[Code of Federal Regulations]
[Title 7, Volume 11]
[Revised as of January 1, 2003]
From the U.S. Government Printing Office via GPO Access
[CITE: 7CFR1755.870]

[Page 680-694]
 
                          TITLE 7--AGRICULTURE
 
    CHAPTER XVII--RURAL UTILITIES SERVICE, DEPARTMENT OF AGRICULTURE
 
PART 1755--TELECOMMUNICATIONS STANDARDS AND SPECIFICATIONS FOR MATERIALS, EQUIPMENT AND CONSTRUCTION--Table of Contents
 
Sec. 1755.870  RUS specification for terminating cables.

    (a) Scope. (1) This section establishes the requirements for 
terminating cables used to connect incoming outside plant cables to the 
vertical side of the main distributing frame in a telephone central 
office.
    (i) The conductors are solid tinned copper, individually insulated 
with extruded solid dual insulating compounds.
    (ii) The insulated conductors are twisted into pairs which are then 
stranded or oscillated to form a cylindrical core.
    (iii) The cable structure is completed by the application of a core 
wrap, a shield, and a polyvinyl chloride jacket.
    (2) The number of pairs and gauge size of conductors which are used 
within the RUS program are provided in the following table:

------------------------------------------------------------------------
                 American Wire Gauge (AWG)                    22     24
------------------------------------------------------------------------
Number of Pairs...........................................     12     12
                                                               50     50
                                                              100    100
                                                              200    200
                                                              300    300
                                                              400    400
                                                              600    600
                                                              800   800
------------------------------------------------------------------------
Note: Cables larger in pair sizes from those shown in this table shall
  meet all the requirements of this section.

    (3) All cables sold to RUS borrowers for projects involving RUS loan 
funds under this section must be accepted by RUS Technical Standards 
Committee ``A'' (Telephone). For cables manufactured to the 
specification of this section, all design changes to an accepted design 
must be submitted for acceptance. RUS will be the sole authority on what 
constitutes a design change.
    (4) Materials, manufacturing techniques, or cable designs not 
specifically addressed by this section may be allowed if accepted by 
RUS. Justification for acceptance of modified materials, manufacturing 
techniques, or cable designs shall be provided to substantiate product 
utility and long term stability and endurance.
    (5) The American National Standard Institute/Electronic Industries 
Association (ANSI/EIA) 359-A-84, EIA Standard Colors for Color 
Identification and Coding, referenced in this section is incorporated by 
reference by RUS. This incorporation by reference was approved by the 
Director of the Federal Register in accordance with 5 U.S.C. 552(a) and 
1 CFR part 51. Copies of ANSI/EIA 359-A-84 are available for inspection 
during normal business hours at RUS, room 2845, U.S. Department of 
Agriculture, Washington, DC 20250-1500 or at the Office of the Federal 
Register, 800 North Capitol Street, NW., suite 700, Washington, DC. 
Copies are available from Global Engineering Documents, 15 Inverness Way 
East, Englewood, CO 80112, telephone number (303) 792-2181.

[[Page 681]]

    (6) American Society for Testing and Materials Specifications (ASTM) 
B 33-91, Standard Specification for Tinned Soft or Annealed Copper Wire 
for Electrical Purposes; ASTM B 736-92a Standard Specification for 
Aluminum, Aluminum Alloy and Aluminum-Clad Steel Cable Shielding Stock; 
ASTM D 1248-84 (1989), Standard Specification for Polyethylene Plastics 
Molding and Extrusion Materials; ASTM D 1535-89, Standard Test Method 
for Specifying Color by the Munsell System; ASTM D 2287-81 (Reapproved 
1988), Standard Specification for Nonrigid Vinyl Chloride Polymer and 
Copolymer Molding and Extrusion Compounds; ASTM D 2436-85, Standard 
Specification for Forced-Convection Laboratory Ovens for Electrical 
Insulation; ASTM D 2633-82 (Reapproved 1989), Standard Methods of 
Testing Thermoplastic Insulations and Jackets for Wire and Cable; ASTM D 
4101-82 (1988), Standard Specification for Propylene Plastic Injection 
and Extrusion Materials; ASTM D 4565-90a, Standard Test Methods for 
Physical and Environmental Performance Properties of Insulations and 
Jackets for Telecommunications Wire and Cable; ASTM D 4566-90, Standard 
Test Methods for Electrical Performance Properties of Insulations and 
Jackets for Telecommunications Wire and Cable; and ASTM E 29-90, 
Standard Practice for Using Significant Digits in Test Data to Determine 
Conformance with Specifications, referenced in this section are 
incorporated by reference by RUS. These incorporations by references 
were approved by the Director of the Federal Register in accordance with 
5 U.S.C. 552(a) and 1 CFR part 51. Copies of the ASTM standards are 
available for inspection during normal business hours at RUS, room 2845, 
U.S. Department of Agriculture, Washington, DC 20250-1500 or at the 
Office of the Federal Register, 800 North Capitol Street, NW., suite 
700, Washington, DC. Copies are available from ASTM, 1916 Race Street, 
Philadelphia, Pennsylvania 19103-1187, telephone number (215) 299-5585.
    (7) American National Standards Institute/National Fire Protection 
Association (ANSI/NFPA), NFPA 70-1993 National Electrical Code 
referenced in this section is incorporated by reference by RUS. This 
incorporation by reference was approved by the Director of the Federal 
Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. A copy of 
the ANSI/NFPA standard is available for inspection during normal 
business hours at RUS, room 2845, U.S. Department of Agriculture, 
Washington, DC 20250-1500 or at the Office of the Federal Register, 800 
North Capitol Street, NW., suite 700, Washington, DC. Copies are 
available from NFPA, Batterymarch Park, Quincy, Massachusetts 02269, 
telephone number 1 (800) 344-3555.
    (8) Underwriters Laboratories Inc. (UL) 1666, Standard Test for 
Flame Propagation Height of Electrical and Optical-Fiber Cables 
Installed Vertically in Shafts, dated January 22, 1991, referenced in 
this section is incorporated by reference by RUS. This incorporation by 
reference was approved by the Director of the Federal Register in 
accordance with 5 U.S.C. 552(a) and 1 CFR part 51. A copy of the UL 
standard is available for inspection during normal business hours at 
RUS, room 2845, U.S. Department of Agriculture, Washington, DC 20250-
1500 or at the Office of the Federal Register, 800 North Capitol Street, 
NW., suite 700, Washington, DC. Copies are available from UL Inc., 333 
Pfingsten Road, Northbrook, Illinois 60062-2096, telephone number (708) 
272-8800.
    (b) Conductors and conductor insulation. (1) Each conductor shall be 
a solid round wire of commercially pure annealed tin coated copper. 
Conductors shall meet the requirements of the American Society for 
Testing and Materials (ASTM) B 33-91 except that requirements for 
Dimensions and Permissible Variations are waived.
    (2) Joints made in conductors during the manufacturing process may 
be brazed, using a silver alloy solder and nonacid flux, or they may be 
welded using either an electrical or cold welding technique. In joints 
made in uninsulated conductors, the two conductor ends shall be butted. 
Splices made in insulated conductors need not be butted but may be 
joined in a manner acceptable to RUS.

