[Code of Federal Regulations]
[Title 29, Volume 5]
[Revised as of July 1, 2003]
From the U.S. Government Printing Office via GPO Access
[CITE: 29CFR1910.106]

[Page 238-271]
 
                             TITLE 29--LABOR
 
CHAPTER XVII--OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT 
                                OF LABOR
 
PART 1910--OCCUPATIONAL SAFETY AND HEALTH STANDARDS--Table of Contents
 
                     Subpart H--Hazardous Materials
 
Sec. 1910.106  Flammable and combustible liquids.

    (a) Definitions. As used in this section:
    (1) Aerosol shall mean a material which is dispensed from its 
container as a mist, spray, or foam by a propellant under pressure.
    (2) Atmospheric tank shall mean a storage tank which has been 
designed to operate at pressures from atmospheric through 0.5 p.s.i.g.
    (3) Automotive service station shall mean that portion of property 
where flammable or combustible liquids used as motor fuels are stored 
and dispensed from fixed equipment into the fuel tanks of motor vehicles 
and shall include any facilities available for the sale and service of 
tires, batteries, and accessories, and for minor automotive maintenance 
work. Major automotive repairs, painting, body and fender work are 
excluded.
    (4) Basement shall mean a story of a building or structure having 
one-half or more of its height below ground level and to which access 
for fire fighting purposes is unduly restricted.
    (5) Boiling point shall mean the boiling point of a liquid at a 
pressure of 14.7 pounds per square inch absolute (p.s.i.a.) (760 mm.). 
Where an accurate boiling point is unavailable for the material in 
question, or for mixtures which do not have a constant boiling point, 
for purposes of this section the 10 percent point of a distillation 
performed in accordance with the Standard Method of Test for 
Distillation of Petroleum Products, ASTM D-86-62, which is incorporated 
by reference as specified in Sec. 1910.6, may be used as the boiling point 
of the liquid.
    (6) Boilover shall mean the expulsion of crude oil (or certain other 
liquids) from a burning tank. The light fractions of the crude oil 
burnoff producing a heat wave in the residue, which on reaching a water 
strata may result in the expulsion of a portion of the contents of the 
tank in the form of froth.
    (7) Bulk plant shall mean that portion of a property where flammable 
or combustible liquids are received by tank vessel, pipelines, tank car, 
or tank vehicle, and are stored or blended in bulk for the purpose of 
distributing such liquids by tank vessel, pipeline, tank car, tank 
vehicle, or container.
    (8) Chemical plant shall mean a large integrated plant or that 
portion of such a plant other than a refinery or distillery where 
flammable or combustible liquids are produced by chemical reactions or 
used in chemical reactions.
    (9) Closed container shall mean a container as herein defined, so 
sealed by means of a lid or other device that neither liquid nor vapor 
will escape from it at ordinary temperatures.
    (10) Crude petroleum shall mean hydrocarbon mixtures that have a 
flash point below 150 F. and which have not been processed in a 
refinery.
    (11) Distillery shall mean a plant or that portion of a plant where 
flammable or combustible liquids produced by fermentation are 
concentrated, and where the concentrated products may also be mixed, 
stored, or packaged.
    (12) Fire area shall mean an area of a building separated from the 
remainder of the building by construction having a fire resistance of at 
least 1 hour and having all communicating openings properly protected by 
an assembly having a fire resistance rating of at least 1 hour.
    (13) Flammable aerosol shall mean an aerosol which is required to be 
labeled ``Flammable'' under the Federal Hazardous Substances Labeling 
Act (15 U.S.C. 1261). For the purposes of paragraph (d) of this section, 
such aerosols are considered Class IA liquids.
    (14) Flashpoint means the minimum temperature at which a liquid 
gives off vapor within a test vessel in sufficient concentration to form 
an ignitable mixture with air near the surface of the liquid, and shall 
be determined as follows:
    (i) For a liquid which has a viscosity of less than 45 SUS at 100 
F. (37.8 C.), does not contain suspended solids, and

[[Page 239]]

does not have a tendency to form a surface film while under test, the 
procedure specified in the Standard Method of Test for Flashpoint by Tag 
Closed Tester (ASTM D-56-70), which is incorporated by reference as 
specified in Sec. 1910.6, shall be used.
    (ii) For a liquid which has a viscosity of 45 SUS or more at 100 F. 
(37.8 C.), or contains suspended solids, or has a tendency to form a 
surface film while under test, the Standard Method of Test for 
Flashpoint by Pensky-Martens Closed Tester (ASTM D-93-71) shall be used, 
except that the methods specified in Note 1 to section 1.1 of ASTM D-93-
71 may be used for the respective materials specified in the Note. The 
preceding ASTM standards are incorporated by reference as specified in Sec. 
1910.6.
    (iii) For a liquid that is a mixture of compounds that have 
different volatilities and flashpoints, its flashpoint shall be 
determined by using the procedure specified in paragraph (a)(14) (i) or 
(ii) of this section on the liquid in the form it is shipped. If the 
flashpoint, as determined by this test, is 100 F. (37.8 C.) or higher, 
an additional flashpoint determination shall be run on a sample of the 
liquid evaporated to 90 percent of its original volume, and the lower 
value of the two tests shall be considered the flashpoint of the 
material.
    (iv) Organic peroxides, which undergo autoaccelerating thermal 
decomposition, are excluded from any of the flashpoint determination 
methods specified in this subparagraph.
    (15) Hotel shall mean buildings or groups of buildings under the 
same management in which there are sleeping accommodations for hire, 
primarily used by transients who are lodged with or without meals 
including but not limited to inns, clubs, motels, and apartment hotels.
    (16) Institutional occupancy shall mean the occupancy or use of a 
building or structure or any portion thereof by persons harbored or 
detained to receive medical, charitable or other care or treatment, or 
by persons involuntarily detained.
    (17) Liquid shall mean, for the purpose of this section, any 
material which has a fluidity greater than that of 300 penetration 
asphalt when tested in accordance with ASTM Test for Penetration for 
Bituminous Materials, D-5-65, which is incorporated by reference as 
specified in Sec. 1910.6. When not otherwise identified, the term liquid 
shall include both flammable and combustible liquids.
    (18) Combustible liquid means any liquid having a flashpoint at or 
above 100 F. (37.8 C.) Combustible liquids shall be divided into two 
classes as follows:
    (i) Class II liquids shall include those with flashpoints at or 
above 100 F. (37.8 C.) and below 140 F. (60 C.), except any mixture 
having components with flashpoints of 200 F. (93.3 C.) or higher, the 
volume of which make up 99 percent or more of the total volume of the 
mixture.
    (ii) Class III liquids shall include those with flashpoints at or 
above 140 F. (60 C.) Class III liquids are subdivided into two 
subclasses:
    (a) Class IIIA liquids shall include those with flashpoints at or 
above 140 F. (60 C.) and below 200 F. (93.3 C.), except any mixture 
having components with flashpoints of 200 F. (93.3 C.), or higher, the 
total volume of which make up 99 percent or more of the total volume of 
the mixture.
    (b) Class IIIB liquids shall include those with flashpoints at or 
above 200 F. (93.3 C.). This section does not cover Class IIIB 
liquids. Where the term ``Class III liquids is used in this section, it 
shall mean only Class IIIA liquids.
    (iii) When a combustible liquid is heated for use to within 30 F. 
(16.7 C.) of its flashpoint, it shall be handled in accordance with the 
requirements for the next lower class of liquids.
    (19) Flammable liquid means any liquid having a flashpoint below 100 
F. (37.8 C.), except any mixture having components with flashpoints of 
100 F. (37.8 C.) or higher, the total of which make up 99 percent or 
more of the total volume of the mixture. Flammable liquids shall be 
known as Class I liquids. Class I liquids are divided into three classes 
as follows:
    (i) Class IA shall include liquids having flashpoints below 73 F. 
(22.8 C.) and having a boiling point below 100 F. (37.8 C.).

[[Page 240]]

    (ii) Class IB shall include liquids having flashpoints below 73 F. 
(22.8 C.) and having a boiling point at or above 100 F. (37.8 C.).
    (iii) Class IC shall include liquids having flashpoints at or above 
73 F. (22.8 C.) and below 100 F. (37.8 C.).
    (20) Unstable (reactive) liquid shall mean a liquid which in the 
pure state or as commercially produced or transported will vigorously 
polymerize, decompose, condense, or will become self-reactive under 
conditions of shocks, pressure, or temperature.
    (21) Low-pressure tank shall mean a storage tank which has been 
designed to operate at pressures above 0.5 p.s.i.g. but not more than 15 
p.s.i.g.
    (22) Marine service station shall mean that portion of a property 
where flammable or combustible liquids used as fuels are stored and 
dispensed from fixed equipment on shore, piers, wharves, or floating 
docks into the fuel tanks of self-propelled craft, and shall include all 
facilities used in connection therewith.
    (23) Mercantile occupancy shall mean the occupancy or use of a 
building or structure or any portion thereof for the displaying, 
selling, or buying of goods, wares, or merchandise.
    (24) Office occupancy shall mean the occupancy or use of a building 
or structure or any portion thereof for the transaction of business, or 
the rendering or receiving of professional services.
    (25) Portable tank shall mean a closed container having a liquid 
capacity over 60 U.S. gallons and not intended for fixed installation.
    (26) Pressure vessel shall mean a storage tank or vessel which has 
been designed to operate at pressures above 15 p.s.i.g.
    (27) Protection for exposure shall mean adequate fire protection for 
structures on property adjacent to tanks, where there are employees of 
the establishment.
    (28) Refinery shall mean a plant in which flammable or combustible 
liquids are produced on a commercial scale from crude petroleum, natural 
gasoline, or other hydrocarbon sources.
    (29) Safety can shall mean an approved container, of not more than 5 
gallons capacity, having a spring-closing lid and spout cover and so 
designed that it will safely relieve internal pressure when subjected to 
fire exposure.
    (30) Vapor pressure shall mean the pressure, measured in pounds per 
square inch (absolute) exerted by a volatile liquid as determined by the 
``Standard Method of Test for Vapor Pressure of Petroleum Products (Reid 
Method),'' American Society for Testing and Materials ASTM D323-68, 
which is incorporated by reference as specified in Sec. 1910.6.
    (31) Ventilation as specified in this section is for the prevention 
of fire and explosion. It is considered adequate if it is sufficient to 
prevent accumulation of significant quantities of vapor-air mixtures in 
concentration over one-fourth of the lower flammable limit.
    (32) Storage: Flammable or combustible liquids shall be stored in a 
tank or in a container that complies with paragraph (d)(2) of this 
section.
    (33) Barrel shall mean a volume of 42 U.S. gallons.
    (34) Container shall mean any can, barrel, or drum.
    (35) Approved unless otherwise indicated, approved, or listed by a 
nationally recognized testing laboratory. Refer to Sec. 1910.7 for 
definition of nationally recognized testing laboratory.
    (36) Listed see ``approved'' in Sec. 1910.106(a)(35).
    (37) SUS means Saybolt Universal Seconds as determined by the 
Standard Method of Test for Saybolt Viscosity (ASTM D-88-56), and may be 
determined by use of the SUS conversion tables specified in ASTM Method 
D2161-66 following determination of viscosity in accordance with the 
procedures specified in the Standard Method of Test for Viscosity of 
Transparent and Opaque Liquids (ASTM D445-65).
    (38) Viscous means a viscosity of 45 SUS or more.
    (b) Tank storage--(1) Design and construction of tanks--(i) 
Materials. (a) Tanks shall be built of steel except as provided in 
paragraphs (b)(1)(i) (b) through (e) of this section.
    (b) Tanks may be built of materials other than steel for 
installation underground or if required by the properties of the liquid 
stored. Tanks located above ground or inside buildings shall be of 
noncombustible construction.

