                TITLE 33--NAVIGATION AND NAVIGABLE WATERS
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 154--FACILITIES TRANSFERRING OIL OR HAZARDOUS MATERIAL IN BULK--Table 
of Contents
 
                    Subpart C--Equipment Requirements
 
Sec. 154.570  Lighting.

    (a) Except as provided in paragraph (c) of this section, for 
operations between sunset and sunrise, a facility must have fixed 
lighting that adequately illuminates:
    (1) Each transfer connection point on the facility;
    (2) Each transfer connection point in use on any barge moored at the 
facility to or from which oil or hazardous material is being 
transferred;
    (3) Each transfer operations work area on the facility; and
    (4) Each transfer operation work area on any barge moored at the 
facility to or from which oil or hazardous material is being 
transferred.
    (b) Where the illumination is apparently inadequate, the COTP may 
require verification by instrument of the levels of illumination. On a 
horizontal plane 3 feet above the barge deck or walking surface, 
illumination must measure at least:
    (1) 5.0 foot candles at transfer connection points; and
    (2) 1.0 foot candle in transfer operations work areas.
    (c) For small or remote facilities, the COTP may authorize 
operations with an adequate level of illumination provided by the vessel 
or by portable means.
    (d) Lighting must be located or shielded so as not to mislead or 
otherwise interfere with navigation on the adjacent waterways.

[CGD 75-124, 45 FR 7172, Jan. 31, 1980, as amended by CGD 86-034, 55 FR 
36253, Sept. 4, 1990]