510.
    (k) Aerial service wire attachments on utility poles and the manner 
of placing bridle rings and entering cable terminals shall be as shown 
on construction drawing 503-2 contained in Sec. 1755.510.
    (l) Not more than two conductors shall be connected to any terminal 
binding post. Where it is necessary to bridge more than two aerial 
service wires at the same closure, the aerial service wires shall be 
terminated in aerial service wire terminals connected in parallel with a 
No. 20 AWG bridle wire which shall be terminated on the binding posts of 
the filled terminal block.
    (m) Where aerial service wire is attached to aerial plastic cable, 
it shall be brought directly into a ready-access closure and shall be 
terminated on the binding posts of the filled terminal block as shown on 
construction drawing 503-2 contained in Sec. 1755.510.
    (n) The conductor of copper coated steel reinforced aerial service 
wires identified by tracer ridges shall be used as the ring (negative 
battery) conductor of the pair, and shall normally be connected to the 
right or lower binding post of a pair on filled terminal blocks and NIDs 
or fused primary station protectors.
    (o) Nonmetallic reinforced aerial service wire pair identification. 
(1) The tip and ring conductors of nonmetallic reinforced aerial service 
wires shall be identified in accordance with Table 3, as follows:

     Table 3.--Nonmetallic Reinforced Aerial Service Wire Color Code
------------------------------------------------------------------------
                                             Conductor color
          Pair number           ----------------------------------------
                                           Tip                 Ring
------------------------------------------------------------------------
1..............................  White/Blue or White....  Blue
2..............................  White/Orange or White..  Orange
3..............................  White/Green or White...  Green
4..............................  White/Brown or White...  Brown
5..............................  White/Slate or White...  Slate

[[Page 548]]


6..............................  Red/Blue or Red........  Blue
------------------------------------------------------------------------

    (2) The ring (negative battery) conductor of the pair shall normally 
be connected to the right or lower binding post of a pair on filled 
terminal blocks and NIDs or fused primary station protectors.
    (p) When it is necessary to avoid intervening obstacles between a 
pole and a building, span clamp attachments shall be used to support the 
aerial service wires at points between the poles that are supporting the 
cable on the suspension strand as indicated by construction drawings 
501-1 and 501-2 contained in Sec. 1755.510.
    (q) Aerial service wire strung from pole to pole shall be placed 
entirely below or entirely above any existing wire or cable. When 
adequate ground clearance can be obtained, preference shall be given to 
placing aerial service wire below wire and cable.
    (r) When more than one aerial service wire is installed from pole to 
pole, the first aerial service wire shall be sagged in accordance with 
construction drawing 505 contained in Sec. 1755.510. Succeeding aerial 
service wires shall be sagged with 2 in. (50.8 mm) more sag for each 
aerial service wire.
    (s) Aerial service wire spans from pole lines to buildings shall 
follow the shortest feasible route commensurate with the requirements of 
paragraph (t) of this section and shall be sagged in accordance with 
construction drawing 505 contained in Sec. 1755.510. The route shall 
avoid trees and other obstructions to the extent practicable. Where 
trees cannot be avoided, tree trimming permission shall be obtained from 
the owner or the owner's representative, and all limbs and foliage 
within 2 ft (600 mm) of the finally sagged wire shall be removed. If 
tree trimming permission cannot be obtained, the matter shall be 
referred to the borrower for resolution before proceeding with the 
installation.
    (t) Aerial service wires shall contact buildings as closely as 
practicable at a point directly above the NID, or fused primary station 
protector. Generally, horizontal drop wire runs on buildings shall not 
exceed 20 ft (6 m). The warning given in Sec. 1755.505(f)(11) regarding 
drilling holes in aluminum and vinyl siding applies also to attaching 
aerial service wires.
    (u) The point of the first building attachment shall be located so 
that the aerial service wire will be clear of roof drainage points.
    (v) Where practicable, aerial service wires shall pass under 
electrical guys, power distribution secondaries and services, tree 
limbs, etc.
    (w) Aerial service wire shall not pass in front of windows or 
immediately above doors.
    (x) Aerial service wires shall be routed so as to have a minimum 
clearance of 2 ft (600 mm) from any part of a short wave, ham radio, 
etc. antenna mast and a television antenna mast in its normal vertical 
position and of the possible region through which it sweeps when being 
lowered to a horizontal position.
    (y) Aerial service wires shall be installed such that all clearances 
and separations comply with either section 237 of ANSI/IEEE C2-1997, 
NESC, or ANSI/NFPA 70-1999, NEC[reg], or local laws or ordinances, 
whichever is the most stringent.
    (z) Aerial service wire attachments to buildings shall be as 
follows:
    (1) First attachments on buildings shall be made in accordance with 
construction drawings 506, 507, or 508-1 contained in Sec. 1755.510, as 
applicable;
    (2) Intermediate attachments on buildings shall be made in 
accordance with construction drawings 510 or 510-1 contained in 
Sec. 1755.510; and
    (3) Uninsulated attachments shall be permitted to be used as 
follows:
    (i) Wherever NIDS are used as permitted by section 800-30(a)(1) of 
the ANSI/NFPA 70-1999, NEC[reg]; and