[[Page 241]]

    (c) Tanks built of materials other than steel shall be designed to 
specifications embodying principles recognized as good engineering 
design for the material used.
    (d) Unlined concrete tanks may be used for storing flammable or 
combustible liquids having a gravity of 40 API or heavier. Concrete 
tanks with special lining may be used for other services provided the 
design is in accordance with sound engineering practice.
    (e) [Reserved]
    (f) Special engineering consideration shall be required if the 
specific gravity of the liquid to be stored exceeds that of water or if 
the tanks are designed to contain flammable or combustible liquids at a 
liquid temperature below 0 F.
    (ii) Fabrication. (a) [Reserved]
    (b) Metal tanks shall be welded, riveted, and caulked, brazed, or 
bolted, or constructed by use of a combination of these methods. Filler 
metal used in brazing shall be nonferrous metal or an alloy having a 
melting point above 1000 F. and below that of the metal joined.
    (iii) Atmospheric tanks. (a) Atmospheric tanks shall be built in 
accordance with acceptable good standards of design. Atmospheric tanks 
may be built in accordance with the following consensus standards that 
are incorporated by reference as specified in Sec. 1910.6:
    (1) Underwriters' Laboratories, Inc., Subjects No. 142, Standard for 
Steel Aboveground Tanks for Flammable and Combustible Liquids, 1968; No. 
58, Standard for Steel Underground Tanks for Flammable and Combustible 
Liquids, Fifth Edition, December 1961; or No. 80, Standard for Steel 
Inside Tanks for Oil-Burner Fuel, September 1963.
    (2) American Petroleum Institute Standards No. 12A, Specification 
for Oil Storage Tanks with Riveted Shells, Seventh Edition, September 
1951, or No. 650, Welded Steel Tanks for Oil Storage, Third Edition, 
1966.
    (3) American Petroleum Institute Standards No. 12B, Specification 
for Bolted Production Tanks, Eleventh Edition, May 1958, and Supplement 
1, March 1962; No. 12D, Specification for Large Welded Production Tanks, 
Seventh Edition, August 1957; or No. 12F, Specification for Small Welded 
Production Tanks, Fifth Edition, March 1961. Tanks built in accordance 
with these standards shall be used only as production tanks for storage 
of crude petroleum in oil-producing areas.
    (b) Tanks designed for underground service not exceeding 2,500 
gallons capacity may be used aboveground.
    (c) Low-pressure tanks and pressure vessels may be used as 
atmospheric tanks.
    (d) Atmospheric tanks shall not be used for the storage of a 
flammable or combustible liquid at a temperature at or above its boiling 
point.
    (iv) Low pressure tanks. (a) The normal operating pressure of the 
tank shall not exceed the design pressure of the tank.
    (b) Low-pressure tanks shall be built in accordance with acceptable 
standards of design. Low-pressure tanks may be built in accordance with 
the following consensus standards that are incorporated by reference as 
specified in Sec. 1910.6:
    (1) American Petroleum Institute Standard No. 620. Recommended Rules 
for the Design and Construction of Large, Welded, Low-Pressure Storage 
Tanks, Third Edition, 1966.
    (2) The principles of the Code for Unfired Pressure Vessels, Section 
VIII of the ASME Boiler and Pressure Vessels Code, 1968.
    (c) Atmospheric tanks built according to Underwriters' Laboratories, 
Inc., requirements in subdivision (iii)(a) of and shall be limited to 
2.5 p.s.i.g. under emergency venting conditions.

This paragraph may be used for operating pressures not exceeding 1 
p.s.i.g.
    (d) Pressure vessels may be used as low-pressure tanks.
    (v) Pressure vessels. (a) The normal operating pressure of the 
vessel shall not exceed the design pressure of the vessel.
    (b) Pressure vessels shall be built in accordance with the Code for 
Unfired Pressure Vessels, Section VIII of the ASME Boiler and Pressure 
Vessel Code 1968.
    (vi) Provisions for internal corrosion. When tanks are not designed 
in accordance with the American Petroleum Institute, American Society of 
Mechanical Engineers, or the Underwriters' Laboratories, Inc.'s, 
standards, or if corrosion is anticipated beyond that

[[Page 242]]

provided for in the design formulas used, additional metal thickness or 
suitable protective coatings or linings shall be provided to compensate 
for the corrosion loss expected during the design life of the tank.
    (2) Installation of outside aboveground tanks.
    (i) [Reserved]
    (ii) Spacing (shell-to-shell) between aboveground tanks. (a) The 
distance between any two flammable or combustible liquid storage tanks 
shall not be less than 3 feet.
    (b) Except as provided in paragraph (b)(2)(ii)(c) of this section, 
the distance between any two adjacent tanks shall not be less than one-
sixth the sum of their diameters. When the diameter of one tank is less 
than one-half the diameter of the adjacent tank, the distance between 
the two tanks shall not be less than one-half the diameter of the 
smaller tank.
    (c) Where crude petroleum in conjunction with production facilities 
are located in noncongested areas and have capacities not exceeding 
126,000 gallons (3,000 barrels), the distance between such tanks shall 
not be less than 3 feet.
    (d) Where unstable flammable or combustible liquids are stored, the 
distance between such tanks shall not be less than one-half the sum of 
their diameters.
    (e) When tanks are compacted in three or more rows or in an 
irregular pattern, greater spacing or other means shall be provided so 
that inside tanks are accessible for firefighting purposes.
    (f) The minimum separation between a liquefied petroleum gas 
container and a flammable or combustible liquid storage tank shall be 20 
feet, except in the case of flammable or combustible liquid tanks 
operating at pressures exceeding 2.5 p.s.i.g. or equipped with emergency 
venting which will permit pressures to exceed 2.5 p.s.i.g. in which case 
the provisions of subdivisions (a) and (b) of this subdivision shall 
apply. Suitable means shall be taken to prevent the accumulation of 
flammable or combustible liquids under adjacent liquefied petroleum gas 
containers such as by diversion curbs or grading. When flammable or 
combustible liquid storage tanks are within a diked area, the liquefied 
petroleum gas containers shall be outside the diked area and at least 10 
feet away from the centerline of the wall of the diked area. The 
foregoing provisions shall not apply when liquefied petroleum gas 
containers of 125 gallons or less capacity are installed adjacent to 
fuel oil supply tanks of 550 gallons or less capacity.
    (iii) [Reserved]
    (iv) Normal venting for aboveground tanks. (a) Atmospheric storage 
tanks shall be adequately vented to prevent the development of vacuum or 
pressure sufficient to distort the roof of a cone roof tank or exceeding 
the design pressure in the case of other atmospheric tanks, as a result 
of filling or emptying, and atmospheric temperature changes.
    (b) Normal vents shall be sized either in accordance with: (1) The 
American Petroleum Institute Standard 2000 (1968), Venting Atmospheric 
and Low-Pressure Storage Tanks, which is incorporated by reference as 
specified in Sec. 1910.6; or (2) other accepted standard; or (3) shall be 
at least as large as the filling or withdrawal connection, whichever is 
larger but in no case less than 1\1/4\ inch nominal inside diameter.
    (c) Low-pressure tanks and pressure vessels shall be adequately 
vented to prevent development of pressure or vacuum, as a result of 
filling or emptying and atmospheric temperature changes, from exceeding 
the design pressure of the tank or vessel. Protection shall also be 
provided to prevent overpressure from any pump discharging into the tank 
or vessel when the pump discharge pressure can exceed the design 
pressure of the tank or vessel.
    (d) If any tank or pressure vessel has more than one fill or 
withdrawal connection and simultaneous filling or withdrawal can be 
made, the vent size shall be based on the maximum anticipated 
simultaneous flow.
    (e) Unless the vent is designed to limit the internal pressure 2.5 
p.s.i. or less, the outlet of vents and vent drains shall be arranged to 
discharge in such a manner as to prevent localized overheating of any 
part of the tank in the event vapors from such vents are ignited.

[[Page 243]]

    (f) Tanks and pressure vessels storing Class IA liquids shall be 
equipped with venting devices which shall be normally closed except when 
venting to pressure or vacuum conditions. Tanks and pressure vessels 
storing Class IB and IC liquids shall be equipped with venting devices 
which shall be normally closed except when venting under pressure or 
vacuum conditions, or with approved flame arresters.

Exemption: Tanks of 3,000 bbls. capacity or less containing crude 
petroleum in crude-producing areas; and, outside aboveground atmospheric 
tanks under 1,000 gallons capacity containing other than Class IA 
flammable liquids may have open vents. (See subdivision (vi)(b) of this 
subparagraph.)
    (g) Flame arresters or venting devices required in subdivision (f) 
of this subdivision may be omitted for Class IB and IC liquids where 
conditions are such that their use may, in case of obstruction, result 
in tank damage.
    (v) Emergency relief venting for fire exposure for aboveground 
tanks. (a) Every aboveground storage tank shall have some form of 
construction or device that will relieve excessive internal pressure 
caused by exposure fires.
    (b) In a vertical tank the construction referred to in subdivision 
(a) of this subdivision may take the form of a floating roof, lifter 
roof, a weak roof-to-shell seam, or other approved pressure relieving 
construction. The weak roof-to-shell seam shall be constructed to fail 
preferential to any other seam.
    (c) Where entire dependence for emergency relief is placed upon 
pressure relieving devices, the total venting capacity of both normal 
and emergency vents shall be enough to prevent rupture of the shell or 
bottom of the tank if vertical, or of the shell or heads if horizontal. 
If unstable liquids are stored, the effects of heat or gas resulting 
from polymerization, decomposition, condensation, or self-reactivity 
shall be taken into account. The total capacity of both normal and 
emergency venting devices shall be not less than that derived from Table 
H-10 except as provided in subdivision (e) or (f) of this subdivision. 
Such device may be a self-closing manhole cover, or one using long bolts 
that permit the cover to lift under internal pressure, or an additional 
or larger relief valve or valves. The wetted area of the tank shall be 
calculated on the basis of 55 percent of the total exposed area of a 
sphere or spheroid, 75 percent of the total exposed area of a horizontal 
tank and the first 30 feet above grade of the exposed shell area of a 
vertical tank.

       Table H-10--Wetted Area Versus Cubic Feet Free Air Per Hour
                         [14.7 psia and 60 F.]
------------------------------------------------------------------------
                            Square                  Square
Square feet      CFH         feet         CFH        feet         CFH
------------------------------------------------------------------------
        20       21,100         200     211,000       1,000     524,000
        30       31,600         250     239,000       1,200     557,000
        40       42,100         300     265,000       1,400     587,000
        50       52,700         350     288,000       1,600     614,000
        60       63,200         400     312,000       1,800     639,000
        70       73,700         500     354,000       2,000     662,000
        80       84,200         600     392,000       2,400     704,000
        90       94,800         700     428,000       2,800     742,000
       100      105,000         800     462,000         and
       120      126,000         900     493,000        over
       140      147,000       1,000     524,000
       160      168,000
       180      190,000
       200      211,000
------------------------------------------------------------------------

    (d) For tanks and storage vessels designed for pressure over 1 
p.s.i.g., the total rate of venting shall be determined in accordance 
with Table H-10, except that when the exposed wetted area of the surface 
is greater than 2,800 square feet, the total rate of venting shall be 
calculated by the following formula:

CFH = 1,107A \0.82\

Where;

CFH = Venting requirement, in cubic feet of free air per hour.

[[Page 244]]

A = Exposed wetted surface, in square feet.

    Note: The foregoing formula is based on Q=21,000A\0.82\.
    (e) The total emergency relief venting capacity for any specific 
stable liquid may be determined by the following formula:

V = 1337 / L[radic]M

V = Cubic feet of free air per hour from Table H-10.
L = Latent heat of vaporization of specific liquid in B.t.u. per pound.
M = Molecular weight of specific liquids.

    (f) The required airflow rate of subdivision (c) or (e) of this 
subdivision may be multiplied by the appropriate factor listed in the 
following schedule when protection is provided as indicated. Only one 
factor may be used for any one tank.

    0.5 for drainage in accordance with subdivision (vii)(b) of this 
subparagraph for tanks over 200 square feet of wetted area.
    0.3 for approved water spray.
    0.3 for approved insulation.
    0.15 for approved water spray with approved insulation.

    (g) The outlet of all vents and vent drains on tanks equipped with 
emergency venting to permit pressures exceeding 2.5 p.s.i.g. shall be 
arranged to discharge in such a way as to prevent localized overheating 
of any part of the tank, in the event vapors from such vents are 
ignited.
    (h) Each commercial tank venting device shall have stamped on it the 
opening pressure, the pressure at which the valve reaches the full open 
position, and the flow capacity at the latter pressure, expressed in 
cubic feet per hour of air at 60 F. and at a pressure of 14.7 p.s.i.a.
    (i) The flow capacity of tank venting devices 12 inches and smaller 
in nominal pipe size shall be determined by actual test of each type and 
size of vent. These flow tests may be conducted by the manufacturer if 
certified by a qualified impartial observer, or may be conducted by an 
outside agency. The flow capacity of tank venting devices larger than 12 
inches nominal pipe size, including manhole covers with long bolts or 
equivalent, may be calculated provided that the opening pressure is 
actually measured, the rating pressure and corresponding free orifice 
area are stated, the word ``calculated'' appears on the nameplate, and 
the computation is based on a flow coefficient of 0.5 applied to the 
rated orifice area.
    (vi) Vent piping for aboveground tanks. (a) Vent piping shall be 
constructed in accordance with paragraph (c) of this section.
    (b) Where vent pipe outlets for tanks storing Class I liquids are 
adjacent to buildings or public ways, they shall be located so that the 
vapors are released at a safe point outside of buildings and not less 
than 12 feet above the adjacent ground level. In order to aid their 
dispersion, vapors shall be discharged upward or horizontally away from 
closely adjacent walls. Vent outlets shall be located so that flammable 
vapors will not be trapped by eaves or other obstructions and shall be 
at least five feet from building openings.
    (c) When tank vent piping is manifolded, pipe sizes shall be such as 
to discharge, within the pressure limitations of the system, the vapors 
they may be required to handle when manifolded tanks are subject to the 
same fire exposure.
    (vii) Drainage, dikes, and walls for aboveground tanks--(a) Drainage 
and diked areas. The area surrounding a tank or a group of tanks shall 
be provided with drainage as in subdivision (b) of this subdivision, or 
shall be diked as provided in subdivision (c) of this subdivision, to 
prevent accidental discharge of liquid from endangering adjoining 
property or reaching waterways.
    (b) Drainage. Where protection of adjoining property or waterways is 
by means of a natural or manmade drainage system, such systems shall 
comply with the following:
    (1) [Reserved]
    (2) The drainage system shall terminate in vacant land or other area 
or in an impounding basin having a capacity not smaller than that of the 
largest tank served. This termination area and the route of the drainage 
system shall be so located that, if the flammable or combustible liquids 
in the drainage system are ignited, the fire will not seriously expose 
tanks or adjoining property.