[[Page 682]]

    (3) The tensile strength of any section of a conductor, containing a 
factory joint, shall not be less than 85 percent of the tensile strength 
of an adjacent section of the solid conductor of equal length without a 
joint.
    (4) Engineering Information: The sizes of wire used and their 
nominal diameters shall be as shown in the following table:

------------------------------------------------------------------------
                                                    Nominal diameter
                      AWG                      -------------------------
                                                 Millimeters   (Inches)
------------------------------------------------------------------------
22............................................         0.643    (0.0253)
24............................................         0.511    (0.0201)
------------------------------------------------------------------------

    (5) Each conductor shall be insulated with a primary layer of 
natural or white solid, insulating grade, high density polyethylene or 
crystalline propylene/ethylene copolymer and an outer skin of colored, 
solid, insulating grade, polyvinyl chloride (PVC) using one of the 
insulating materials listed in paragraphs (b)(5)(i) through (iii) of 
this section.
    (i) The polyethylene raw material selected to meet the requirements 
of this section shall be Type III, Class A, Category 4 or 5, Grade E9, 
in accordance with ASTM D 1248-84 (1989).
    (ii) The crystalline propylene/ethylene raw material selected to 
meet the requirements of this section shall be Class PP 200B 40003 E11 
in accordance with ASTM D 4101-82 (1988).
    (iii) The PVC raw material selected to meet the requirements of this 
section shall be either Type PVC-64751E3XO, Type PVC-76751E3XO, or Type 
PVC-77751E3XO in accordance with ASTM D 2287-81 (1988).
    (iv) Raw materials intended as conductor insulation furnished to 
these requirements shall be free from dirt, metallic particles, and 
other foreign matter.
    (v) All insulating raw materials shall be accepted by RUS prior to 
their use.
    (6) All conductors in any single length of cable shall be insulated 
with the same type of material.
    (7) A permissible overall performance level of faults in conductor 
insulation when using the test procedures in paragraph (b)(8) of this 
section shall average not greater than one fault per 12,000 conductor 
meters (40,000 conductor feet) for each gauge of conductor.
    (8) The test used to determine compliance with paragraph (b)(7) of 
this section shall be conducted as follows:
    (i) Samples tested shall be taken from finished cables selected at 
random from standard production cable. The samples tested shall contain 
a minimum of 300 conductor meters (1,000 conductor feet) for cables 
sizes less than 50 pairs and 1,500 conductor meters (5,000 conductor 
feet) for cables sizes greater than or equal to 50 pairs. No further 
sample need be taken from the same cable production run within 6,000 
cable meters (20,000 cable feet) of the original test sample from that 
run.
    (ii) The cable sample shall have its jacket, shield, and core wrap 
removed and its core shall be immersed in tap water for a minimum period 
of 6 hours. In lieu of removing the jacket, shield, and core wrap from 
the core, the entire cable may be tested. In this case, the core shall 
be completely filled with tap water, under pressure; then the cable 
assembly shall be immersed for a minimum period of 6 hours. With the 
cable core still fully immersed, except for end connections, the 
insulation resistance (IR) of all conductors to water shall be measured 
using a direct current (dc) voltage of 100 volts to 550 volts.
    (iii) An IR value of less than 500 megohms for any individual 
insulated conductor tested at or corrected to a temperature of 23  deg.C 
is considered a failure. If the cable sample is more than 7.5 meters (25 
feet) long, all failing conductors shall be retested and reported in 7.5 
meter (25 foot) segments.
    (iv) The pair count, gauge, footage, and number of insulation faults 
shall be recorded. This information shall be retained on a 6 month 
running basis for review by RUS when requested.
    (v) A fault rate, in a continuous length in any one reel, in excess 
of one fault per 3,000 conductor meters (10,000 conductor feet) due to 
manufacturing defects is cause for rejection. A minimum of 6,000 
conductor meters (20,000 conductor feet) is required to develop a 
noncompliance in a reel.

[[Page 683]]

    (9) Repairs to the conductor insulation during manufacturing are 
permissible. The method of repair shall be accepted by RUS prior to its 
use. The repaired insulation shall be capable of meeting the relevant 
electrical requirements of this section.
    (10) All repaired sections of insulation shall be retested in the 
same manner as originally tested for compliance with paragraph (b)(7) of 
this section.
    (11) The colored composite insulating material removed from or 
tested on the conductor, from a finished cable, shall be capable of 
meeting the following performance requirements:

------------------------------------------------------------------------
                                                              Composite
                          Property                            insulation
------------------------------------------------------------------------
Tensile Strength, Minimum Megapascals (MPa) (Pounds per      16.5 (2400)
 square inch (psi))........................................
Ultimate Elongation Percent, Minimum.......................          125
Cold Bend Failures, Maximum................................         0/10
Shrinkback, Maximum Millimeter (mm) (Inches (in.)).........    9.5 (3/8)
Adhesion, Maximum Newtons (N) (Pound-force (lbf))..........     13.3 (3)
Compression Minimum, N (lbf)...............................   1780 (400)
------------------------------------------------------------------------

    (12) Testing procedures. The procedures for testing the composite 
insulation samples for compliance with paragraph (b)(11) of this section 
shall be as follows:
    (i) Tensile strength and ultimate elongation. Samples of the 
insulation material, removed from the conductor, shall be tested in 
accordance with ASTM D 2633-82(1989), except that the speed of jaw 
separation shall be 50 millimeters/minute (50 mm/min) (2 inches/minute 
(2 in./min)).
    Note: Quality assurance testing at a jaw separation speed of 500 mm/
min (20 in./min) is permissible. Failures at this rate shall be retested 
at the 50 mm/min (2 in./min) rate to determine specification compliance.
    (ii) Cold bend. Samples of the insulation material on the conductor 
shall be tested in accordance with ASTM D 4565-90a at a temperature of -
401  deg.C with a mandrel diameter of 6 mm (0.25 in.). There 
shall be no cracks visible to normal or corrected-to-normal vision.
    (iii) Shrinkback. Samples of insulation shall be tested for four 
hours at a temperature of 1151  deg.C in accordance with 
ASTM D 4565-90a.
    (iv) Adhesion. Samples of insulation material on the conductor shall 
be tested in accordance with ASTM D 4565-90a with a crosshead speed of 
50 mm/min (2 in./min).
    (v) Compression. Samples of the insulation material on the conductor 
shall be tested in accordance with ASTM D 4565-90a with a crosshead 
speed of 5 mm/min (0.2 in./min).
    (13) Other methods of testing may be used if acceptable to RUS.
    (c) Identification of pairs and twisting of pairs. (1) The PVC skin 
shall be colored to identify:
    (i) The tip and ring conductor of each pair; and
    (ii) Each pair in the completed cable.
    (2) The colors used to provide identification of the tip and ring 
conductor of each pair shall be as shown in the following table:

