[Code of Federal Regulations]
[Title 38, Volume 2]
[Revised as of July 1, 2003]
From the U.S. Government Printing Office via GPO Access
[CITE: 38CFR39.8]

[Page 721-728]
 
            TITLE 38--PENSIONS, BONUSES, AND VETERANS' RELIEF
 
          CHAPTER I--DEPARTMENT OF VETERANS AFFAIRS (CONTINUED)
 
PART 39--STATE CEMETERY GRANTS--Table of Contents
 
Sec. 39.8  General standards for site selection and construction of State 
veterans' cemeteries.

    (a) General. (1) The various codes, requirements, recommendations of 
State and local authorities or technical and professional organizations, 
to the extent and manner in which reference is made in these standards, 
are applicable to grants for construction of State veterans' cemeteries. 
Additional information concerning these standards may be obtained from 
the Department of Veterans Affairs, National Cemetery Administration 
(40G), 810 Vermont Avenue, NW., Washington, DC 20420.
    (2) These standards constitute general design and construction 
criteria and shall apply to all projects for which Federal assistance is 
requested under 38 U.S.C. 2408.
    (3) In developing these standards, no attempt has been made to 
comply with all of the various State and local codes and regulations. 
These standards must be followed where they exceed State or local codes 
and regulations. Departure will be permitted, however, when alternate 
standards will provide equivalent or better design criteria. Conversely, 
compliance is required with State and local codes where such 
requirements provide a higher standard. The additional cost, if any, in 
using standards which are higher than those of the Department of 
Veterans Affairs (VA) should be documented and justified in the 
application.
    (4) The space criteria and area requirements referred to in these 
standards should be used as a guide in planning. Additional area and 
facilities beyond those specified as basic may be included if found to 
be required by the program but are subject to approval by VA. 
Substantial deviation from the space or area standards should be 
carefully considered and justified, except for occasional variances 
which would require individual justification. Failing to meet or 
exceeding the standards by more than 10 percent in the completed plan 
would be regarded as evidence of inferior design or as exceeding the 
boundaries of professional requirements. VA participation may be subject 
to proportionate reduction in those projects which unjustifiably exceed 
maximum space or area criteria.

[[Page 722]]

    (b) Site planning standards--(1) Site selection--(i) Location. The 
land should be located as closely as possible to the densest veteran 
population in the area under consideration.
    (ii) Size. Sufficient acreage should be available to provide 
gravesites for estimated needs for at least 20 years. Acreage could vary 
depending on the State veteran population and National Cemetery 
availability.
    (iii) Accessibility. The site should be readily accessible by 
highway, bus or railroad.
    (iv) Topography. The land should range from comparatively level to 
rolling and moderately hilly terrain. Natural rugged contours are 
suitable only if development and maintenance costs would not be 
excessive and burial areas would be accessible to elderly or infirm 
visitors. The land should not be subject to flooding.
    (v) Water table. The water table should be lower than the maximum 
proposed depth of burial.
    (vi) Soil requirement. The soil should be free from rock, muck, 
quicksand, and other materials that would hamper the economical 
excavation of graves by normal methods. In general, the soil should meet 
the standards of good agricultural land that is capable of supporting 
lawns, shrubs, and trees, with normal care and without the addition of 
topsoil.
    (vii) Utilities. Electricity and/or gas should be available (if 
required).
    (viii) Water supply. An adequate supply of water should be 
available.
    (ix) Sanitary sewer. An approved means to dispose of storm flow and 
sewage from the facility should be available.
    (2) Site development requirements--(i) General. The development plan 
shall provide for adequate hardsurfaced roads, walks, parking areas, 
public rest rooms, flag circle, protective enclosure of the area, and a 
main gate. Pedestrian gates should also be provided at the main gate for 
activities that may be necessary or appropriate when the main gates are 
closed.
    (ii) Road widths. Road widths shall be compatible with proposed 
traffic flows and volumes.
    (iii) Surface and structure parking. All parking facilities shall 
include provisions to accommodate the physically handicapped. A minimum 
of one space shall be set aside and identified with signage in each 
parking area with additional spaces provided in the ratio of one 
handicapped space to every twenty regular spaces. Handicapped spaces 
shall not be placed between two conventional diagonal or head-on-parking 
spaces. Each of the handicapped parking spaces shall not be less than 9 
feet wide; in addition, a clear space 4 feet wide shall be provided 
between the adjacent conventional parking spaces and also on the outside 
of the end spaces.
    (iv) Pavement design. The pavement section of all roads, service 
areas and parking areas shall be designed for the maximum anticipated 
traffic loads and existing soil conditions and in accordance with local 
and State design criteria.
    (v) Curbs. Bituminous roads may be provided with integral curbs and 
gutters constructed of portland cement concrete. Free standing curbs may 
be substituted when the advantage of using them is clearly indicated. 
All curbs shall have a ``roll-type'' cross section for vehicle and 
equipment access to lawn areas except as may be necessary for traffic 
control.
    (vi) Curb radii. The radii of curbs at road intersections shall not 
be less than 20[foot]-0
    (vii) Curb ramps (curb cuts). Curb ramps shall be provided to 
accommodate the physically handicapped and lawnmowers. Curb ramps shall 
be provided at all intersections of roads and walks. The curb ramps 
shall not be less than 4 feet wide; they shall not have a slope greater 
than 8 percent, and preferably not greater than 5 percent. The vertical 
angle between the surface of a curb ramp and the surface of a road or 
gutter shall not be less than 176 degrees; the transition between the 
two surfaces shall be smooth. Curb ramps shall have nonslip surfaces.
    (viii) Walks. Walks shall be designed with consideration for the 
physically handicapped. Walks and ramps designed on an incline shall 
have periodic level platforms. All walks, ramps and platforms shall have 
nonslip surfaces. Any walk shall be ramped if the slope exceeds 3 
percent. Walks that have gradients of from 2 to 3 percent shall be