[[Page 245]]

    (c) Diked areas. Where protection of adjoining property or waterways 
is accomplished by retaining the liquid around the tank by means of a 
dike, the volume of the diked area shall comply with the following 
requirements:
    (1) Except as provided in subdivision (2) of this subdivision, the 
volumetric capacity of the diked area shall not be less than the 
greatest amount of liquid that can be released from the largest tank 
within the diked area, assuming a full tank. The capacity of the diked 
area enclosing more than one tank shall be calculated by deducting the 
volume of the tanks other than the largest tank below the height of the 
dike.
    (2) For a tank or group of tanks with fixed roofs containing crude 
petroleum with boilover characteristics, the volumetric capacity of the 
diked area shall be not less than the capacity of the largest tank 
served by the enclosure, assuming a full tank. The capacity of the diked 
enclosure shall be calculated by deducting the volume below the height 
of the dike of all tanks within the enclosure.
    (3) Walls of the diked area shall be of earth, steel, concrete or 
solid masonry designed to be liquidtight and to withstand a full 
hydrostatic head. Earthen walls 3 feet or more in height shall have a 
flat section at the top not less than 2 feet wide. The slope of an 
earthen wall shall be consistent with the angle of repose of the 
material of which the wall is constructed.
    (4) The walls of the diked area shall be restricted to an average 
height of 6 feet above interior grade.
    (5) [Reserved]
    (6) No loose combustible material, empty or full drum or barrel, 
shall be permitted within the diked area.
    (viii) Tank openings other than vents for aboveground tanks.
    (a)-(c) [Reserved]
    (d) Openings for gaging shall be provided with a vaportight cap or 
cover.
    (e) For Class IB and Class IC liquids other than crude oils, 
gasolines, and asphalts, the fill pipe shall be so designed and 
installed as to minimize the possibility of generating static 
electricity. A fill pipe entering the top of a tank shall terminate 
within 6 inches of the bottom of the tank and shall be installed to 
avoid excessive vibration.
    (f) Filling and emptying connections which are made and broken shall 
be located outside of buildings at a location free from any source of 
ignition and not less than 5 feet away from any building opening. Such 
connection shall be closed and liquidtight when not in use. The 
connection shall be properly identified.
    (3) Installation of underground tanks--(i) Location. Excavation for 
underground storage tanks shall be made with due care to avoid 
undermining of foundations of existing structures. Underground tanks or 
tanks under buildings shall be so located with respect to existing 
building foundations and supports that the loads carried by the latter 
cannot be transmitted to the tank. The distance from any part of a tank 
storing Class I liquids to the nearest wall of any basement or pit shall 
be not less than 1 foot, and to any property line that may be built 
upon, not less than 3 feet. The distance from any part of a tank storing 
Class II or Class III liquids to the nearest wall of any basement, pit 
or property line shall be not less than 1 foot.
    (ii) Depth and cover. Underground tanks shall be set on firm 
foundations and surrounded with at least 6 inches of noncorrosive, inert 
materials such as clean sand, earth, or gravel well tamped in place. The 
tank shall be placed in the hole with care since dropping or rolling the 
tank into the hole can break a weld, puncture or damage the tank, or 
scrape off the protective coating of coated tanks. Tanks shall be 
covered with a minimum of 2 feet of earth, or shall be covered with not 
less than 1 foot of earth, on top of which shall be placed a slab of 
reinforced concrete not less than 4 inches thick. When underground tanks 
are, or are likely to be, subject to traffic, they shall be protected 
against damage from vehicles passing over them by at least 3 feet of 
earth cover, or 18 inches of well-tamped earth, plus 6 inches of 
reinforced concrete or 8 inches of asphaltic concrete. When asphaltic or 
reinforced concrete paving is used as part of the protection, it shall 
extend at least 1 foot horizontally beyond the outline of the tank in 
all directions.

[[Page 246]]

    (iii) Corrosion protection. Corrosion protection for the tank and 
its piping shall be provided by one or more of the following methods:
    (a) Use of protective coatings or wrappings;
    (b) Cathodic protection; or,
    (c) Corrosion resistant materials of construction.
    (iv) Vents. (a) Location and arrangement of vents for Class I 
liquids. Vent pipes from tanks storing Class I liquids shall be so 
located that the discharge point is outside of buildings, higher than 
the fill pipe opening, and not less than 12 feet above the adjacent 
ground level. Vent pipes shall discharge only upward in order to 
disperse vapors. Vent pipes 2 inches or less in nominal inside diameter 
shall not be obstructed by devices that will cause excessive back 
pressure. Vent pipe outlets shall be so located that flammable vapors 
will not enter building openings, or be trapped under eaves or other 
obstructions. If the vent pipe is less than 10 feet in length, or 
greater than 2 inches in nominal inside diameter, the outlet shall be 
provided with a vacuum and pressure relief device or there shall be an 
approved flame arrester located in the vent line at the outlet or within 
the approved distance from the outlet.
    (b) Size of vents. Each tank shall be vented through piping adequate 
in size to prevent blow-back of vapor or liquid at the fill opening 
while the tank is being filled. Vent pipes shall be not less than 1\1/4\ 
inch nominal inside diameter.

                     Table H-11--Vent Line Diameters
------------------------------------------------------------------------
                                                   Pipe length \1\
             Maximum flow GPM              -----------------------------
                                             50 feet  100 feet  200 feet
------------------------------------------------------------------------
                                            Inches    Inches    Inches

100.......................................    1\1/4\    1\1/4\    1\1/4\
200.......................................    1\1/4\    1\1/4\    1\1/4\
300.......................................    1\1/4\    1\1/4\    1\1/2\
400.......................................    1\1/4\    1\1/2\       2
500.......................................    1\1/2\    1\1/2\       2
600.......................................    1\1/2\       2         2
700.......................................       2         2         2
800.......................................       2         2         3
900.......................................       2         2         3
1,000.....................................       2         2         3
------------------------------------------------------------------------
\1\ Vent lines of 50 ft., 100 ft., and 200 ft. of pipe plus 7 ells.

    (c) Location and arrangement of vents for Class II or Class III 
liquids. Vent pipes from tanks storing Class II or Class III flammable 
liquids shall terminate outside of the building and higher than the fill 
pipe opening. Vent outlets shall be above normal snow level. They may be 
fitted with return bends, coarse screens or other devices to minimize 
ingress of foreign material.
    (d) Vent piping shall be constructed in accordance with paragraph 
(c) of this section. Vent pipes shall be so laid as to drain toward the 
tank without sags or traps in which liquid can collect. They shall be 
located so that they will not be subjected to physical damage. The tank 
end of the vent pipe shall enter the tank through the top.
    (e) When tank vent piping is manifolded, pipe sizes shall be such as 
to discharge, within the pressure limitations of the system, the vapors 
they may be required to handle when manifolded tanks are filled 
simultaneously.
    (v) Tank openings other than vents. (a) Connections for all tank 
openings shall be vapor or liquid tight.
    (b) Openings for manual gaging, if independent of the fill pipe, 
shall be provided with a liquid-tight cap or cover. If inside a 
building, each such opening shall be protected against liquid overflow 
and possible vapor release by means of a spring loaded check valve or 
other approved device.
    (c) Fill and discharge lines shall enter tanks only through the top. 
Fill lines shall be sloped toward the tank.
    (d) For Class IB and Class IC liquids other than crude oils, 
gasolines, and asphalts, the fill pipe shall be so designed and 
installed as to minimize the possibility of generating static 
electricity by terminating within 6 inches of the bottom of the tank.
    (e) Filling and emptying connections which are made and broken shall 
be located outside of buildings at a location free from any source of 
ignition and not less than 5 feet away from any building opening. Such 
connection shall be closed and liquidtight when not in use. The 
connection shall be properly identified.
    (4) Installation of tanks inside of buildings--(i) Location. Tanks 
shall not be permitted inside of buildings except as provided in 
paragraphs (e), (g), (h), or (i) of this section.

[[Page 247]]

    (ii) Vents. Vents for tanks inside of buildings shall be as provided 
in subparagraphs (2) (iv), (v), (vi)(b), and (3)(iv) of this paragraph, 
except that emergency venting by the use of weak roof seams on tanks 
shall not be permitted. Vents shall discharge vapors outside the 
buildings.
    (iii) Vent piping. Vent piping shall be constructed in accordance 
with paragraph (c) of this section.
    (iv) Tank openings other than vents. (a) Connections for all tank 
openings shall be vapor or liquidtight. Vents are covered in subdivision 
(ii) of this subparagraph.
    (b) Each connection to a tank inside of buildings through which 
liquid can normally flow shall be provided with an internal or an 
external valve located as close as practical to the shell of the tank. 
Such valves, when external, and their connections to the tank shall be 
of steel except when the chemical characteristics of the liquid stored 
are incompatible with steel. When materials other than steel are 
necessary, they shall be suitable for the pressures, structural 
stresses, and temperatures involved, including fire exposures.
    (c) Flammable or combustible liquid tanks located inside of 
buildings, except in one-story buildings designed and protected for 
flammable or combustible liquid storage, shall be provided with an 
automatic-closing heat-actuated valve on each withdrawal connection 
below the liquid level, except for connections used for emergency 
disposal, to prevent continued flow in the event of fire in the vicinity 
of the tank. This function may be incorporated in the valve required in 
(b) of this subdivision, and if a separate valve, shall be located 
adjacent to the valve required in (b) of this subdivision.
    (d) Openings for manual gaging, if independent of the fill pipe (see 
(f) of this subdivision), shall be provided with a vaportight cap or 
cover. Each such opening shall be protected against liquid overflow and 
possible vapor release by means of a spring loaded check valve or other 
approved device.
    (e) For Class IB and Class IC liquids other than crude oils, 
gasolines, and asphalts, the fill pipe shall be so designed and 
installed as to minimize the possibility of generating static 
electricity by terminating within 6 inches of the bottom of the tank.
    (f) The fill pipe inside of the tank shall be installed to avoid 
excessive vibration of the pipe.
    (g) The inlet of the fill pipe shall be located outside of buildings 
at a location free from any source of ignition and not less than 5 feet 
away from any building opening. The inlet of the fill pipe shall be 
closed and liquidtight when not in use. The fill connection shall be 
properly identified.
    (h) Tanks inside buildings shall be equipped with a device, or other 
means shall be provided, to prevent overflow into the building.
    (5) Supports, foundations, and anchorage for all tank locations--(i) 
General. Tank supports shall be installed on firm foundations. Tank 
supports shall be of concrete, masonry, or protected steel. Single wood 
timber supports (not cribbing) laid horizontally may be used for outside 
aboveground tanks if not more than 12 inches high at their lowest point.
    (ii) Fire resistance. Steel supports or exposed piling shall be 
protected by materials having a fire resistance rating of not less than 
2 hours, except that steel saddles need not be protected if less than 12 
inches high at their lowest point. Water spray protection or its 
equivalent may be used in lieu of fire-resistive materials to protect 
supports.
    (iii) Spheres. The design of the supporting structure for tanks such 
as spheres shall receive special engineering consideration.
    (iv) Load distribution. Every tank shall be so supported as to 
prevent the excessive concentration of loads on the supporting portion 
of the shell.
    (v) Foundations. Tanks shall rest on the ground or on foundations 
made of concrete, masonry, piling, or steel. Tank foundations shall be 
designed to minimize the possibility of uneven settling of the tank and 
to minimize corrosion in any part of the tank resting on the foundation.
    (vi) Flood areas. Where a tank is located in an area that may be 
subjected to flooding, the applicable precautions outlined in this 
subdivision shall be observed.

