Sec. 127.107  Electrical power systems.

    (a) The electrical power system must have a power source and a 
separate emergency power source, so that failure of one source does not 
affect the capability of the other source. The system must meet the 
National Electrical Code, NFPA 70.
    (b) The emergency power source must provide enough power for the 
operation of the--
    (1) Emergency shutdown system;
    (2) Communications equipment;
    (3) Firefighting equipment; and
    (4) Emergency lighting.
    (c) If an auxiliary generator is used as an emergency power source, 
it must meet Section 700-12 of NFPA 70.