[[Page 723]]

provided with level platforms at 200-foot intervals and at intersections 
with other walks. Ramps shall not have a slope greater than 8 percent, 
and preferably not greater than 5 percent. The ramps shall have 
handrails on both sides unless other protective devices are provided; 
every handrail shall have clearance of not less than 1\1/2\ inches 
between the back of the handrail and the wall or any other vertical 
surface behind it. Ramps shall not be less than 4 feet wide between 
curbs; curbs shall be provided on both sides. The curbs shall not be 
less than 4 inches high and 4 inches wide. A level platform in a ramp 
shall not be less than the full width of the ramp and not less than 5 
feet long. Entrance platforms and ramps shall be provided with 
protective weather barriers to shield them against hazardous conditions 
resulting from inclement weather.
    (ix) Steps. Exterior steps may be included in the site development 
as long as provisions are also provided for use by physically 
handicapped persons.
    (x) Grading. Minimum lawn slopes shall be 2 percent; critical spot 
grade elevations shall be shown on the contract drawings. Insofar as 
practicable, lawn areas shall be designed without steep slopes.
    (xi) Landscaping. (A) The landscaping plan should provide for a 
park-like setting of harmonious open spaces balanced with groves of 
indigenous and cultivated deciduous and evergreen trees. Shrubbery 
should be kept to a minimum.
    (B) Steep slopes that are unsuitable for interment areas should be 
kept in their natural state.
    (xii) Surface drainage. Surface grades shall be determined in 
coordination with the architectural, structural and mechanical design of 
buildings and facilities so as to provide proper surface drainage.
    (xiii) Burial areas--(A) General. A site plan of the cemetery shall 
include a burial layout. If appropriate, the burial layout should 
reflect the phases of development in the various sections. All 
applicable dimensions to roadways, fences, utilities or other structures 
shall be indicated on the layout.
    (B) Area standard. The VA standard for computing gravesite yield 
from net burial acreage is 600 gravesites per acre. This figure normally 
can account for roads, utilities, and other service related structures. 
Depending on the character of the land and the way in which the cemetery 
is to be developed, a minimum of 50 percent of the gross acreage 
available at the site should be designated as burial acreage. A site 
proposed for development as a veterans' cemetery should be adequate to 
meet the State's projected interment needs for a minimum of twenty 
years.
    (C) Gravesites. Gravesites should be laid out in uniform pattern. 
There should be a minimum of 10 feet from the edge of roads and drives 
and a minimum of 20 feet from the boundaries or fence lines. Maximum 
carrying distance from the edge of a permanent road to any gravesite 
should not be over 275 feet. Temporary roads may be provided to serve 
areas in phase developments.
    (D) Monumentation. Each grave shall be marked with an appropriate 
marker and there shall be kept in each cemetery a register of burials 
setting forth the name of each person buried and the number of the grave 
in which he/she is buried. It is advisable that permanent gravesite 
control markers be installed based on a grid system throughout the 
burial area unless otherwise specified. This will facilitate the 
gravesite layout, placement of utility lines, and alignment of 
headstones. Markers may be either flat or upright, but should be uniform 
throughout the cemetery.
    (c) Space criteria for support facilities. These criteria are based 
on a projected annual burial rate of one to six per day, staffing by 
position, and maintenance and service equipment. For cemeteries with 
less than one or more than six burials per day, support facilities are 
considered on an individual basis in accordance with paragraph (a)(4) of 
this section. In converting NSF (net square feet) to GSF (gross square 
feet), a conversion factor of 1.5 is the maximum allowed. The applicant 
shall, in support of the design, include the following as an attachment 
to the application: A list of all grounds maintenance supplies and 
equipment and the number of FTE (full-time employees) by job assignment 
for the next 10 years.