[[Page 248]]

    (a) No aboveground vertical storage tank containing a flammable or 
combustible liquid shall be located so that the allowable liquid level 
within the tank is below the established maximum flood stage, unless the 
tank is provided with a guiding structure such as described in (m), (n), 
and (o) of this subdivision.
    (b) Independent water supply facilities shall be provided at 
locations where there is no ample and dependable public water supply 
available for loading partially empty tanks with water.
    (c) In addition to the preceding requirements, each tank so located 
that more than 70 percent, but less than 100 percent, of its allowable 
liquid storage capacity will be submerged at the established maximum 
flood stage, shall be safeguarded by one of the following methods: Tank 
shall be raised, or its height shall be increased, until its top extends 
above the maximum flood stage a distance equivalent to 30 percent or 
more of its allowable liquid storage capacity: Provided, however, That 
the submerged part of the tank shall not exceed two and one-half times 
the diameter. Or, as an alternative to the foregoing, adequate 
noncombustible structural guides, designed to permit the tank to float 
vertically without loss of product, shall be provided.
    (d) Each horizontal tank so located that more than 70 percent of its 
storage capacity will be submerged at the established flood stage, shall 
be anchored, attached to a foundation of concrete or of steel and 
concrete, of sufficient weight to provide adequate load for the tank 
when filled with flammable or combustible liquid and submerged by flood 
waters to the established flood stage, or adequately secured by other 
means.
    (e) [Reserved]
    (f) At locations where there is no ample and dependable water 
supply, or where filling of underground tanks with liquids is 
impracticable because of the character of their contents, their use, or 
for other reasons, each tank shall be safeguarded against movement when 
empty and submerged by high ground water or flood waters by anchoring, 
weighting with concrete or other approved solid loading material, or 
securing by other means. Each such tank shall be so constructed and 
installed that it will safely resist external pressures due to high 
ground water or flood waters.
    (g) At locations where there is an ample and dependable water supply 
available, underground tanks containing flammable or combustible 
liquids, so installed that more than 70 percent of their storage 
capacity will be submerged at the maximum flood stage, shall be so 
anchored, weighted, or secured by other means, as to prevent movement of 
such tanks when filled with flammable or combustible liquids, and 
submerged by flood waters to the established flood stage.
    (h) Pipe connections below the allowable liquid level in a tank 
shall be provided with valves or cocks located as closely as practicable 
to the tank shell. Such valves and their connections to tanks shall be 
of steel or other material suitable for use with the liquid being 
stored. Cast iron shall not be permitted.
    (i) At locations where an independent water supply is required, it 
shall be entirely independent of public power and water supply. 
Independent source of water shall be available when flood waters reach a 
level not less than 10 feet below the bottom of the lowest tank on a 
property.
    (j) The self-contained power and pumping unit shall be so located or 
so designed that pumping into tanks may be carried on continuously 
throughout the rise in flood waters from a level 10 feet below the 
lowest tank to the level of the potential flood stage.
    (k) Capacity of the pumping unit shall be such that the rate of rise 
of water in all tanks shall be equivalent to the established potential 
average rate of rise of flood waters at any stage.
    (l) Each independent pumping unit shall be tested periodically to 
insure that it is in satisfactory operating condition.
    (m) Structural guides for holding floating tanks above their 
foundations shall be so designed that there will be no resistance to the 
free rise of a tank, and shall be constructed of noncombustible 
material.
    (n) The strength of the structure shall be adequate to resist 
lateral

[[Page 249]]

movement of a tank subject to a horizontal force in any direction 
equivalent to not less than 25 pounds per square foot acting on the 
projected vertical cross-sectional area of the tank.
    (o) Where tanks are situated on exposed points or bends in a 
shoreline where swift currents in flood waters will be present, the 
structures shall be designed to withstand a unit force of not less than 
50 pounds per square foot.
    (p) The filling of a tank to be protected by water loading shall be 
started as soon as flood waters reach a dangerous flood stage. The rate 
of filling shall be at least equal to the rate of rise of the 
floodwaters (or the established average potential rate of rise).
    (q) Sufficient fuel to operate the water pumps shall be available at 
all times to insure adequate power to fill all tankage with water.
    (r) All valves on connecting pipelines shall be closed and locked in 
closed position when water loading has been completed.
    (s) Where structural guides are provided for the protection of 
floating tanks, all rigid connections between tanks and pipelines shall 
be disconnected and blanked off or blinded before the floodwaters reach 
the bottom of the tank, unless control valves and their connections to 
the tank are of a type designed to prevent breakage between the valve 
and the tank shell.
    (t) All valves attached to tanks other than those used in connection 
with water loading operations shall be closed and locked.
    (u) If a tank is equipped with a swing line, the swing pipe shall be 
raised to and secured at its highest position.
    (v) Inspections. The Assistant Secretary or his designated 
representative shall make periodic inspections of all plants where the 
storage of flammable or combustible liquids is such as to require 
compliance with the foregoing requirements, in order to assure the 
following:
    (1) That all flammable or combustible liquid storage tanks are in 
compliance with these requirements and so maintained.
    (2) That detailed printed instructions of what to do in flood 
emergencies are properly posted.
    (3) That station operators and other employees depended upon to 
carry out such instructions are thoroughly informed as to the location 
and operation of such valves and other equipment necessary to effect 
these requirements.
    (vii) Earthquake areas. In areas subject to earthquakes, the tank 
supports and connections shall be designed to resist damage as a result 
of such shocks.
    (6) Sources of ignition. In locations where flammable vapors may be 
present, precautions shall be taken to prevent ignition by eliminating 
or controlling sources of ignition. Sources of ignition may include open 
flames, lightning, smoking, cutting and welding, hot surfaces, 
frictional heat, sparks (static, electrical, and mechanical), 
spontaneous ignition, chemical and physical-chemical reactions, and 
radiant heat.
    (7) Testing--(i) General. All tanks, whether shop built or field 
erected, shall be strength tested before they are placed in service in 
accordance with the applicable paragraphs of the code under which they 
were built. The American Society of Mechanical Engineers (ASME) code 
stamp, American Petroleum Institute (API) monogram, or the label of the 
Underwriters' Laboratories, Inc., on a tank shall be evidence of 
compliance with this strength test. Tanks not marked in accordance with 
the above codes shall be strength tested before they are placed in 
service in accordance with good engineering principles and reference 
shall be made to the sections on testing in the codes listed in 
subparagraphs (1) (iii)(a), (iv)(b), or (v)(b) of this paragraph.
    (ii) Strength. When the vertical length of the fill and vent pipes 
is such that when filled with liquid the static head imposed upon the 
bottom of the tank exceeds 10 pounds per square inch, the tank and 
related piping shall be tested hydrostatically to a pressure equal to 
the static head thus imposed.
    (iii) Tightness. In addition to the strength test called for in 
subdivisions (i) and (ii) of this subparagraph, all tanks and 
connections shall be tested for tightness. Except for underground tanks, 
this tightness test shall be made at operating pressure with air, inert 
gas, or water prior to placing the tank

[[Page 250]]

in service. In the case of field-erected tanks the strength test may be 
considered to be the test for tank tightness. Underground tanks and 
piping, before being covered, enclosed, or placed in use, shall be 
tested for tightness hydrostatically, or with air pressure at not less 
than 3 pounds per square inch and not more than 5 pounds per square 
inch.
    (iv) Repairs. All leaks or deformations shall be corrected in an 
acceptable manner before the tank is placed in service. Mechanical 
caulking is not permitted for correcting leaks in welded tanks except 
pinhole leaks in the roof.
    (v) Derated operations. Tanks to be operated at pressures below 
their design pressure may be tested by the applicable provisions of 
subdivision (i) or (ii) of this subparagraph, based upon the pressure 
developed under full emergency venting of the tank.
    (c) Piping, valves, and fittings--(1) General--(i) Design. The 
design (including selection of materials) fabrication, assembly, test, 
and inspection of piping systems containing flammable or combustible 
liquids shall be suitable for the expected working pressures and 
structural stresses. Conformity with the applicable provisions of 
Pressure Piping, ANSI B31 series and the provisions of this paragraph, 
shall be considered prima facie evidence of compliance with the 
foregoing provisions.
    (ii) Exceptions. This paragraph does not apply to any of the 
following:
    (a) Tubing or casing on any oil or gas wells and any piping 
connected directly thereto.
    (b) Motor vehicle, aircraft, boat, or portable or stationary 
engines.
    (c) Piping within the scope of any applicable boiler and pressures 
vessel code.
    (iii) Definitions. As used in this paragraph, piping systems consist 
of pipe, tubing, flanges, bolting, gaskets, valves, fittings, the 
pressure containing parts of other components such as expansion joints 
and strainers, and devices which serve such purposes as mixing, 
separating, snubbing, distributing, metering, or controlling flow.
    (2) Materials for piping, valves, and fittings--(i) Required 
materials. Materials for piping, valves, or fittings shall be steel, 
nodular iron, or malleable iron, except as provided in paragraph (c)(2) 
(ii), (iii) and (iv) of this section.
    (ii) Exceptions. Materials other than steel, nodular iron, or 
malleable iron may be used underground, or if required by the properties 
of the flammable or combustible liquid handled. Material other than 
steel, nodular iron, or malleable iron shall be designed to 
specifications embodying principles recognized as good engineering 
practices for the material used.
    (iii) Linings. Piping, valves, and fittings may have combustible or 
noncombustible linings.
    (iv) Low-melting materials. When low-melting point materials such as 
aluminum and brass or materials that soften on fire exposure such as 
plastics, or non-ductile materials such as cast iron, are necessary, 
special consideration shall be given to their behavior on fire exposure. 
If such materials are used in above ground piping systems or inside 
buildings, they shall be suitably protected against fire exposure or so 
located that any spill resulting from the failure of these materials 
could not unduly expose persons, important buildings or structures or 
can be readily controlled by remote valves.
    (3) Pipe joints. Joints shall be made liquid tight. Welded or 
screwed joints or approved connectors shall be used. Threaded joints and 
connections shall be made up tight with a suitable lubricant or piping 
compound. Pipe joints dependent upon the friction characteristics of 
combustible materials for mechanical continuity of piping shall not be 
used inside buildings. They may be used outside of buildings above or 
below ground. If used above ground, the piping shall either be secured 
to prevent disengagement at the fitting or the piping system shall be so 
designed that any spill resulting from such disengagement could not 
unduly expose persons, important buildings or structures, and could be 
readily controlled by remote valves.
    (4) Supports. Piping systems shall be substantially supported and 
protected against physical damage and excessive stresses arising from 
settlement, vibration, expansion, or contraction.
    (5) Protection against corrosion. All piping for flammable or 
combustible

[[Page 251]]

liquids, both aboveground and underground, where subject to external 
corrosion, shall be painted or otherwise protected.
    (6) Valves. Piping systems shall contain a sufficient number of 
valves to operate the system properly and to protect the plant. Piping 
systems in connection with pumps shall contain a sufficient number of 
valves to control properly the flow of liquid in normal operation and in 
the event of physical damage. Each connection to pipelines, by which 
equipments such as tankcars or tank vehicles discharge liquids by means 
of pumps into storage tanks, shall be provided with a check valve for 
automatic protection against backflow if the piping arrangement is such 
that backflow from the system is possible.
    (7) Testing. All piping before being covered, enclosed, or placed in 
use shall be hydrostatically tested to 150 percent of the maximum 
anticipated pressure of the system, or pneumatically tested to 110 
percent of the maximum anticipated pressure of the system, but not less 
than 5 pounds per square inch gage at the highest point of the system. 
This test shall be maintained for a sufficient time to complete visual 
inspection of all joints and connections, but for at least 10 minutes.
    (d) Container and portable tank storage--(1) Scope--(i) General. 
This paragraph shall apply only to the storage of flammable or 
combustible liquids in drums or other containers (including flammable 
aerosols) not exceeding 60 gallons individual capacity and those 
portable tanks not exceeding 660 gallons individual capacity.
    (ii) Exceptions. This paragraph shall not apply to the following:
    (a) Storage of containers in bulk plants, service stations, 
refineries, chemical plants, and distilleries;
    (b) Class I or Class II liquids in the fuel tanks of a motor 
vehicle, aircraft, boat, or portable or stationary engine;
    (c) Flammable or combustible paints, oils, varnishes, and similar 
mixtures used for painting or maintenance when not kept for a period in 
excess of 30 days;
    (d) Beverages when packaged in individual containers not exceeding 1 
gallon in size.
    (2) Design, construction, and capacity of containers--(i) General. 
Only approved containers and portable tanks shall be used. Metal 
containers and portable tanks meeting the requirements of and containing 
products authorized by chapter I, title 49 of the Code of Federal 
Regulations (regulations issued by the Hazardous Materials Regulations 
Board, Department of Transportation), shall be deemed to be acceptable.
    (ii) Emergency venting. Each portable tank shall be provided with 
one or more devices installed in the top with sufficient emergency 
venting capacity to limit internal pressure under fire exposure 
conditions to 10 p.s.i.g., or 30 percent of the bursting pressure of the 
tank, whichever is greater. The total venting capacity shall be not less 
than that specified in paragraphs (b)(2)(v) (c) or (e) of this section. 
At least one pressure-activated vent having a minimum capacity of 6,000 
cubic feet of free air (14.7 p.s.i.a. and 60 F.) shall be used. It 
shall be set to open at not less than 5 p.s.i.g. If fusible vents are 
used, they shall be actuated by elements that operate at a temperature 
not exceeding 300 F.
    (iii) Size. Flammable and combustible liquid containers shall be in 
accordance with Table H-12, except that glass or plastic containers of 
no more than 1-gallon capacity may be used for a Class IA or IB 
flammable liquid if:
    (a)(1) Such liquid either would be rendered unfit for its intended 
use by contact with metal or would excessively corrode a metal container 
so as to create a leakage hazard; and
    (2) The user's process either would require more than 1 pint of a 
Class IA liquid or more than 1 quart of a Class IB liquid of a single 
assay lot to be used at one time, or would require the maintenance of an 
analytical standard liquid of a quality which is not met by the 
specified standards of liquids available, and the quantity of the 
analytical standard liquid required to be used in any one control 
process exceeds one-sixteenth the capacity of the container allowed 
under Table H-12 for the class of liquid; or
    (b) The containers are intended for direct export outside the United 
States.

