Sec. 127.201  Sensing and alarm systems.

    (a) Fixed sensors must have audio and visual alarms in the control 
room and audio alarms nearby.
    (b) Fixed sensors that continuously monitor for LNG vapors must--
    (1) Be in each enclosed area where vapor or gas may accumulate; and
    (2) Meet Section 9-4 of NFPA 59A.

[[Page 32]]

    (c) Fixed sensors that continuously monitor for flame, heat, or 
products of combustion must--
    (1) Be in each enclosed or covered Class I, Division 1, hazardous 
location defined in Section 500-5(a) of NFPA 70 and each area in which 
flammable or combustible material is stored; and
    (2) Meet Section 9-4 of NFPA 59A.