Sec. 149.453  Fire pumps.

    (a) Each PPC must have at least two independently driven fire pumps 
that can deliver two streams of water at a continuous pitot tube 
pressure of at least 75 p.s.i. at each fire hose nozzle.
    (b) Each fire pump must have:
    (1) A relief valve on its discharge side that is set to relieve at 
25 p.s.i. in excess of the pressure necessary to meet the requirement in 
paragraph (a) of this section;
    (2) A pressure gauge on its discharge side; and
    (3) Its own water source.
    (c) Fire pumps may only be connected to the fire main system.