[[Page 252]]



                       Table H-12--Maximum Allowable Size of Containers and Portable Tanks
----------------------------------------------------------------------------------------------------------------
                                                               Flammable liquids            Combustible liquids
                   Container type                    -----------------------------------------------------------
                                                       Class IA    Class IB    Class IC    Class II    Class III
----------------------------------------------------------------------------------------------------------------
Glass or approved plastic...........................        1 pt        1 qt       1 gal       1 gal      1 gal.
Metal (other than DOT drums)........................       1 gal       5 gal       5 gal       5 gal      5 gal.
Safety cans.........................................       2 gal       5 gal       5 gal       5 gal      5 gal.
Metal drums (DOT specifications)....................      60 gal      60 gal      60 gal      60 gal     60 gal.
Approved portable tanks.............................     660 gal     660 gal     660 gal     660 gal    660 gal.
----------------------------------------------------------------------------------------------------------------
Note: Container exemptions: (a) Medicines, beverages, foodstuffs, cosmetics, and other common consumer items,
  when packaged according to commonly accepted practices, shall be exempt from the requirements of Sec.
  1910.106(d)(2) (i) and (ii).

    (3) Design, construction, and capacity of storage cabinets--(i) 
Maximum capacity. Not more than 60 gallons of Class I or Class II 
liquids, nor more than 120 gallons of Class III liquids may be stored in 
a storage cabinet.
    (ii) Fire resistance. Storage cabinets shall be designed and 
constructed to limit the internal temperature to not more than 325 F. 
when subjected to a 10-minute fire test using the standard time-
temperature curve as set forth in Standard Methods of Fire Tests of 
Building Construction and Materials, NFPA 251-1969, which is 
incorporated by reference as specified in Sec. 1910.6. All joints and seams 
shall remain tight and the door shall remain securely closed during the 
fire test. Cabinets shall be labeled in conspicuous lettering, 
``Flammable--Keep Fire Away.''
    (a) Metal cabinets constructed in the following manner shall be 
deemed to be in compliance. The bottom, top, door, and sides of cabinet 
shall be at least No. 18 gage sheet iron and double walled with 1\1/2\-
inch air space. Joints shall be riveted, welded or made tight by some 
equally effective means. The door shall be provided with a three-point 
lock, and the door sill shall be raised at least 2 inches above the 
bottom of the cabinet.
    (b) Wooden cabinets constructed in the following manner shall be 
deemed in compliance. The bottom, sides, and top shall be constructed of 
an approved grade of plywood at least 1 inch in thickness, which shall 
not break down or delaminate under fire conditions. All joints shall be 
rabbetted and shall be fastened in two directions with flathead 
woodscrews. When more than one door is used, there shall be a rabbetted 
overlap of not less than 1 inch. Hinges shall be mounted in such a 
manner as not to lose their holding capacity due to loosening or burning 
out of the screws when subjected to the fire test.
    (4) Design and construction of inside storage rooms--(i) 
Construction. Inside storage rooms shall be constructed to meet the 
required fire-resistive rating for their use. Such construction shall 
comply with the test specifications set forth in Standard Methods of 
Fire Tests of Building Construction and Materials, NFPA 251-1969. Where 
an automatic sprinkler system is provided, the system shall be designed 
and installed in an acceptable manner. Openings to other rooms or 
buildings shall be provided with noncombustible liquid-tight raised 
sills or ramps at least 4 inches in height, or the floor in the storage 
area shall be at least 4 inches below the surrounding floor. Openings 
shall be provided with approved self-closing fire doors. The room shall 
be liquid-tight where the walls join the floor. A permissible alternate 
to the sill or ramp is an open-grated trench inside of the room which 
drains to a safe location. Where other portions of the building or other 
properties are exposed, windows shall be protected as set forth in the 
Standard for Fire Doors and Windows, NFPA No. 80-1968, which is 
incorporated by reference as specified in Sec. 1910.6, for Class E or F 
openings. Wood at least 1 inch nominal thickness may be used for 
shelving, racks, dunnage, scuffboards, floor overlay, and similar 
installations.
    (ii) Rating and capacity. Storage in inside storage rooms shall 
comply with Table H-13.

[[Page 253]]



                                       Table H-13--Storage in Inside Rooms
----------------------------------------------------------------------------------------------------------------
                                                                                                         Total
                                                                                                       allowable
                                                                                                      quantities
       Fire protection \1\ provided               Fire resistance                Maximum size         (gals./sq.
                                                                                                       ft./floor
                                                                                                         area)
----------------------------------------------------------------------------------------------------------------
Yes......................................  2 hours.....................  500 sq. ft.................         10
No.......................................  2 hours.....................  500 sq. ft.................          5
Yes......................................  1 hour......................  150 sq. ft.................          4
No.......................................  1 hour......................  150 sq. ft.................          2
----------------------------------------------------------------------------------------------------------------
\1\ Fire protection system shall be sprinkler, water spray, carbon dioxide, or other system.

    (iii) Wiring. Electrical wiring and equipment located in inside 
storage rooms used for Class I liquids shall be approved under Subpart S 
of this part for Class I, Division 2 Hazardous Locations; for Class II 
and Class III liquids, shall be approved for general use.
    (iv) Ventilation. Every inside storage room shall be provided with 
either a gravity or a mechanical exhaust ventilation system. Such system 
shall be designed to provide for a complete change of air within the 
room at least six times per hour. If a mechanical exhaust system is 
used, it shall be controlled by a switch located outside of the door. 
The ventilating equipment and any lighting fixtures shall be operated by 
the same switch. A pilot light shall be installed adjacent to the switch 
if Class I flammable liquids are dispensed within the room. Where 
gravity ventilation is provided, the fresh air intake, as well as the 
exhaust outlet from the room, shall be on the exterior of the building 
in which the room is located.
    (v) Storage in inside storage rooms. In every inside storage room 
there shall be maintained one clear aisle at least 3 feet wide. 
Containers over 30 gallons capacity shall not be stacked one upon the 
other. Dispensing shall be by approved pump or self-closing faucet only.
    (5) Storage inside building--(i) Egress. Flammable or combustible 
liquids, including stock for sale, shall not be stored so as to limit 
use of exits, stairways, or areas normally used for the safe egress of 
people.
    (ii) Containers. The storage of flammable or combustible liquids in 
containers or portable tanks shall comply with subdivisions (iii) 
through (v) of this subparagraph.
    (iii) Office occupancies. Storage shall be prohibited except that 
which is required for maintenance and operation of building and 
operation of equipment. Such storage shall be kept in closed metal 
containers stored in a storage cabinet or in safety cans or in an inside 
storage room not having a door that opens into that portion of the 
building used by the public.
    (iv) Mercantile occupancies and other retail stores.
    (a)-(d) [Reserved]
    (e) Leaking containers shall be removed to a storage room or taken 
to a safe location outside the building and the contents transferred to 
an undamaged container.
    (v) General purpose public warehouses. Storage shall be in 
accordance with Table H-14 or H-15 and in buildings or in portions of 
such buildings cut off by standard firewalls. Material creating no fire 
exposure hazard to the flammable or combustible liquids may be stored in 
the same area.

                                      Table H-14--Indoor Container Storage
----------------------------------------------------------------------------------------------------------------
                                                                                                Gallons
                                                                                     ---------------------------
                                                                                        Protected    Unprotected
                 Class liquid                               Storage level                storage       storage
                                                                                       maximum per   maximum per
                                                                                          pile          pile
----------------------------------------------------------------------------------------------------------------
A.............................................  Ground and upper floors.............         2,750           660
                                                                                              (50)          (12)
                                                Basement............................           Not           Not
                                                                                         permitted     permitted
B.............................................  Ground and upper floors.............         5,500         1,375
                                                                                             (100)          (25)
                                                Basement............................           Not           Not
                                                                                         permitted     permitted
C.............................................  Ground and upper floors.............        16,500         4,125
                                                                                             (300)          (75)
                                                Basement............................           Not           Not
                                                                                         permitted     permitted
II............................................  Ground and upper floors.............        16,500         4,125
                                                                                             (300)          (75)
                                                Basement............................         5,500           Not
                                                                                                       permitted

[[Page 254]]


                                                                                             (100)
III...........................................  Ground and upper floors.............        55,000        13,750
                                                                                           (1,000)         (250)
                                                Basement............................         8,250           Not
                                                                                                       permitted
                                                                                             (450)
----------------------------------------------------------------------------------------------------------------
Note 1: When 2 or more classes of materials are stored in a single pile, the maximum gallonage permitted in that
  pile shall be the smallest of the 2 or more separate maximum gallonages.
Note 2: Aisles shall be provided so that no container is more than 12 ft. from an aisle. Main aisles shall be at
  least 3 ft. wide and side aisles at least 4 ft. wide.
Note 3: Each pile shall be separated from each other by at least 4 ft.
(Numbers in parentheses indicate corresponding number of 55-gal. drums.)


                                    Table H-15--Indoor Portable Tank Storage
----------------------------------------------------------------------------------------------------------------
                                                                                                Gallons
                                                                                     ---------------------------
                                                                                        Protected    Unprotected
                 Class liquid                               Storage level                storage       storage
                                                                                       maximum per   maximum per
                                                                                          pile          pile
----------------------------------------------------------------------------------------------------------------
IA............................................  Ground and upper floors.............           Not           Not
                                                                                         permitted     permitted
                                                Basement............................           Not           Not
                                                                                         permitted     permitted
IB............................................  Ground and upper floors.............        20,000         2,000
                                                Basement............................           Not           Not
                                                                                         permitted     permitted
IC............................................  Ground and upper floors.............        40,000         5,500
                                                Basement............................           Not           Not
                                                                                         permitted     permitted
II............................................  Ground and upper floors.............        40,000         5,500
                                                Basement............................        20,000           Not
                                                                                                       permitted
III...........................................  Ground and upper floors.............        60,000        22,000
                                                Basement............................        20,000           Not
                                                                                                       permitted
----------------------------------------------------------------------------------------------------------------
Note 1: When 1 or more classes of materials are stored in a single pile, the maximum gallonage permitted in that
  pile shall be the smallest of the 2 or more separate maximum gallonages.
Note 2: Aisles shall be provided so that no portable tank is more than 12 ft. from an aisle. Main aisles shall
  be at least 8 ft. wide and side aisles at least 4 ft. wide.
Note 3: Each pile shall be separated from each other by at least 4 ft.

