Sec. 154.822  Detonation arresters, flame arresters, and flame screens.

    (a) Each detonation arrester required by this part must:
    (1) Be capable of arresting a detonation from either side of the 
device; and
    (2) Be acceptable to the Commandant (G-MSO). A detonation arrester 
designed, built, and tested in accordance with appendix A of this part 
will be acceptable to the Commandant (G-MSO).
    (b) Each flame arrester required by this part must be acceptable to 
the Commandant (G-MSO). A flame arrester designed, built, and tested in 
accordance with appendix B of this part will be acceptable to the 
Commandant (G-MSO).
    (c) Each flame screen required by this part must be either a single 
screen of corrosion resistant wire of at least 30 by 30 mesh, or two 
screens, both of corrosion resistant wire, of at least 20 by 20 mesh, 
spaced not less than 12.7 millimeters (\1/2\ in.) or more than 38.1 
millimeters (1\1/2\ in.) apart.