------------------------------------------------------------------------
                                                     Color
              Pair No.               -----------------------------------
                                            Tip               Ring
------------------------------------------------------------------------
 1..................................  White            Blue
 2..................................  White            Orange
 3..................................  White            Green
 4..................................  White            Brown
 5..................................  White            Slate
 6..................................  Red              Blue
 7..................................  Red              Orange
 8..................................  Red              Green
 9..................................  Red              Brown
10..................................  Red              Slate
11..................................  Black            Blue
12..................................  Black            Orange
13..................................  Black            Green
14..................................  Black            Brown
15..................................  Black            Slate
16..................................  Yellow           Blue
17..................................  Yellow           Orange
18..................................  Yellow           Green
19..................................  Yellow           Brown
20..................................  Yellow           Slate
21..................................  Violet           Blue
22..................................  Violet           Orange
23..................................  Violet           Green
24..................................  Violet           Brown
25..................................  Violet           Slate
------------------------------------------------------------------------

    (3) Standards of color. The colors of the insulated conductors 
supplied in accordance with this section are specified in terms of the 
Munsell Color System (ASTM D 1535-89) and shall comply with the ``Table 
of Wire and Cable Limit Chips'' as defined in ANSI/EIA-359-A-84. (Visual 
color standards meeting these requirements may be obtained directly from 
the Munsell Color Company, Inc., 2441 North Calvert Street, Baltimore, 
Maryland 21218).
    (4) Positive identification of the tip and ring conductors of each 
pair by marking each conductor of a pair with the color of its mate is 
permissible.

[[Page 684]]

The method of marking shall be accepted by RUS prior to its use.
    (5) Other methods of providing positive identification of the tip 
and ring conductors of each pair may be employed if accepted by RUS 
prior to its use.
    (6) The insulated conductors shall be twisted into pairs.
    (7) In order to provide sufficiently high crosstalk isolation, the 
pair twists shall be designed to enable the cable to meet the 
capacitance unbalance and the crosstalk loss requirements of paragraphs 
(h)(2), (h)(3), and (h)(4) of this section.
    (8) The average length of pair twists in any pair in the finished 
cable, when measured on any 3 meter (m) (10 foot (ft)) length, shall not 
exceed 152 mm (6 in.).
    (d) Forming of the cable core. (1) Twisted pairs shall be assembled 
in such a way as to form a substantially cylindrical group.
    (2) When desired for lay-up reasons, the basic group may be divided 
into two or more subgroups called units.
    (3) Each group, or unit in a particular group, shall be enclosed in 
bindings of the colors indicated for its particular pair count. The pair 
count, indicated by the color of insulation, shall be consecutive as 
indicated in paragraph (d)(5) of this section through units in a group.
    (4) Threads or tapes used as binders shall be nonhygroscopic and 
nonwicking. The threads shall consists of a suitable number of ends of 
each color arranged as color bands. When tapes are used as binders, they 
shall be colored. Binders shall be applied with a lay of not more than 
100 mm (4 in.). The colored binders shall be readily recognizable as the 
basic intended color and shall be distinguishable from all other colors.
    (5) The colors of the bindings and their significance with respect 
to pair count shall be as shown in the following table:

------------------------------------------------------------------------
       Group No.            Color of bindings        Group pair count
------------------------------------------------------------------------
1.....................  White-Blue..............  1-25
2.....................  White-Orange............  26-50
3.....................  White-Green.............  51-75
4.....................  White-Brown.............  76-100
5.....................  White-Slate.............  101-125
6.....................  Red-Blue................  126-150
7.....................  Red-Orange..............  151-175
8.....................  Red-Green...............  176-200
9.....................  Red-Brown...............  201-225
10....................  Red-Slate...............  226-250
11....................  Black-Blue..............  251-275
12....................  Black-Orange............  276-300
13....................  Black-Green.............  301-325
14....................  Black-Brown.............  326-350
15....................  Black-Slate.............  351-375
16....................  Yellow-Blue.............  376-400
17....................  Yellow-Orange...........  401-425
18....................  Yellow-Green............  426-450
19....................  Yellow-Brown............  451-475
20....................  Yellow-Slate............  476-500
21....................  Violet-Blue.............  501-525
22....................  Violet-Orange...........  526-550
23....................  Violet-Green............  551-575
24....................  Violet-Brown............  576-600
------------------------------------------------------------------------

    (6) The use of the white unit binder in cables of 100 pair or less 
is optional.
    (7) When desired for manufacturing reasons, two or more 25 pair 
groups may be bound together with nonhygroscopic and nonwicking threads 
or tapes into super-units. The group binders and the super-unit binders 
shall be colored such that the combination of the two binders shall 
positively identify each 25 pair group from every other 25 pair group in 
the cable.
    (8) Super-unit binders shall be of the colors shown in the following 
table:

                        Super-Unit Binder Colors
------------------------------------------------------------------------
                 Pair No.                           Binder color
------------------------------------------------------------------------
1-600.....................................  White
601-1200..................................  Red
------------------------------------------------------------------------

    (e) Core wrap.(1) The core shall be completely covered with a layer 
of nonhygroscopic and nonwicking dielectric material. The core wrap 
shall be applied with an overlap.
    (2) The core wrap shall provide a sufficient heat barrier to prevent 
visible evidence of conductor insulation deformation or adhesion between 
conductors, caused by adverse heat transfer during the jacketing 
operation.
    (3) Engineering Information: If required for manufacturing reasons, 
white or uncolored binders of nonhygroscopic and nonwicking material may 
be applied over the core and/or core wrap.
    (f) Shield. (1) An aluminum shield, plastic coated on one side, 
shall be applied longitudinally over the core wrap.

[[Page 685]]