    (vi) Flammable and combustible liquid warehouses or storage 
buildings. (a) If the storage building is located 50 feet or less from a 
building or line of adjoining property that may be built upon, the 
exposing wall shall be a blank wall having a fire-resistance rating of 
at least 2 hours.
    (b) The total quantity of liquids within a building shall not be 
restricted, but the arrangement of storage shall comply with Table H-14 
or H-15.
    (c) Containers in piles shall be separated by pallets or dunnage 
where necessary to provide stability and to prevent excessive stress on 
container walls.
    (d) Portable tanks stored over one tier high shall be designed to 
nest securely, without dunnage, and adequate materials handing equipment 
shall be available to handle tanks safely at the upper tier level.
    (e) No pile shall be closer than 3 feet to the nearest beam, chord, 
girder, or other obstruction, and shall be 3 feet below sprinkler 
deflectors or discharge orifices of water spray, or other overhead fire 
protection systems.
    (f) Aisles of at least 3 feet wide shall be provided where necessary 
for reasons of access to doors, windows or standpipe connections.
    (6) Storage outside buildings--(i) General. Storage outside 
buildings shall be in accordance with Table H-16 or H-17, and 
subdivisions (ii) and (iv) of this subparagraph.

[[Page 255]]



                                      Table H-16--Outdoor Container Storage
----------------------------------------------------------------------------------------------------------------
                                                                                        4--Distance
                                                                           3--Distance  to property  5--Distance
                          1--Class                             2--Maximum    between     line that    to street,
                                                                per pile      piles        can be       alley,
                                                                                         built upon   public way
----------------------------------------------------------------------------------------------------------------
                                                                gallons         feet         feet         feet
                                                             ---------------------------------------------------
IA..........................................................        1,100            5           20           10
IB..........................................................        2,200            5           20           10
IC..........................................................        4,400            5           20           10
II..........................................................        8,800            5           10            5
III.........................................................       22,000            5           10            5
----------------------------------------------------------------------------------------------------------------
Note 1: When 2 or more classes of materials are stored in a single pile, the maximum gallonage in that pile
  shall be the smallest of the 2 or more separate gallonages.
Note 2: Within 200 ft. of each container, there shall be a 12-ft. wide access way to permit approach of fire
  control apparatus.
Note 3: The distances listed apply to properties that have protection for exposures as defined. If there are
  exposures, and such protection for exposures does not exist, the distances in column 4 shall be doubled.
Note 4: When total quantity stored does not exceed 50 percent of maximum per pile, the distances in columns 4
  and 5 may be reduced 50 percent, but not less than 3 ft.

    (ii) Maximum storage. A maximum of 1,100 gallons of flammable or 
combustible liquids may be located adjacent to buildings located on the 
same premises and under the same management provided the provisions of 
subdivisions (a) and (b) of this subdivision are complied with.
    (a) [Reserved]
    (b) Where quantity stored exceeds 1,100 gallons, or provisions of 
subdivision (a) of this subdivision cannot be met, a minimum distance of 
10 feet between buildings and nearest container of flammable or 
combustible liquid shall be maintained.
    (iii) Spill containment. The storage area shall be graded in a 
manner to divert possible spills away from buildings or other exposures 
or shall be surrounded by a curb at least 6 inches high. When curbs are 
used, provisions shall be made for draining of accumulations of ground 
or rain water or spills of flammable or combustible liquids. Drains 
shall terminate at a safe location and shall be accessible to operation 
under fire conditions.
    (iv) Security. The storage area shall be protected against tampering 
or trespassers where necessary and shall be kept free of weeds, debris 
and other combustible material not necessary to the storage.
    (7) Fire control--(i) Extinguishers. Suitable fire control devices, 
such as small hose or portable fire extinguishers, shall be available at 
locations where flammable or combustible liquids are stored.

                                    Table H-17--Outdoor Portable Tank Storage
----------------------------------------------------------------------------------------------------------------
                                                                                        4--Distance
                                                                           3--Distance  to property  5--Distance
                          1--Class                             2--Maximum    between     line that    to street,
                                                                per pile      piles        can be       alley,
                                                                                         built upon   public way
----------------------------------------------------------------------------------------------------------------
                                                                 gallon         feet         feet         feet
                                                             ---------------------------------------------------
IA..........................................................        2,200            5           20           10
IB..........................................................        4,400            5           20           10
IC..........................................................        8,800            5           20           10
II..........................................................       17,600            5           10            5
III.........................................................       44,000            5           10            5
----------------------------------------------------------------------------------------------------------------
Note 1: When 2 or more classes of materials are stored in a single pile, the maximum gallonage in that pile
  shall be the the smallest of the 2 or more separate gallonages.
Note 2: Within 200 ft. of each portable tank, there shall be a 12-ft. wide access way to permit approach of fire
  control apparatus.
Note 3: The distances listed apply to properties that have protection for exposures as defined. If there are
  exposures, and such protection for exposures does not exist, the distances in column 4 shall be doubled.
Note 4: When total quantity stored does not exceed 50 percent of maximum per pile, the distances in columns 4
  and 5 may be reduced 50 percent, but not less than 3 ft.


[[Page 256]]

    (a) At least one portable fire extinguisher having a rating of not 
less than 12-B units shall be located outside of, but not more than 10 
feet from, the door opening into any room used for storage.
    (b) At least one portable fire extinguisher having a rating of not 
less than 12-B units must be located not less than 10 feet, nor more 
than 25 feet, from any Class I or Class II liquid storage area located 
outside of a storage room but inside a building.
    (ii) Sprinklers. When sprinklers are provided, they shall be 
installed in accordance with Sec. 1910.159.
    (iii) Open flames and smoking. Open flames and smoking shall not be 
permitted in flammable or combustible liquid storage areas.
    (iv) Water reactive materials. Materials which will react with water 
shall not be stored in the same room with flammable or combustible 
liquids.
    (e) Industrial plants--(1) Scope--(i) Application. This paragraph 
shall apply to those industrial plants where:
    (a) The use of flammable or combustible liquids is incidental to the 
principal business, or
    (b) Where flammable or combustible liquids are handled or used only 
in unit physical operations such as mixing, drying, evaporating, 
filtering, distillation, and similar operations which do not involve 
chemical reaction. This paragraph shall not apply to chemical plants, 
refineries or distilleries.
    (ii) Exceptions. Where portions of such plants involve chemical 
reactions such as oxidation, reduction, halogenation, hydrogenation, 
alkylation, polymerization, and other chemical processes, those portions 
of the plant shall be in accordance with paragraph (h) of this section.
    (2) Incidental storage or use of flammable and combustible liquids--
(i) Application. This subparagraph shall be applicable to those portions 
of an industrial plant where the use and handling of flammable or 
combustible liquids is only incidental to the principal business, such 
as automobile assembly, construction of electronic equipment, furniture 
manufacturing, or other similar activities.
    (ii) Containers. Flammable or combustible liquids shall be stored in 
tanks or closed containers.
    (a) Except as provided in subdivisions (b) and (c) of this 
subdivision, all storage shall comply with paragraph (d) (3) or (4) of 
this section.
    (b) The quantity of liquid that may be located outside of an inside 
storage room or storage cabinet in a building or in any one fire area of 
a building shall not exceed:
    (1) 25 gallons of Class IA liquids in containers
    (2) 120 gallons of Class IB, IC, II, or III liquids in containers
    (3) 660 gallons of Class IB, IC, II, or III liquids in a single 
portable tank.
    (c) Where large quantities of flammable or combustible liquids are 
necessary, storage may be in tanks which shall comply with the 
applicable requirements of paragraph (b) of this section.
    (iii) Separation and protection. Areas in which flammable or 
combustible liquids are transferred from one tank or container to 
another container shall be separated from other operations in the 
building by adequate distance or by construction having adequate fire 
resistance. Drainage or other means shall be provided to control spills. 
Adequate natural or mechanical ventilation shall be provided.
    (iv) Handling liquids at point of final use. (a) Flammable liquids 
shall be kept in covered containers when not actually in use.
    (b) Where flammable or combustible liquids are used or handled, 
except in closed containers, means shall be provided to dispose promptly 
and safely of leakage or spills.
    (c) Class I liquids may be used only where there are no open flames 
or other sources of ignition within the possible path of vapor travel.
    (d) Flammable or combustible liquids shall be drawn from or 
transferred into vessels, containers, or portable tanks within a 
building only through a closed piping system, from safety cans, by means 
of a device drawing through the top, or from a container or portable 
tanks by gravity through an approved self-closing valve. Transferring by 
means of air pressure on the container or portable tanks shall be 
prohibited.

[[Page 257]]

    (3) Unit physical operations--(i) Application. This subparagraph 
shall be applicable in those portions of industrial plants where 
flammable or combustible liquids are handled or used in unit physical 
operations such as mixing, drying, evaporating, filtering, distillation, 
and similar operations which do not involve chemical change. Examples 
are plants compounding cosmetics, pharmaceuticals, solvents, cleaning 
fluids, insecticides, and similar types of activities.
    (ii) Location. Industrial plants shall be located so that each 
building or unit of equipment is accessible from at least one side for 
firefighting and fire control purposes. Buildings shall be located with 
respect to lines of adjoining property which may be built upon as set 
forth in paragraph (h)(2) (i) and (ii) of this section except that the 
blank wall referred to in paragraph (h)(2)(ii) of this section shall 
have a fire resistance rating of at least 2 hours.
    (iii) Chemical processes. Areas where unstable liquids are handled 
or small scale unit chemical processes are carried on shall be separated 
from the remainder of the plant by a fire wall of 2-hour minimum fire 
resistance rating.
    (iv) Drainage. (a) Emergency drainage systems shall be provided to 
direct flammable or combustible liquid leakage and fire protection water 
to a safe location. This may require curbs, scuppers, or special 
drainage systems to control the spread of fire; see paragraph 
(b)(2)(vii)(b) of this section.
    (b) Emergency drainage systems, if connected to public sewers or 
discharged into public waterways, shall be equipped with traps or 
separator.
    (v) Ventilation. (a) Areas as defined in subdivision (i) of this 
subparagraph using Class I liquids shall be ventilated at a rate of not 
less than 1 cubic foot per minute per square foot of solid floor area. 
This shall be accomplished by natural or mechanical ventilation with 
discharge or exhaust to a safe location outside of the building. 
Provision shall be made for introduction of makeup air in such a manner 
as not to short circuit the ventilation. Ventilation shall be arranged 
to include all floor areas or pits where flammable vapors may collect.
    (b) Equipment used in a building and the ventilation of the building 
shall be designed so as to limit flammable vapor-air mixtures under 
normal operating conditions to the interior of equipment, and to not 
more than 5 feet from equipment which exposes Class I liquids to the 
air. Examples of such equipment are dispensing stations, open 
centrifuges, plate and frame filters, open vacuum filters, and surfaces 
of open equipment.
    (vi) Storage and handling. The storage, transfer, and handling of 
liquid shall comply with paragraph (h)(4) of this section.
    (4) Tank vehicle and tank car loading and unloading. (i) Tank 
vehicle and tank car loading or unloading facilities shall be separated 
from aboveground tanks, warehouses, other plant buildings or nearest 
line of adjoining property which may be built upon by a distance of 25 
feet for Class I liquids and 15 feet for Class II and Class III liquids 
measured from the nearest position of any fill stem. Buildings for pumps 
or shelters for personnel may be a part of the facility. Operations of 
the facility shall comply with the appropriate portions of paragraph 
(f)(3) of this section.
    (ii) [Reserved]
    (5) Fire control--(i) Portable and special equipment. Portable fire 
extinguishment and control equipment shall be provided in such 
quantities and types as are needed for the special hazards of operation 
and storage.
    (ii) Water supply. Water shall be available in volume and at 
adequate pressure to supply water hose streams, foam-producing 
equipment, automatic sprinklers, or water spray systems as the need is 
indicated by the special hazards of operation, dispensing and storage.
    (iii) Special extinguishers. Special extinguishing equipment such as 
that utilizing foam, inert gas, or dry chemical shall be provided as the 
need is indicated by the special hazards of operation dispensing and 
storage.
    (iv) Special hazards. Where the need is indicated by special hazards 
of operation, flammable or combustible liquid processing equipment, 
major piping, and supporting steel shall be protected by approved water 
spray systems, deluge systems, approved fire-resistant