[[Page 549]]

    (ii) On masonry and other types of nonflammable buildings.
    (aa) Insulated attachments shall be used on wooden frame, metallic 
siding and other types of combustible buildings where fused primary 
station protectors are used, as required by section 800-30(a)(2) of 
ANSI/NFPA 70-1999, NEC[reg].
    (bb) Aerial service wire runs on buildings shall be attached 
vertically and horizontally in a neat and most inconspicuous possible 
manner. See construction drawing 513 contained in Sec. 1755.510. 
Horizontal runs on buildings are undesirable and shall be kept to a 
minimum. Diagonal runs shall not be made.
    (cc) Aerial service wire runs on buildings shall be located so as 
not to be subjected to damage from passing vehicles, pedestrians, or 
livestock.
    (dd) Minimum separation between aerial service wires and other 
facilities on or in buildings shall be in accordance with 
Sec. 1755.505(f)(8), Table 1.
    (ee) Appropriate devices for attaching aerial service wires to 
buildings vary with the type of building construction and with the type 
of customer access location equipment. Table 4 lists various types of 
attachments and their application with respect to construction, customer 
access location equipment, and proper mounting devices. Construction 
drawings 506 through 513 contained in Sec. 1755.510 illustrate 
requirements with respect to various angles of service wire contacts and 
uses of various attachments. Table 4 is as follows:

[[Page 550]]

[GRAPHIC] [TIFF OMITTED] TR17AU01.004

    Notes: 1. Screw dimensions are minimum. Where appropriate, either or 
both dimensions shall be increased. All wood screws for exterior use 
shall be stainless steel. All other exterior metal devices shall be 
stainless steel, zinc coated steel, silicon bronze, or corrosion 
resistant aluminum alloy.
    2. Toggle bolt dimensions are minimum. Where appropriate, either or 
both dimensions shall be increased.
    3. All devices should be attached to studding.
    4. Screw-type devices shall be secured by means of expansion-type 
anchors. Equivalent manual or machine-driven devices may be used. Where 
toggle bolts are specified equivalent devices may be used.
    5. Pilot holes shall be provided for screws and bridle rings in 
shingles and dropsiding.
    6. Attachment device not applicable.

[[Page 551]]

    7. Attachment device applicable but no separate fastening device 
required.
    8. To convert English units to Metric units use 1 in. = 25.4 mm.

    (ff) Fastener spacings for vertical and horizontal runs on frame or 
masonry buildings shall not be more than 6 ft (2 m) apart. Fasteners 
should be spaced close enough to prevent the aerial service wire from 
``slapping'' against the building during windy conditions.
    (gg) When it is necessary to pass behind or around obstructions such 
as downspouts and vertical conduits, the aerial service wire shall be 
supported firmly with attachment devices placed not more than 6 in. (152 
mm) from the obstruction as illustrated in Figures 4 and 5 of paragraph 
(hh) of this section. Preferably, the aerial service wire should be 
routed behind obstructions to minimize the possibility of mechanical 
damage to the aerial service wire in the event repair work to the 
obstruction is required.
    (hh) When passing around building projections of masonry or wood or 
around corners, aerial service wires shall be installed as illustrated 
in Figures 5 and 6. Figures 4, 5, and 6 are as follows:

[[Page 552]]

[GRAPHIC] [TIFF OMITTED] TR17AU01.005


[[Page 553]]


[GRAPHIC] [TIFF OMITTED] TR17AU01.006


[[Page 554]]


[GRAPHIC] [TIFF OMITTED] TR17AU01.007

    (ii) In areas where ice and snow conditions are severe, aerial 
service wires shall be located so that ice and snow falling from the 
roof will not strike the wires. However, where aerial service wires must 
pass under the sloping part of the roof, first attachments shall be made 
as close as practicable to the eaves.
    (jj) If two aerial service wire spans are required to the same 
building, the first attachment shall be such that both aerial service 
wires can be attached at the same attachment device. Refer to 
construction drawing 508-1 contained in Sec. 1755.510. Where more than 
two aerial service wires are required, additional attachment devices

[[Page 555]]

in the same general location on the building shall be used.
    (kk) When two or more aerial service wire runs are required on the 
same building they shall share the same type of attachment devices.
    (ll) Aerial service wire entrances to buildings shall conform to 
sketch B of construction drawing 510-2 contained in Sec. 1755.510, 
unless the entrance is made through a conduit.
    (mm) When the aerial service wire approaches the entrance hole from 
above, a 1.5 in. (40 mm) minimum drip loop shall be formed in accordance 
with sketch B of construction drawing 510-2 contained in Sec. 1755.510.
    (nn) If an entrance conduit which slopes upward from outside to 
inside is available and suitably located, it shall be used for the 
aerial service wire entrance.

[66 FR 43317, Aug. 17, 2001]