    (2) The shield may be applied over the core wrap with or without 
corrugations (smooth) and shall be bonded to the outer jacket.
    (3) The shield overlap shall be a minimum of 3 mm (0.125 in.) for 
cables with core diameters of 15 mm (0.625 in.) or less and a minimum of 
6 mm (0.25 in.) for cables with core diameters greater than 15 mm (0.625 
in.). The core diameter is defined as the diameter under the core wrap 
and binding.
    (4) General requirements for application of the shielding material 
shall be as follows:
    (i) Successive lengths of shielding tapes may be joined during the 
manufacturing process by means of cold weld, electric weld, soldering 
with a nonacid flux, or other acceptable means;
    (ii) The metal shield with the plastic coating shall have the 
coating removed prior to joining the metal ends together. After joining, 
the plastic coating shall be restored without voids using good 
manufacturing techniques;
    (iii) The shields of each length of cable shall be tested for 
continuity. A one meter (3 ft) section of shield containing a factory 
joint shall exhibit not more than 110 percent of the resistance of a 
shield of equal length without a joint;
    (iv) The breaking strength of any section of a shield tape 
containing a factory joint shall not be less than 80 percent of the 
breaking strength of an adjacent section of the shield of equal length 
without a joint;
    (v) The reduction in thickness of the shielding material due to the 
corrugating or application process shall be kept to a minimum and shall 
not exceed 10 percent at any spot; and
    (vi) The shielding material shall be applied in such a manner as to 
enable the cable to pass the bend test as specified in paragraph (i)(1) 
of this section.
    (5) The dimensions of the uncoated aluminum tape shall be 
0.20300.0254 mm (0.00800.0010 in.).
    (6) The aluminum tape shall conform to either Alloy AA-1100-0, AA-
1145-0, or AA-1235-0 as covered in the latest edition of Aluminum 
Standards and Data, issued by the Aluminum Association, except that 
requirements for tensile strength are waived.
    (7) The single-sided plastic coated aluminum shield shall conform to 
the requirements of ASTM B 736-92a, Type I Coating, Class 1 or 2, or 
Type II Coating, Class 1. The minimum thickness of the Type I Coating 
shall be 0.038 mm (0.0015 in.). The minimum thickness of the Type II 
Coating shall be 0.008 mm (0.0003 in.).
    (8) The plastic coated aluminum shield shall be tested for 
resistance to water migration by immersing a one meter (3 ft) length of 
tape under a one meter (3 ft) head of water containing a soluble dye 
plus 0.25 percent (%) wetting agent.
    (i) After a minimum of 5 minutes, no dye shall appear between the 
interface of the shield tape and the plastic coating.
    (ii) The actual test method shall be acceptable to RUS.
    (9) The bond between the plastic coated shield and the jacket shall 
conform to the following requirements:
    (i) Prepare test strips approximately 200 mm (8 in.) in length. Slit 
the jacket and shield longitudinally to produce 4 strips evenly spaced 
and centered in 4 quadrants on the jacket circumference. One of the 
strips shall be centered over the overlapped edge of the shielding tape. 
The strips shall be 13 mm (0.5 in.) wide. For cable diameters less than 
19 mm (0.75 in.) make two strips evenly spaced.
    (ii) Separate the shield and jacket for a sufficient distance to 
allow the shield and jacket to be fitted in the upper and lower jaws of 
a tensile machine. Record the maximum force required to separate the 
shield and jacket to the nearest newton (pound-force). Repeat this 
action for each test strip.
    (iii) The force required to separate the jacket from the shield 
shall not be less than 9 N (2 lbf) for any individual strip when tested 
in accordance with paragraph (f)(9)(ii) of this section. The average 
force for all strips of any cable shall not be less than 18 N (4 lbf).
    (g) Cable jacket and extraneous material. (1) The jacket shall 
provide the cable with a tough, flexible, protective covering which can 
withstand stresses reasonably expected in normal installation and 
service.

[[Page 686]]

    (2) The jacket shall be free from holes, splits, blisters, or other 
imperfections and shall be as smooth and concentric as is consistent 
with the best commercial practice.
    (3) The raw material used for the cable jacket shall be one of the 
following four types:
    (i) Type PVC-55554EOXO in accordance with ASTM D 2287-81(1988);
    (ii) Type PVC-65554EOXO in accordance with ASTM D 2287-81(1988);
    (iii) Type PVC-55556EOXO in accordance with ASTM D 2287-81(1988); or
    (iv) Type PVC-66554EOXO in accordance with ASTM D 2287-81(1988).
    (4) The jacketing material removed from or tested on the cable shall 
be capable of meeting the following performance requirements:

------------------------------------------------------------------------
                                                               Jacket
                         Property                            performance
------------------------------------------------------------------------
Tensile Strength-Unaged Minimum, MPa (psi)................   13.8 (2000)
Ultimate Elongation-Unaged Minimum, Percent (%)...........           200
Tensile Strength-Aged Minimum, % of original value........            80
Ultimate Elongation-Aged Minimum, % of original value.....            50
Impact Failures, Maximum..................................          2/10
------------------------------------------------------------------------

    (5) Testing procedures. The procedures for testing the jacket 
samples for compliance with paragraph (g)(4) of this section shall be as 
follows:
    (i) Tensile strength and ultimate elongation-unaged. The test shall 
be performed in accordance with ASTM D 2633-82(1989), using a jaw 
separation speed of 50 mm/min (2 in./min).
    Note: Quality assurance testing at a jaw separation speed of 500 mm/
min (20 in./min) is permissible. Failures at this rate shall be retested 
at the 50 mm/min (2 in./min) rate to determine specification compliance.
    (ii) Tensile strength and ultimate elongation-aged. The test shall 
be performed in accordance with paragraph (g)(5)(i) of this section 
after being aged for 7 days at a temperature of 1001  deg.C 
in a circulating air oven conforming to ASTM D 2436-85.
    (iii) Impact. The test shall be performed in accordance with ASTM D 
4565-90a using an impact force of 4 newton-meter (3 pound force-foot) at 
a temperature of -101  deg.C. The cylinder shall strike the 
sample at the shield overlap. A crack or split in the jacket constitutes 
failure.
    (6) Jacket thickness. The nominal jacket thickness shall be as 
specified in the following table. The test method used shall be either 
the End Sample Method (paragraph (g)(6)(i) of this section) or the 
Continuous Uniformity Thickness Gauge Method (paragraph (g)(6)(ii) of 
this section):

------------------------------------------------------------------------
                                            Nominal jacket thickness mm
               No. of pairs                            (in.)
------------------------------------------------------------------------
25 or less...............................  1.4 (0.055)
50.......................................  1.5 (0.060)
100......................................  1.7 (0.065)
200......................................  1.9 (0.075)
300......................................  2.2 (0.085)
400......................................  2.4 (0.095)
600......................................  2.9 (0.115)
800 and over.............................  3.3 (0.130)
------------------------------------------------------------------------

    (i) End sample method. The jacket shall be capable of meeting the 
following requirements:

Minimum Average Thickness--90% of nominal thickness
Minimum Thickness--70% of nominal thickness

    (ii) Continuous uniformity thickness gauge method. (A) The jacket 
shall be capable of meeting the following requirements:

Minimum Average Thickness--90% of nominal thickness
Minimum (Min.) Thickness--70 % of nominal thickness
Maximum (Max.) Eccentricity--55%
Eccentricity=Max. Thickness--Min. Thickness (Average Thickness)x100

    (B) Maximum and minimum thickness values. The maximum and minimum 
thickness values shall be based on the average of each axial section.
    (7) The color of the jacket shall be either black or dark grey in 
conformance with the Munsell Color System specified in ASTM D 1535-89.
    (8) There shall be no water or other contaminants in the finished 
cable which would have a detrimental effect on its performance or its 
useful life.
    (h) Electrical requirements--(1) Mutual capacitance and conductance. 
(i) The average mutual capacitance (corrected for length) of all pairs 
in any reel shall not exceed the following when tested in accordance 
with ASTM D 4566-90 at a frequency of 1.00.1 kilohertz (kHz) 
and a temperature of 233  deg.C:

[[Page 687]]