[[Page 258]]

coatings, insulation, or any combination of these.
    (v) Maintenance. All plant fire protection facilities shall be 
adequately maintained and periodically inspected and tested to make sure 
they are always in satisfactory operating condition, and they will serve 
their purpose in time of emergency.
    (6) Sources of ignition--(i) General. Adequate precautions shall be 
taken to prevent the ignition of flammable vapors. Sources of ignition 
include but are not limited to open flames; lightning; smoking; cutting 
and welding; hot surfaces; frictional heat; static, electrical, and 
mechanical sparks; spontaneous ignition, including heat-producing 
chemical reactions; and radiant heat.
    (ii) Grounding. Class I liquids shall not be dispensed into 
containers unless the nozzle and container are electrically 
interconnected. Where the metallic floorplate on which the container 
stands while filling is electrically connected to the fill stem or where 
the fill stem is bonded to the container during filling operations by 
means of a bond wire, the provisions of this section shall be deemed to 
have been complied with.
    (7) Electrical--(i) Equipment. (a) All electrical wiring and 
equipment shall be installed according to the requirements of Subpart S 
of this part.
    (b) Locations where flammable vapor-air mixtures may exist under 
normal operations shall be classified Class I, Division 1 according to 
the requirements of Subpart S of this part. For those pieces of 
equipment installed in accordance with subparagraph (3)(v)(b) of this 
paragraph, the Division 1 area shall extend 5 feet in all directions 
from all points of vapor liberation. All areas within pits shall be 
classified Division 1 if any part of the pit is within a Division 1 or 2 
classified area, unless the pit is provided with mechanical ventilation.
    (c) Locations where flammable vapor-air mixtures may exist under 
abnormal conditions and for a distance beyond Division 1 locations shall 
be classified Division 2 according to the requirements of Subpart S of 
this part. These locations include an area within 20 feet horizontally, 
3 feet vertically beyond a Division 1 area, and up to 3 feet above floor 
or grade level within 25 feet, if indoors, or 10 feet if outdoors, from 
any pump, bleeder, withdrawal fitting, meter, or similar device handling 
Class I liquids. Pits provided with adequate mechanical ventilation 
within a Division 1 or 2 area shall be classified Division 2. If Class 
II or Class III liquids only are handled, then ordinary electrical 
equipment is satisfactory though care shall be used in locating 
electrical apparatus to prevent hot metal from falling into open 
equipment.
    (d) Where the provisions of subdivisions (a), (b), and (c), of this 
subdivision require the installation of electrical equipment suitable 
for Class I, Division 1 or Division 2 locations, ordinary electrical 
equipment including switchgear may be used if installed in a room or 
enclosure which is maintained under positive pressure with respect to 
the hazardous area. Ventilation makeup air shall be uncontaminated by 
flammable vapors.
    (8) Repairs to equipment. Hot work, such as welding or cutting 
operations, use of spark-producing power tools, and chipping operations 
shall be permitted only under supervision of an individual in 
responsible charge. The individual in responsible charge shall make an 
inspection of the area to be sure that it is safe for the work to be 
done and that safe procedures will be followed for the work specified.
    (9) Housekeeping--(i) General. Maintenance and operating practices 
shall be in accordance with established procedures which will tend to 
control leakage and prevent the accidental escape of flammable or 
combustible liquids. Spills shall be cleaned up promptly.
    (ii) Access. Adequate aisles shall be maintained for unobstructed 
movement of personnel and so that fire protection equipment can be 
brought to bear on any part of flammable or combustible liquid storage, 
use, or any unit physical operation.
    (iii) Waste and residue. Combustible waste material and residues in 
a building or unit operating area shall be kept to a minimum, stored in 
covered metal receptacles and disposed of daily.
    (iv) Clear zone. Ground area around buildings and unit operating 
areas shall be kept free of weeds, trash, or

[[Page 259]]

other unnecessary combustible materials.
    (f) Bulk plants--(1) Storage--(i) Class I liquids. Class I liquids 
shall be stored in closed containers, or in storage tanks above ground 
outside of buildings, or underground in accordance with paragraph (b) of 
this section.
    (ii) Class II and III liquids. Class II and Class III liquids shall 
be stored in containers, or in tanks within buildings or above ground 
outside of buildings, or underground in accordance with paragraph (b) of 
this section.
    (iii) Piling containers. Containers of flammable or combustible 
liquids when piled one upon the other shall be separated by dunnage 
sufficient to provide stability and to prevent excessive stress on 
container walls. The height of the pile shall be consistent with the 
stability and strength of containers.
    (2) Buildings--(i) Exits. Rooms in which flammable or combustible 
liquids are stored or handled by pumps shall have exit facilities 
arranged to prevent occupants from being trapped in the event of fire.
    (ii) Heating. Rooms in which Class I liquids are stored or handled 
shall be heated only by means not constituting a source of ignition, 
such as steam or hot water. Rooms containing heating appliances 
involving sources of ignition shall be located and arranged to prevent 
entry of flammable vapors.
    (iii) Ventilation. (a) Ventilation shall be provided for all rooms, 
buildings, or enclosures in which Class I liquids are pumped or 
dispensed. Design of ventilation systems shall take into account the 
relatively high specific gravity of the vapors. Ventilation may be 
provided by adequate openings in outside walls at floor level 
unobstructed except by louvers or coarse screens. Where natural 
ventilation is inadequate, mechanical ventilation shall be provided.
    (b) Class I liquids shall not be stored or handled within a building 
having a basement or pit into which flammable vapors may travel, unless 
such area is provided with ventilation designed to prevent the 
accumulation of flammable vapors therein.
    (c) Containers of Class I liquids shall not be drawn from or filled 
within buildings unless provision is made to prevent the accumulation of 
flammable vapors in hazardous concentrations. Where mechanical 
ventilation is required, it shall be kept in operation while flammable 
liquids are being handled.
    (3) Loading and unloading facilities--(i) Separation. Tank vehicle 
and tank car loading or unloading facilities shall be separated from 
aboveground tanks, warehouses, other plant buildings or nearest line of 
adjoining property that may be built upon by a distance of 25 feet for 
Class I liquids and 15 feet for Class II and Class III liquids measured 
from the nearest position of any fill spout. Buildings for pumps or 
shelters for personnel may be a part of the facility.
    (ii) Class restriction. Equipment such as piping, pumps, and meters 
used for the transfer of Class I liquids between storage tanks and the 
fill stem of the loading rack shall not be used for the transfer of 
Class II or Class III liquids.
    (iii) Valves. Valves used for the final control for filling tank 
vehicles shall be of the self-closing type and manually held open except 
where automatic means are provided for shutting off the flow when the 
vehicle is full or after filling of a preset amount.
    (iv) Static protection. (a) Bonding facilities for protection 
against static sparks during the loading of tank vehicles through open 
domes shall be provided:
    (1) Where Class I liquids are loaded, or
    (2) Where Class II or Class III liquids are loaded into vehicles 
which may contain vapors from previous cargoes of Class I liquids.
    (b) Protection as required in (a) of this subdivision (iv) shall 
consist of a metallic bond wire permanently electrically connected to 
the fill stem or to some part of the rack structure in electrical 
contact with the fill stem. The free end of such wire shall be provided 
with a clamp or equivalent device for convenient attachment to some 
metallic part in electrical contact with the cargo tank of the tank 
vehicle.
    (c) Such bonding connection shall be made fast to the vehicle or 
tank before dome covers are raised and shall remain in place until 
filling is completed and all dome covers have been closed and secured.

[[Page 260]]

    (d) Bonding as specified in (a), (b), and (c) of this subdivision is 
not required:
    (1) Where vehicles are loaded exclusively with products not having a 
static accumulating tendency, such as asphalt, most crude oils, residual 
oils, and water soluble liquids;
    (2) Where no Class I liquids are handled at the loading facility and 
the tank vehicles loaded are used exclusively for Class II and Class III 
liquids; and
    (3) Where vehicles are loaded or unloaded through closed bottom or 
top connections.
    (e) Filling through open domes into the tanks of tank vehicles or 
tank cars, that contain vapor-air mixtures within the flammable range or 
where the liquid being filled can form such a mixture, shall be by means 
of a downspout which extends near the bottom of the tank. This 
precaution is not required when loading liquids which are 
nonaccumulators of static charges.
    (v) Stray currents. Tank car loading facilities where Class I 
liquids are loaded through open domes shall be protected against stray 
currents by bonding the pipe to at least one rail and to the rack 
structure if of metal. Multiple lines entering the rack area shall be 
electrically bonded together. In addition, in areas where excessive 
stray currents are known to exist, all pipe entering the rack area shall 
be provided with insulating sections to electrically isolate the rack 
piping from the pipelines. No bonding between the tank car and the rack 
or piping is required during either loading or unloading of Class II or 
III liquids.
    (vi) Container filling facilities. Class I liquids shall not be 
dispensed into containers unless the nozzle and container are 
electrically interconnected. Where the metallic floorplate on which the 
container stands while filling is electrically connected to the fill 
stem or where the fill stem is bonded to the container during filling 
operations by means of a bond wire, the provisions of this section shall 
be deemed to have been complied with.
    (4) Wharves--(i) Definition, application. The term wharf shall mean 
any wharf, pier, bulkhead, or other structure over or contiguous to 
navigable water used in conjunction with a bulk plant, the primary 
function of which is the transfer of flammable or combustible liquid 
cargo in bulk between the bulk plant and any tank vessel, ship, barge, 
lighter boat, or other mobile floating craft; and this subparagraph 
shall apply to all such installations except Marine Service Stations as 
covered in paragraph (g) of this section.
    (ii)-(iii) [Reserved]
    (iv) Design and construction. Substructure and deck shall be 
substantially designed for the use intended. Deck may employ any 
material which will afford the desired combination of flexibility, 
resistance to shock, durability, strength, and fire resistance. Heavy 
timber construction is acceptable.
    (v) [Reserved]
    (vi) Pumps. Loading pumps capable of building up pressures in excess 
of the safe working pressure of cargo hose or loading arms shall be 
provided with bypasses, relief valves, or other arrangement to protect 
the loading facilities against excessive pressure. Relief devices shall 
be tested at not more than yearly intervals to determine that they 
function satisfactorily at the pressure at which they are set.
    (vii) Hoses and couplings. All pressure hoses and couplings shall be 
inspected at intervals appropriate to the service. The hose and 
couplings shall be tested with the hose extended and using the 
``inservice maximum operating pressures.'' Any hose showing material 
deteriorations, signs of leakage, or weakness in its carcass or at the 
couplings shall be withdrawn from service and repaired or discarded.
    (viii) Piping and fittings. Piping, valves, and fittings shall be in 
accordance with paragraph (c) of this section, with the following 
exceptions and additions:
    (a) Flexibility of piping shall be assured by appropriate layout and 
arrangement of piping supports so that motion of the wharf structure 
resulting from wave action, currents, tides, or the mooring of vessels 
will not subject the pipe to repeated strain beyond the elastic limit.
    (b) Pipe joints depending upon the friction characteristics of 
combustible materials or grooving of pipe ends for

[[Page 261]]

mechanical continuity of piping shall not be used.
    (c) Swivel joints may be used in piping to which hoses are 
connected, and for articulated swivel-joint transfer systems, provided 
that the design is such that the mechanical strength of the joint will 
not be impaired if the packing material should fail, as by exposure to 
fire.
    (d) Piping systems shall contain a sufficient number of valves to 
operate the system properly and to control the flow of liquid in normal 
operation and in the event of physical damage.
    (e) In addition to the requirements of subdivision (d) of this 
subdivision, each line conveying flammable liquids leading to a wharf 
shall be provided with a readily accessible block valve located on shore 
near the approach to the wharf and outside of any diked area. Where more 
than one line is involved, the valves shall be grouped in one location.
    (f) Means of easy access shall be provided for cargo line valves 
located below the wharf deck.
    (g) Pipelines on flammable or combustible liquids wharves shall be 
adequately bonded and grounded. If excessive stray currents are 
encountered, insulating joints shall be installed. Bonding and grounding 
connections on all pipelines shall be located on wharfside of hose-riser 
insulating flanges, if used, and shall be accessible for inspection.
    (h) Hose or articulated swivel-joint pipe connections used for cargo 
transfer shall be capable of accommodating the combined effects of 
change in draft and maximum tidal range, and mooring lines shall be kept 
adjusted to prevent the surge of the vessel from placing stress on the 
cargo transfer system.
    (i) Hose shall be supported so as to avoid kinking and damage from 
chafing.
    (ix) Fire protection. Suitable portable fire extinguishers with a 
rating of not less than 12-BC shall be located within 75 feet of those 
portions of the facility where fires are likely to occur, such as hose 
connections, pumps, and separator tanks.
    (a) Where piped water is available, ready-connected fire hose in 
size appropriate for the water supply shall be provided so that 
manifolds where connections are made and broken can be reached by at 
least one hose stream.
    (b) Material shall not be placed on wharves in such a manner as to 
obstruct access to firefighting equipment, or important pipeline control 
valves.
    (c) Where the wharf is accessible to vehicle traffic, an 
unobstructed roadway to the shore end of the wharf shall be maintained 
for access of firefighting apparatus.
    (x) Operations control. Loading or discharging shall not commence 
until the wharf superintendent and officer in charge of the tank vessel 
agree that the tank vessel is properly moored and all connections are 
properly made. Mechanical work shall not be performed on the wharf 
during cargo transfer, except under special authorization based on a 
review of the area involved, methods to be employed, and precautions 
necessary.
    (5) Electrical equipment--(i) Application. This subparagraph shall 
apply to areas where Class I liquids are stored or handled. For areas 
where Class II or Class III liquids only are stored or handled, the 
electrical equipment may be installed in accordance with the provisions 
of Subpart S of this part, for ordinary locations.
    (ii) Conformance. All electrical equipment and wiring shall be of a 
type specified by and shall be installed in accordance with Subpart S of 
this part.
    (iii) Classification. So far as it applies Table H-18 shall be used 
to delineate and classify hazardous areas for the purpose of 
installation of electrical equipment under normal circumstances. In 
Table H-18 a classified area shall not extend beyond an unpierced wall, 
roof, or other solid partition. The area classifications listed shall be 
based on the premise that the installation meets the applicable 
requirements of this section in all respects.
    (6) Sources of ignition. Class I liquids shall not be handled, 
drawn, or dispensed where flammable vapors may reach a source of 
ignition. Smoking shall be prohibited except in designated localities. 
``No Smoking'' signs shall be conspicuously posted where hazard from 
flammable liquid vapors is normally present.

