[Code of Federal Regulations] [Title 33, Volume 2] [Revised as of July 1, 2003] From the U.S. Government Printing Office via GPO Access [CITE: 33CFR145.10] [Page 154-155] TITLE 33--NAVIGATION AND NAVIGABLE WATERS CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) PART 145--FIRE-FIGHTING EQUIPMENT--Table of Contents Sec. 145.10 Locations and number of fire extinguishers required. (a) Approved portable and semi-portable extinguishers shall be installed in accordance with Table 145.10(a). (b) Semi-portable extinguishers shall be located in the open so as to be readily seen. Table 145.10(a)--Portable and Semi-Portable Extinguishers ---------------------------------------------------------------------------------------------------------------- Space Classification Quantity and location ---------------------------------------------------------------------------------------------------------------- safety areas Communicating corridors.................. A-II........................ 1 in each main corridor not more than 150 feet apart. (May be located in stairways.) Radio room............................... C-II........................ 1 in vicinity of exit. accommodations Sleeping accommodations.................. A-II........................ 1 in each sleeping accommodation space. (Where occupied by more than 4 persons.) services spaces Galleys.................................. B-II or C-II................ 1 for each 2,500 square feet or fraction thereof for hazards involved. Storerooms............................... A-II........................ 1 for each 2,500 square feet or fraction thereof located in vicinity of exits, either inside or outside of spaces. machinery spaces Gas-fired boilers........................ B-II (CO2 or dry chemical).. 2 required. Gas-fired boilers........................ B-V......................... 1 required.\1\ [[Page 155]] Oil-fired boilers........................ B-II........................ 2 required. Oil-fired boilers........................ B-V......................... 2 required.\1\ Internal combustion or gas turbine B-II........................ 1 for each engine.\2\ engines. Electric motors or generators of open C-II........................ 1 for each 2 motors or generators.\3\ type. ---------------------------------------------------------------------------------------------------------------- \1\ Not required where a fixed carbon dioxide system is installed. \2\ When installation is on weather deck or open to atmosphere at all times 1 B-II for each three engines is allowable. \3\ Small electrical appliances, such as fans, etc., shall not be counted or used as basis for determining number of extinguishers required. [CGFR 56-4, 21 FR 903, Feb. 9, 1956]