------------------------------------------------------------------------
                                                   Mutual capacitance
                                               -------------------------
             Number of cable pairs               Nanofarad/  (Nanofarad/
                                                 kilometer      mile)
------------------------------------------------------------------------
12............................................  520.1 kHz and a temperature of 233 
 deg.C.
    (2) Pair-to-pair capacitance unbalance. The capacitance unbalance as 
measured on the completed cable shall not exceed 45.3 picofarad/
kilometer (pF/km) (25 picofarad/1000 ft (pF/1000 ft)) rms when tested in 
accordance with ASTM D 4566-90 at a frequency of 1.00.1 kHz 
and a temperature of 233  deg.C.
    (3) Pair-to-ground capacitance unbalance. (i) The average 
capacitance unbalance as measured on the completed cable shall not 
exceed 574 pF/km (175 pF/1000 ft) when tested in accordance with ASTM D 
4566-90 at a frequency of 10.1 kHz and a temperature of 
233  deg.C.
    (ii) When measuring pair-to-ground capacitance unbalance all pairs 
except the pair under test are grounded to the shield except when 
measuring cable containing super-units in which case all other pairs in 
the same super-unit shall be grounded to the shield.
    (iii) Pair-to-ground capacitance unbalance may vary directly with 
the length of the cable.
    (4) Crosstalk loss. (i) The rms output-to-output far-end crosstalk 
loss (FEXT) measured on the completed cable in accordance with ASTM D 
4566-90 at a test frequency of 150 kHz shall not be less than 68 
decibel/kilometer (dB/km) (73 decibel/1000 ft (dB/1000 ft)). The rms 
calculation shall be based on the combined total of all adjacent and 
alternate pair combinations within the same layer and center to first 
layer pair combinations.
    (ii) The FEXT crosstalk loss between any pair combination of a cable 
shall not be less than 58 dB/km (63 dB/1000 ft) at a frequency of 150 
kHz. If the loss Ko at a frequency Fo for length 
Lo is known, then Kx can be determined for any 
other frequency Fx or length Lx by:
[GRAPHIC] [TIFF OMITTED] TR14JN94.000

    (iii) The near-end crosstalk loss (NEXT) as measured within and 
between units of a completed cable in accordance with ASTM D 4566-90 at 
a frequency of 772 kHz shall not be less than the following mean minus 
sigma (M-S) crosstalk requirement for any unit within the cable:

------------------------------------------------------------------------
                                                                   M-S
                           Unit size                             decibel
                                                                  (dB)
------------------------------------------------------------------------
Within Unit:
  12 and 13 pairs.............................................        56
  18 and 25 pairs.............................................        60
Between Unit:
  Adjacent 13 pairs...........................................        65
  Adjacent 25 pairs...........................................        66
  Nonadjacent (all)...........................................        81
------------------------------------------------------------------------


Where M-S is the Mean near-end coupling loss based on the combined total 
of all pair combinations, less one Standard Deviation, Sigma, of the 
mean value.
    (5) Insulation resistance. Each insulated conductor in each length 
of completed cable, when measured with all other insulated conductors 
and the shield grounded, shall have an insulation resistance of not less 
than 152 megohm-kilometer (500 megohm-mile) at 201  deg.C. 
The measurement shall be made in accordance with the procedures of ASTM 
D 4566-90.
    (6) High voltage test. (i) In each length of completed cable, the 
dielectric strength of the insulation between conductors shall be tested 
in accordance

[[Page 688]]

with ASTM D 4566-90 and shall withstand, for 3 seconds, a direct current 
(dc) potential whose value is not less than:
    (A) 3.6 kilovolts for 22-gauge conductors; or
    (B) 3.0 kilovolts for 24-gauge conductors.
    (ii) In each length of completed cable, the dielectric strength 
between the shield and all conductors in the core shall be tested in 
accordance with ASTM D 4566-90 and shall withstand, for 3 seconds, a dc 
potential whose value is not less than 10 kilovolts.
    (7) Conductor resistance. The dc resistance of any conductor shall 
be measured in the completed cable in accordance with ASTM D 4566-90 and 
shall not exceed the following values when measured at or corrected to a 
temperature of 201  deg.C:

------------------------------------------------------------------------
                                                   Maximum resistance
                                               -------------------------
                      AWG                          ohms/      (ohms/1000
                                                 kilometer       ft)
------------------------------------------------------------------------
22............................................         60.7       (18.5)
24............................................         95.1       (29.0)
------------------------------------------------------------------------

    (8) Resistance unbalance. (i) The difference in dc resistance 
between the two conductors of a pair in the completed cable shall not 
exceed the values listed in this paragraph when measured in accordance 
with the procedures of ASTM D 4566-90:

------------------------------------------------------------------------
                                                 Resistance  Maximum for
                                                 unbalance     any reel
                                               -------------------------
                      AWG                                     Individual
                                                  Average        pair
                                                  percent      percent
------------------------------------------------------------------------
22............................................          1.5          4.0
24............................................          1.5          5.0
------------------------------------------------------------------------

    (ii) The resistance unbalance between tip and ring conductors shall 
be random with respect to the direction of unbalance. That is, the 
resistance of the tip conductors shall not be consistently higher with 
respect to the ring conductors and vice versa.
    (9) Electrical variations. (i) Pairs in each length of cable having 
either a ground, cross, short, or open circuit condition shall not be 
permitted.
    (ii) The maximum number of pairs in a cable which may vary as 
specified in paragraph (h)(9)(iii) of this section from the electrical 
parameters given in this section are listed in this paragraph. These 
pairs may be excluded from the arithmetic calculation:

------------------------------------------------------------------------
                                                             Maximum No.
                                                               of pairs
                                                                 with
                     Nominal pair count                       allowable
                                                              electrical
                                                              variation
------------------------------------------------------------------------
12-100.....................................................            1
101-300....................................................            2
301-400....................................................            3
401-600....................................................            4
601 and above..............................................            6
------------------------------------------------------------------------

    (iii) Parameter variations--(A) Capacitance unbalance-to-ground. If 
the cable fails either the maximum individual pair or average 
capacitance unbalance-to-ground requirement and all individual pairs are 
3280 pF/km (1000 pF/1000 ft) or less the number of pairs specified in 
paragraph (h)(9)(ii) of this section may be eliminated from the average 
and maximum individual calculations.
    (B) Resistance unbalance. Individual pair of not more than 7 percent 
for all gauges.
    (C) Far end crosstalk. Individual pair combination of not less than 
52 dB/km (57 dB/1000 ft).
    Note: RUS recognizes that in large pair count cables (600 pair and 
above) a cross, short, or open circuit condition occasionally may 
develop in a pair which does not affect the performance of the other 
cable pairs. In these circumstances rejection of the entire cable may be 
economically unsound or repairs may be impractical. In such 
circumstances the manufacturer may desire to negotiate with the customer 
for acceptance of the cable. No more than 0.5 percent of the pairs may 
be involved.
    (i) Mechanical requirements--(1) Cable cold bend test. The completed 
cable shall be capable of meeting the requirements of ASTM D 4565-90a 
after conditioning at -20 2  deg.C except the mandrel 
diameters shall be as specified below:

------------------------------------------------------------------------
           Cable outside diameter                  Mandrel diameter
------------------------------------------------------------------------
<40 mm (1.5 in.)............................  15x
40 mm (1.5 in.)..................  20x
------------------------------------------------------------------------

    (2) Cable flame test. The completed cable shall be capable of 
meeting a maximum flame height of 3.7 m (12.0 ft) when tested in 
accordance with Underwriters Laboratories (UL) 1666 dated January 22, 
1991.

