[Code of Federal Regulations] [Title 33, Volume 2] [Revised as of July 1, 2003] From the U.S. Government Printing Office via GPO Access [CITE: 33CFR149.479] [Page 209] TITLE 33--NAVIGATION AND NAVIGABLE WATERS CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED) PART 149--DESIGN, CONSTRUCTION, AND EQUIPMENT--Table of Contents Subpart D--Safety Equipment Sec. 149.479 International shore connection. (a) The fixed fire main system of a PPC must have: (1) At least two risers; (2) A cutoff valve and check valve for each riser; and (3) At least two international shore connections that meet the requirements in 46 CFR 162.034. (b) Each riser must be in an accessible location to vessels alongside the PPC, and two of the risers must be on opposite sides of the PPC. Other Fire Extinguishing Systems