[[Page 262]]

    (7) Drainage and waste disposal. Provision shall be made to prevent 
flammable or combustible liquids which may be spilled at loading or 
unloading points from entering public sewers and drainage systems, or 
natural waterways. Connection to such sewers, drains, or waterways by 
which flammable or combustible liquids might enter shall be provided 
with separator boxes or other approved means whereby such entry is 
precluded. Crankcase drainings and flammable or combustible liquids 
shall not be dumped into sewers, but shall be stored in tanks or tight 
drums outside of any building until removed from the premises.
    (8) Fire control. Suitable fire-control devices, such as small hose 
or portable fire extinguishers, shall be available to locations where 
fires are likely to occur. Additional fire-control equipment may be 
required where a tank of more than 50,000 gallons individual capacity 
contains Class I liquids and where an unusual exposure hazard exists 
from surrounding property. Such additional fire-control equipment shall 
be sufficient to extinguish a fire in the largest tank. The design and 
amount of such equipment shall be in accordance with approved 
engineering standards.
    (g) Service stations--(1) Storage and handling--(i) General 
provisions. (a) Liquids shall be stored in approved closed containers 
not exceeding 60 gallons capacity, in tanks located underground, in 
tanks in special enclosures as described in paragraph (g)(i) of this 
section, or in aboveground tanks as provided for in paragraphs 
(g)(4)(ii), (b), (c) and (d) of this section.
    (b) Aboveground tanks, located in an adjoining bulk plant, may be 
connected by piping to service station underground tanks if, in addition 
to valves at aboveground tanks, a valve is also installed within control 
of service station personnel.
    (c) Apparatus dispensing Class I liquids into the fuel tanks of 
motor vehicles of the public shall not be located at a bulk plant unless 
separated by a fence or similar barrier from the area in which bulk 
operations are conducted.
    (d) [Reserved]
    (e) The provisions of paragraph (g)(1)(i)(a) of this section shall 
not prohibit the dispensing of flammable liquids in the open from a tank 
vehicle to a motor vehicle. Such dispensing shall be permitted provided:
    (1) The tank vehicle complies with the requirements covered in the 
Standard on Tank Vehicles for Flammable Liquids, NFPA 385-1966.
    (2) The dispensing is done on premises not open to the public.
    (3) [Reserved]
    (4) The dispensing hose does not exceed 50 feet in length.
    (5) The dispensing nozzle is a listed automatic-closing type without 
a latchopen device.
    (f) Class I liquids shall not be stored or handled within a building 
having a basement or pit into which flammable vapors may travel, unless 
such area is provided with ventilation designed to prevent the 
accumulation of flammable vapors therein.
    (g) [Reserved]

      Table H-18--Electrical Equipment Hazardous Areas--Bulk Plants
------------------------------------------------------------------------
                                 Class I
           Location              Group D     Extent of classified area
                                division
------------------------------------------------------------------------
Tank vehicle and tank car:
 \1\
  Loading through open dome..           1  Within 3 feet of edge of
                                            dome, extending in all
                                            directions.
                                        2  Area between 3 feet and 5
                                            feet from edge of dome,
                                            extending in all directions.
  Loading through bottom                1  Within 3 feet of point of
   connections with                         venting to atmosphere
   atmospheric venting.                     extending in all directions.
                                        2  Area between 3 feet and 5
                                            feet from point of venting
                                            to atmosphere, extending in
                                            all directions. Also up to
                                            18 inches above grade within
                                            a horizontal radius of 10
                                            feet from point of loading
                                            connection.
  Loading through closed dome           1  Within 3 feet of open end of
   with atmospheric venting.            2   vent, extending in all
                                            directions.
                                           Area between 3 feet and 5
                                            feet from open end of vent,
                                            extending in all directions.
                                            Also within 3 feet of edge
                                            of dome, extending in all
                                            directions.

[[Page 263]]


  Loading through closed dome           2  Within 3 feet of point of
   with vapor recovery.                     connection of both fill and
                                            vapor lines, extending in
                                            all directions.
  Bottom loading with vapor             2  Within 3 feet of point of
   recovery or any bottom                   connections extending in all
   unloading.                               directions. Also up to 18
                                            inches above grade with in a
                                            horizontal radius of 10 feet
                                            from point of connection.
Drum and container filling:
  Outdoors, or indoors with             1  Within 3 feet of vent and
   adequate ventilation.                    fill opening, extending in
                                            all directions.
                                        2  Area between 3 feet and 5
                                            feet from vent or fill
                                            opening, extending in all
                                            directions. Also up to 18
                                            inches above floor or grade
                                            level within a horizontal
                                            radius of 10 feet from vent
                                            or fill opening.
  Outdoors, or indoors with             1  Within 3 feet of vent and
   adequate ventilation.                    fill opening, extending in
                                            all directions.
                                        2  Area between 3 feet and 5
                                            feet from vent or fill
                                            opening, extending in all
                                            directions. Also up to 18
                                            inches above floor or grade
                                            level within a horizontal
                                            radius of 10 feet from vent
                                            or fill opening.
Tank--Aboveground:
  Shell, ends, or roof and              2  Within 10 feet from shell,
   dike area.                               ends, or roof of tank, Area
                                            inside dikes to level of top
                                            of dike.
  Vent.......................           1  Within 5 feet of open end of
                                            vent, extending in all
                                            directions.
                                        2  Area between 5 feet and 10
                                            feet from open end of vent,
                                            extending in all directions.
  Floating roof..............           1  Area above the roof and
                                            within the shell.
Pits:
  Without mechanical                    1  Entire area within pit if any
   ventilation.                             part is within a Division 1
                                            or 2 classified area.
  With mechanical ventilation           2  Entire area within pit if any
                                            part is within a Division 1
                                            or 2 classified area.
  Containing valves, fittings           2  Entire pit.
   or piping, and not within
   a Division 1 or 2
   classified area.
Pumps, bleeders, withdrawal
 fittings, meters and similar
 devices:
  Indoors....................           2  Within 5 feet of any edge of
                                            such devices, extending in
                                            all directions. Also up to 3
                                            feet above floor or grade
                                            level within 25 feet
                                            horizontally from any edge
                                            of such devices.
  Outdoors...................           2  Within 3 feet of any edge of
                                            such devices, extending in
                                            all directions. Also up to
                                            18 inches above grade level
                                            within 10 feet horizontally
                                            from any edge of such
                                            devices.
  Storage and repair garage             1  All pits or spaces below
   for tank vehicles.                       floor level.
                                        2  Area up to 18 inches above
                                            floor or grade level for
                                            entire storage or repair
                                            garage.
  Drainage ditches,                     2  Area up to 18 inches above
   separators, impounding                   ditch, separator or basin.
   basins.                                  Also up to 18 inches above
                                            grade within 15 feet
                                            horizontally from any edge.
  Garages for other than tank      (\2\ )  If there is any opening to
   vehicles.                                these rooms within the
                                            extent of an outdoor
                                            classified area, the entire
                                            room shall be classified the
                                            same as the area
                                            classification at the point
                                            of the opening.
  Outdoor drum storage.......      (\2\ )
  Indoor warehousing where         (\2\ )  If there is any opening to
   there is no flammable                    these rooms within the
   liquid transfer.                         extent of an indoor
                                            classified are, the room
                                            shall be classified the same
                                            as if the wall, curb or
                                            partition did not exist.
  Office and rest rooms......      (\2\ )
------------------------------------------------------------------------
\1\ When classifying the extent of the area, consideration shall be
  given to the fact that tank cars or tank vehicles may be spotted at
  varying points. Therefore, the extremities of the loading or unloading
  positions shall be used.
\2\ Ordinary.

    (ii) Special enclosures. (a) When installation of tanks in 
accordance with paragraph (b)(3) of this section is impractical because 
of property or building limitations, tanks for flammable or combustible 
liquids may be installed in buildings if properly enclosed.
    (b) The enclosure shall be substantially liquid and vaportight 
without backfill. Sides, top, and bottom of the enclosure shall be of 
reinforced concrete at least 6 inches thick, with openings for 
inspection through the top only. Tank connections shall be so

[[Page 264]]

piped or closed that neither vapors nor liquid can escape into the 
enclosed space. Means shall be provided whereby portable equipment may 
be employed to discharge to the outside any liquid or vapors which might 
accumulate should leakage occur.
    (iii) Inside buildings. (a) Except where stored in tanks as provided 
in subdivision (ii) of this subparagraph, no Class I liquids shall be 
stored within any service station building except in closed containers 
of aggregate capacity not exceeding 60 gallons. One container not 
exceeding 60 gallons capacity equipped with an approved pump is 
permitted.
    (b) Class I liquids may be transferred from one container to another 
in lubrication or service rooms of a service station building provided 
the electrical installation complies with Table H-19 and provided that 
any heating equipment complies with subparagraph (6) of this paragraph.
    (c) Class II and Class III liquids may be stored and dispensed 
inside service station buildings from tanks of not more than 120 gallons 
capacity each.
    (iv) [Reserved]
    (v) Dispensing into portable containers. No delivery of any Class I 
liquids shall be made into portable containers unless the container is 
constructed of metal, has a tight closure with screwed or spring cover, 
and is fitted with a spout or so designed that the contents can be 
poured without spilling.
    (2) [Reserved]
    (3) Dispensing systems--(i) Location. Dispensing devices at 
automotive service stations shall be so located that all parts of the 
vehicle being served will be on the premises of the service station.
    (ii) Inside location. Approved dispensing units may be located 
inside of buildings. The dispensing area shall be separated from other 
areas in an approved manner. The dispensing unit and its piping shall be 
mounted either on a concrete island or protected against collision 
damage by suitable means and shall be located in a position where it 
cannot be struck by a vehicle descending a ramp or other slope out of 
control. The dispensing area shall be provided with an approved 
mechanical or gravity ventilation system. When dispensing units are 
located below grade, only approved mechanical ventilation shall be used 
and the entire dispensing area shall be protected by an approved 
automatic sprinkler system. Ventilating systems shall be electrically 
interlocked with gasoline dispensing units so that the dispensing units 
cannot be operated unless the ventilating fan motors are energized.
    (iii) Emergency power cutoff. A clearly identified and easily 
accessible switch(es) or a circuit breaker(s) shall be provided at a 
location remote from dispensing devices, including remote pumping 
systems, to shut off the power to all dispensing devices in the event of 
an emergency.
    (iv) Dispensing units. (a) Class I liquids shall be transferred from 
tanks by means of fixed pumps so designed and equipped as to allow 
control of the flow and to prevent leakage or accidental discharge.
    (b)(1) Only listed devices may be used for dispensing Class I 
liquids. No such device may be used if it shows evidence of having been 
dismantled.
    (2) Every dispensing device for Class I liquids installed after 
December 31, 1978, shall contain evidence of listing so placed that any 
attempt to dismantle the device will result in damage to such evidence, 
visible without disassembly or dismounting of the nozzle.
    (c) Class I liquids shall not be dispensed by pressure from drums, 
barrels, and similar containers. Approved pumps taking suction through 
the top of the container or approved self-closing faucets shall be used.
    (d) The dispensing units, except those attached to containers, shall 
be mounted either on a concrete island or protected against collision 
damage by suitable means.
    (v) Remote pumping systems.
    (a) This subdivision shall apply to systems for dispensing Class I 
liquids where such liquids are transferred from storage to individual or 
multiple dispensing units by pumps located elsewhere than at the 
dispensing units.
    (b) Pumps shall be designed or equipped so that no part of the 
system will be subjected to pressures above its allowable working 
pressure. Pumps installed above grade, outside of buildings, shall be 
located not less than 10

[[Page 265]]

feet from lines of adjoining property which may be built upon, and not 
less than 5 feet from any building opening. When an outside pump 
location is impractical, pumps may be installed inside of buildings, as 
provided for dispensers in subdivision (ii) of