[[Page 689]]

    (3) Cable listing. All cables manufactured to the specification of 
this section at a minimum shall be listed as Communication Riser Cable 
(Type CMR) in accordance with Sections 800-50 and 800-51(b) of the 1993 
National Electrical Code.
    (j) Sheath slitting cord (optional). (1) Sheath slitting cords may 
be used in the cable structure at the option of the manufacturer.
    (2) When a sheath slitting cord is used it shall be nonhygroscopic 
and nonwicking, continuous throughout a length of cable, and of 
sufficient strength to open the sheath without breaking the cord.
    (3) Sheath slitting cords shall be capable of consistently slitting 
the jacket and/or shield for a continuous length of 0.6 m (2 ft) when 
tested in accordance with the procedure specified in appendix B of this 
section.
    (k) Identification marker and length marker. (1) Each length of 
cable shall be permanently identified as to manufacturer and year of 
manufacture.
    (2) The number of conductor pairs and their gauge size shall be 
marked on the jacket.
    (3) The marking shall be printed on the jacket at regular intervals 
of not more than 1.5 m (5 ft).
    (4) An alternative method of marking may be used if accepted by RUS 
prior to its use.
    (5) The completed cable shall have sequentially numbered length 
markers in FEET OR METERS at regular intervals of not more than 1.5 m (5 
ft) along the outside of the jacket.
    (6) The method of length marking shall be such that for any single 
length of cable, continuous sequential numbering shall be employed.
    (7) The numbers shall be dimensioned and spaced to produce good 
legibility and shall be approximately 3 mm (0.125 in.) in height. An 
occasional illegible marking is permissible if there is a legible 
marking located not more than 1.5 m (5 ft) from it.
    (8) The method of marking shall be by means of suitable surface 
markings producing a clear, distinguishable, contrasting marking 
acceptable to RUS. Where direct or transverse printing is employed, the 
characters should be indented to produce greater durability of marking. 
Any other method of length marking shall be acceptable to RUS as 
producing a marker suitable for the field. Size, shape and spacing of 
numbers, durability, and overall legibility of the marker shall be 
considered in acceptance of the method.
    (9) The accuracy of the length marking shall be such that the actual 
length of any cable section is never less than the length indicated by 
the marking and never more than one percent greater than the length 
indicated by the marking.
    (10) The color of the initial marking for a black colored jacket 
shall be either white or silver. The color of the initial marking for a 
dark grey colored jacket shall be either red or black. If the initial 
marking of the black colored jacket fails to meet the requirements of 
the preceding paragraphs, it will be permissible to either remove the 
defective marking and re-mark with the white or silver color or leave 
the defective marking on the cable and re-mark with yellow. If the 
initial marking of the dark grey colored jacket fails to meet the 
requirements of the preceding paragraphs, it will be permissible to 
either remove the defective marking and re-mark with the red or black 
color or leave the defective marking on the cable and re-mark with 
yellow. No further re-marking is permitted. Any re-marking shall be on a 
different portion of the cable circumference than any existing marking 
when possible and have a numbering sequence differing from any other 
existing marking by at least 5,000.
    (11) Any reel of cable which contains more than one set of 
sequential markings shall be labeled to indicate the color and sequence 
of marking to be used. The labeling shall be applied to the reel and 
also to the cable.
    (l) Preconnectorized cable (optional). (1) At the option of the 
manufacturer and upon request by the purchaser, cables 100 pairs and 
larger may be factory terminated in 25 pair splicing modules.
    (2) The splicing modules shall meet the requirements of RUS Bulletin 
345-54, PE-52, RUS Specification for Telephone Cable Splicing Connectors 
(Incorporated by Reference at Sec. 1755.97), and be accepted by RUS 
prior to their use.

[[Page 690]]

    (m) Acceptance testing and extent of testing. (1) The tests 
described in appendix A of this section are intended for acceptance of 
cable designs and major modifications of accepted designs. RUS decides 
what constitutes a major modification. These tests are intended to show 
the inherent capability of the manufacturer to produce cable products 
having long life and stability.
    (2) For initial acceptance, the manufacturer shall submit:
    (i) An original signature certification that the product fully 
complies with each section of the specification;
    (ii) Qualification Test Data, per appendix A of this section;
    (iii) To periodic plant inspections;
    (iv) A certification that the product does or does not comply with 
the domestic origin manufacturing provisions of the ``Buy American'' 
requirements of the Rural Electrification Act of 1938 (7 U.S.C. 901 et 
seq.);
    (v) Written user testimonials concerning performance of the product; 
and
    (vi) Other nonproprietary data deemed necessary by the Chief, 
Outside Plant Branch (Telephone).
    (3) For requalification acceptance, the manufacturer shall submit an 
original signature certification that the product fully complies with 
each section of the specification, excluding the Qualification Section, 
and a certification that the product does or does not comply with the 
domestic origin manufacturing provisions of the ``Buy American'' 
requirements of the Rural Electrification Act of 1938 (7 U.S.C. 901 et 
seq.) for acceptance by June 30 every three years. The required data and 
certification shall have been gathered within 90 days of the submission.
    (4) Initial and requalification acceptance requests should be 
addressed to: Chairman, Technical Standards Committee ``A'' (Telephone), 
Telecommunications Standards Division, Rural Utilities Service, 
Washington, DC 20250-1500.
    (5) Tests on 100 percent of completed cable. (i) The shield of each 
length of cable shall be tested for continuity using the procedures of 
ASTM D 4566-90.
    (ii) Dielectric strength between all conductors and the shield shall 
be tested to determine freedom from grounds in accordance with paragraph 
(h)(6)(ii) of this section.
    (iii) Each conductor in the completed cable shall be tested for 
continuity using the procedures of ASTM D 4566-90.
    (iv) Dielectric strength between conductors shall be tested to 
ensure freedom from shorts and crosses in accordance with paragraph 
(h)(6)(i) of this section.
    (v) Each conductor in the completed preconnectorized cable shall be 
tested for continuity.
    (vi) Each length of completed preconnectorized cable shall be tested 
for split pairs.
    (vii) The average mutual capacitance shall be measured on all 
cables. If the average mutual capacitance for the first 100 pairs tested 
from randomly selected groups is between 50 and 53 nF/km (80 to 85 nF/
mile), the remainder of the pairs need not to be tested on the 100 
percent basis. (See paragraph (h)(1) of this section).
    (6) Capability tests. Tests on a quality assurance basis shall be 
made as frequently as is required for each manufacturer to determine and 
maintain compliance with:
    (i) Performance requirements for conductor insulation and jacket 
material;
    (ii) Bonding properties of coated or laminated shielding materials;
    (iii) Sequential marking and lettering;
    (iv) Capacitance unbalance and crosstalk;
    (v) Insulation resistance;
    (vi) Conductor resistance and resistance unbalance;
    (vii) Cable cold bend and cable flame tests; and
    (viii) Mutual conductance.
    (n) Summary of records of electrical and physical tests. (1) Each 
manufacturer shall maintain a suitable summary of records for a period 
of at least 3 years for all electrical and physical tests required on 
completed cable by this section as set forth in paragraphs (m)(5) and 
(m)(6) of this section. The test data for a particular reel shall be in 
a form that it may be readily available to the purchaser or to RUS upon 
request.

[[Page 691]]

    (2) Measurements and computed values shall be rounded off to the 
number of places of figures specified for the requirement according to 
ASTM E 29-90.
    (o) Manufacturing irregularities. (1) Repairs to the shield are not 
permitted in cable supplied to the end user under this section.
    (2) No repairs or defects in the jacket are allowed.
    (p) Preparation for shipment. (1) The cable shall be shipped on 
reels unless otherwise specified or agreed to by the purchaser. The 
diameter of the drum shall be large enough to prevent damage to the 
cable from reeling or unreeling. The reels shall be substantial and so 
constructed as to prevent damage to the cable during shipment and 
handling.
    (2) A waterproof corrugated board or other means of protection 
acceptable to RUS shall be applied to the reel and shall be suitably 
secured in place to prevent damage to the cable during storage and 
shipment.
    (3) The outer end of the cable shall be securely fastened to the 
reel head so as to prevent the cable from becoming loose in transit. The 
inner end of the cable shall be securely fastened in such a way as to 
make it readily available if required for electrical testing. Spikes, 
staples, or other fastening devices which penetrate the cable jacket 
shall not be used. The method of fastening the cable ends shall be 
accepted by RUS prior to it being used.
    (4) Each length of cable shall be wound on a separate reel unless 
otherwise specified or agreed to by the purchaser.
    (5) The arbor hole shall admit a spindle 63 mm (2.5 in.) in diameter 
without binding. Steel arbor hole liners may be used but shall be 
acceptable to RUS prior to their use.
    (6) Each reel shall be plainly marked to indicate the direction in 
which it should be rolled to prevent loosening of the cable on the reel.
    (7) Each reel shall be stenciled or labeled on either one or both 
sides with the name of the manufacturer, year of manufacture, actual 
shipping length, an inner and outer end sequential length marking, 
description of the cable, reel number and the RUS cable designation:

                            Cable Designation

CT
Cable Construction
Pair Count
Conductor Gauge

A = Coated Aluminum Shield

P = Preconnectorized Cable

Example: CTAP 100-22

Terminating Cable, Coated Aluminum Shield, Preconnectorized, 100 pairs, 
22 AWG.

    (8) When preconnectorized cable is shipped, the splicing modules 
shall be protected to prevent damage during shipment and handling. The 
protection method shall be acceptable to RUS prior to its use.

(The information collection and recordkeeping requirements of this 
section have been approved by the Office of Management and Budget (OMB) 
under control number 0572-0059)

         Appendix A to Sec. 1755.870--Qualification Test Methods

    (I) The test procedures described in this appendix are for 
qualification of initial designs and major modifications of accepted 
designs. Included in paragraph (V) of this appendix are suggested 
formats that may be used in submitting test results to RUS.
    (II) Sample Selection and Preparation. (1) All testing shall be 
performed on lengths removed sequentially from the same 25 pair, 22 
gauge jacketed cable. This cable shall not have been exposed to 
temperatures in excess of 38  deg.C since its initial cool down after 
sheathing. The lengths specified are minimum lengths and if desirable 
from a laboratory testing standpoint longer lengths may be used.
    (a) Length A shall be 12 0.2 meters (40 0.5 
feet) long. Prepare the test sample by removing the jacket, shield, and 
core wrap for a sufficient distance on both ends to allow the insulated 
conductors to be flared out. Remove sufficient conductor insulation so 
that appropriate electrical test connections can be made at both ends. 
Coil the sample with a diameter of 15 to 20 times its sheath diameter. 
Two lengths are required.
    (b) Length B shall be 300 millimeters (1 foot) long. Three lengths 
are required.
    (c) Length C shall be 3 meters (10 feet) long and shall be 
maintained at 23 3  deg.C for the duration of the test. Two 
lengths are required.
    (2) Data Reference Temperature. Unless otherwise specified, all 
measurements shall be made at 23 3  deg.C.
    (III) Environmental Tests--(1) Heat Aging Test--(a) Test Samples. 
Place one sample each of lengths A and B in an oven or environmental 
chamber. The ends of sample A shall

[[Page 692]]

exit from the chamber or oven for electrical tests. Securely seal the 
oven exit holes.
    (b) Sequence of Tests. Sample B referenced in paragraph (III)(1)(a) 
of this appendix shall be subjected to the insulation compression test 
outlined in paragraph (III)(2) of this appendix.
    (c) Initial Measurements. (i) For sample A, measure the open circuit 
capacitance and conductance for each odd pair at 1, 150, and 772 
kilohertz after conditioning the sample at the data reference 
temperature for 24 hours. Calculate the average and standard deviation 
for the data of the 13 pairs on a per kilometer (per mile) basis.
    (ii) Record on suggested formats in paragraph (V) of this appendix 
or on other easily readable formats.
    (d) Heat Conditioning. (i) Immediately after completing the initial 
measurements, condition the sample for 14 days at a temperature of 65 
2  deg.C.
    (ii) At the end of this period. Measure and calculate the parameters 
given in paragraph (III)(1)(c) of this appendix. Record on suggested 
formats in paragraph (V) of this appendix or on other easily readable 
formats.
    (e) Overall Electrical Deviation. (i) Calculate the percent change 
in all average parameters between the final parameters after 
conditioning with the initial parameters in paragraph (III)(1)(c) of 
this appendix.
    (ii) The stability of the electrical parameters after completion of 
this test shall be within the following prescribed limits:
    (A) Capacitance. The average mutual capacitance shall be within 10 
percent of its original value;
    (B) The change in average mutual capacitance shall be less than 10 
percent over the frequency range of 1 to 150 kilohertz; and
    (C) Conductance. The average mutual conductance shall not exceed 3.7 
micromhos/kilometer (6 micromhos/mile) at a frequency of 1 kilohertz.
    (2) Insulation Compression Test--(a) Test Sample B. Remove jacket, 
shield, and core wrap being careful not to damage the conductor 
insulation. Remove one pair from the core and carefully separate and 
straighten the insulated conductors. Retwist the two insulated 
conductors together under sufficient tension to form 10 evenly spaced 
360 degree twists in a length of 100 millimeters (4 inches).
    (b) Sample Testing. Center the mid 50 millimeters (2 inches) of the 
twisted pair between two smooth rigid parallel metal plates measuring 50 
millimeters (2 inches) in length or diameter. Apply a 1.5 volt direct 
current potential between the conductors, using a light or buzzer to 
indicate electrical contact between the conductors. Apply a constant 
load of 67 newtons (15 pound-force) on the sample for one minute and 
monitor for evidence of contact between the conductors. Record results 
on suggested formats in paragraph (V) of this appendix or on other 
easily readable formats.
    (3) Temperature Cycling. (a) Repeat paragraphs (III)(1)(a) through 
(III)(1)(c)(ii) of this appendix for a separate set of samples A and B 
which have not been subjected to prior environmental conditioning.
    (b) Immediately after completing the measurements, subject the test 
samples to 10 cycles of temperature between -40  deg.C and +60  deg.C. 
The test samples shall be held at each temperature extreme for a minimum 
of 1.5 hours during each cycle of temperature. The air within the 
temperature cycling chamber shall be circulated throughout the duration 
of the cycling.
    (c) Repeat paragraphs (III)(1)(d)(ii) through (III)(2)(b) of this 
appendix.
    (IV) Control Sample--(1) Test Samples. One length of sample B shall 
have been maintained at 23 3  deg.C for at least 48 hours 
before the testing.
    (2) Repeat paragraphs (III)(2) through (III)(2)(b) of this appendix.
    (3) Surge Test. (a) One length of sample C shall be used to measure 
the breakdown between conductors while the other length of C shall be 
used to measure core to shield breakdown.
    (b) The samples shall be capable of withstanding, without damage, a 
single surge voltage of 20 kilovolts peak between conductors, and 35 
kilovolts peak between conductors and the shield as hereinafter 
described. The surge voltage shall be developed from a capacitor 
discharge through a forming resistor connected in parallel with the 
dielectric of the test sample. The surge generator constants shall be 
such as to produce a surge of 1.5 x 40 microseconds wave shape.
    (c) The shape of the generated wave shall be determined at a reduced 
voltage by connecting an oscilloscope across the forming resistor with 
the cable sample connected in parallel with the forming resistor. The 
capacitor bank is charged to the test voltage and then discharged 
through the forming resistor and test sample. The test sample shall be 
considered to have passed the test if there is no distinct change in the 
wave shape obtained with the initial reduced voltage compared to that 
obtained after the application of the test voltage.
    (V) The following suggested formats may be used in submitting the 
test results to RUS:

[[Page 693]]

              Environmental Conditioning ------------------

                                              Frequency 1 Kilohertz
----------------------------------------------------------------------------------------------------------------
                                                               Capacitance nF/km (nF/   Conductance micromhos/km
                                                                        mile)               (micromhos/mile)
                          Pair No.                           ---------------------------------------------------
                                                                Initial       Final       Initial       Final
----------------------------------------------------------------------------------------------------------------
 1..........................................................  ...........  ...........  ...........  ...........
 3..........................................................  ...........  ...........  ...........  ...........
 5..........................................................  ...........  ...........  ...........  ...........
 7..........................................................  ...........  ...........  ...........  ...........
 9..........................................................  ...........  ...........  ...........  ...........
11..........................................................  ...........  ...........  ...........  ...........
13..........................................................  ...........  ...........  ...........  ...........
15..........................................................  ...........  ...........  ...........  ...........
17..........................................................  ...........  ...........  ...........  ...........
19..........................................................  ...........  ...........  ...........  ...........
21..........................................................  ...........  ...........  ...........  ...........
23..........................................................  ...........  ...........  ...........  ...........
25..........................................................  ...........  ...........  ...........  ...........
Average x...................................................  ...........  ...........  ...........  ...........
Overall Percent Difference in
    Average x...............................................  ...........  ...........  ...........  ...........
----------------------------------------------------------------------------------------------------------------

             Environmental Conditioning --------------------

                                             Frequency 150 Kilohertz
----------------------------------------------------------------------------------------------------------------
                                                               Capacitance nF/km (nF/   Conductance micromhos/km
                                                                        mile)               (micromhos/mile)
                          Pair No.                           ---------------------------------------------------
                                                                Initial       Final       Initial       Final
----------------------------------------------------------------------------------------------------------------
 1..........................................................  ...........  ...........  ...........  ...........
 3..........................................................  ...........  ...........  ...........  ...........
 5..........................................................  ...........  ...........  ...........  ...........
 7..........................................................  ...........  ...........  ...........  ...........
 9..........................................................  ...........  ...........  ...........  ...........
11..........................................................  ...........  ...........  ...........  ...........
13..........................................................  ...........  ...........  ...........  ...........
15..........................................................  ...........  ...........  ...........  ...........
17..........................................................  ...........  ...........  ...........  ...........
19..........................................................  ...........  ...........  ...........  ...........
21..........................................................  ...........  ...........  ...........  ...........
23..........................................................  ...........  ...........  ...........  ...........
25..........................................................  ...........  ...........  ...........  ...........
Average x...................................................  ...........  ...........  ...........  ...........
    Overall Percent Difference in Average x.................  ...........  ...........  ...........  ...........
----------------------------------------------------------------------------------------------------------------

             Environmental Conditioning --------------------

                                             Frequency 772 Kilohertz
----------------------------------------------------------------------------------------------------------------
                                                               Capacitance nF/km (nF/   Conductance micromhos/km
                                                                        mile)               (micromhos/mile)
                          Pair No.                           ---------------------------------------------------
                                                                Initial       Final       Initial       Final
----------------------------------------------------------------------------------------------------------------
 1..........................................................  ...........  ...........  ...........  ...........
 3..........................................................  ...........  ...........  ...........  ...........
 5..........................................................  ...........  ...........  ...........  ...........
 7..........................................................  ...........  ...........  ...........  ...........
 9..........................................................  ...........  ...........  ...........  ...........
11..........................................................  ...........  ...........  ...........  ...........
13..........................................................  ...........  ...........  ...........  ...........
15..........................................................  ...........  ...........  ...........  ...........
17..........................................................  ...........  ...........  ...........  ...........
19..........................................................  ...........  ...........  ...........  ...........
21..........................................................  ...........  ...........  ...........  ...........
23..........................................................  ...........  ...........  ...........  ...........
25..........................................................  ...........  ...........  ...........  ...........
Average x...................................................  ...........  ...........  ...........  ...........
    Overall Percent Difference in...........................
    Average x...............................................  ...........  ...........  ...........  ...........
----------------------------------------------------------------------------------------------------------------


[[Page 694]]


------------------------------------------------------------------------
                                                                Failures
------------------------------------------------------------------------
Insulation Compression:
  Control.....................................................  ........
  Heat Age....................................................  ........
  Temperature Cycling.........................................  ........
Surge Test (kilovolts):
  Conductor-to-Conductor......................................  ........
  Shield-to-Conductors........................................  ........
------------------------------------------------------------------------

     Appendix B to Sec. 1755.870--Sheath Slitting Cord Qualification

    (I) This test procedure described in this appendix is for 
qualification of initial and subsequent changes in sheath slitting 
cords.
    (II) Sample selection. All testing shall be performed on two 1.2 m 
(4 ft) lengths of cable removed sequentially from the same 25 pair, 22 
gauge jacketed cable. This cable shall not have been exposed to 
temperatures in excess of 38  deg.C since its initial cool down after 
sheathing.
    (III) Test procedure. (1) Using a suitable tool, expose enough of 
the sheath slitting cord to permit grasping with needle nose pliers.
    (2) The prepared test specimens shall be maintained at a temperature 
of 23 1  deg.C for at least 4 hours immediately prior to and 
during the test.
    (3) Wrap the sheath slitting cord around the plier jaws to ensure a 
good grip.
    (4) Grasp and hold the cable in a convenient position while gently 
and firmly pulling the sheath slitting cord longitudinally in the 
direction away from the cable end. The angle of pull may vary to any 
convenient and functional degree. A small starting notch is permissible.
    (5) The sheath slitting cord is considered acceptable if the cord 
can slit the jacket and/or shield for a continuous length of 0.6 m (2 
ft) without breaking the cord.

[59 FR 30507, June 14, 1994; 59 FR 34899, July 7, 1994, as amended at 60 
FR 1711, Jan. 5, 1995]