[[Page 724]]

    (1) Administrative building.

Office, Cemetery Director, 150 NSF
Administrative (Lobby/Office) Area, 165 NSF \1\
---------------------------------------------------------------------------

    \1\ Add 80 NSF for each additional staff (maximum of 2).
---------------------------------------------------------------------------

Operations (File/Work Area), 160 NSF
Family/Conference Room, 200 NSF
Refreshment Unit, 45 NSF
Housekeeping Aid's Closet, 40 NSF
Toilet Facilities,
    Water Closet (Handicapped), 35 NSF
    Each additional fixture, 22 NSF

    (2) Maintenance/service building.\2\
---------------------------------------------------------------------------

    \2\ Service Building may be combined with the administrative 
building.

Office, 150 NSF \3\
---------------------------------------------------------------------------

    \3\ Add 80 NSF for each additional employee required to be located 
in the office.
---------------------------------------------------------------------------

Lunch Room:
    Under 5 FTE, Not authorized
    5 or more FTE (Minimum 120--Maximum 300 NSF), 12 NSF/FTE
Kitchen Unit, 45 NSF
Vending Machines, 25 NSF

    (i) Toilet and Shower Facilities.\4\
---------------------------------------------------------------------------

    \4\ One Water Closet and Shower/30 FTE and One Lavatory/Urinal/20 
FTE or fraction thereof (minimum one handicap equipped per toilet and 
shower room). If FTE exceed 5, provide one Water Closet/Lavatory/Shower 
for females. Recommend that female facilities be located and designed so 
as to be included with male facilities when no females are on 
maintenance staff.
---------------------------------------------------------------------------

    (A) Toilet Facilities:

Water Closet (Handicapped), 35 NSF
    Each additional Fixture, 22 NSF

    (B) Shower:

Handicapped \5\, 80 NSF
---------------------------------------------------------------------------

    \5\ If required by State program requirements.
---------------------------------------------------------------------------

    Standard Fixture, 25 NSF

    (C) Lockers, 6 NSF/FTE
    (D) Boot and Towel Storage, 1.5 NSF/FTE
    (E) Housekeeping aids closet, 40 NSF
    (ii) Vehicle and Equipment Maintenance/Storage.
    (A) Service bay, 450 NSF
    (B) Vehicle and Equipment Storage, 288 NSF/Bay \6\
---------------------------------------------------------------------------

    \6\ /Total NSF divided by 288 = number of bays.

Backhoe, 288 NSF/each
Industrial tractors, 96 NSF/each
Cub tractors, 32 NSF/each
Hand Mower and trimmers, 12 NSF/each

    (C) Ground Maintenance Storage, 288 NSF
    (D) Flammable Storage, 100 NSF
    (iii) Other Equipment Storage: Based on climatic conditions it may 
be justified to erect open structures or paved areas to protect the 
following types of equipment.

Dump Trucks, 240 NSF/each
Pickup Trucks, 240 NSF/each
Cemetery Automobiles, 240 NSF/each
Gang & Circular Mowers, 29 NSF/each
Dumpsters (Trash/Solid Waste) \7\, 240 NSF/each
---------------------------------------------------------------------------

    \7\ No allowance for cover or enclosure.
---------------------------------------------------------------------------

Dump Wagon or utility trailers \7\, 240 NSF/each
Plow Blades \7\, 120 NSF/each
Headstones/Markers \7\, 120 NSF

    (3) Interment/Committal Service Shelter: One permanent shelter is 
authorized for every five interments per day.

Covered area (maximum 256 NSF), 16 NSF/person
Total paved area (including covered area), 784 NSF
Enclosed equipment/storage area, 40 NSF

    (4) Interment/Committal Service Chapel: A chapel may be substituted 
for the interment/committal service shelters. Only one chapel is allowed 
per cemetery.

Chapel area (fixed seating and chancel), 512 NSF
Clergy robing room, 100 NSF
General storage, 80 NSF
Housekeeping aid's Closet, 40 NSF
Restroom(s) Men/Women:
    Water Closet (each Handicapped restroom), 35 NSF
    Lavatory (each restroom), 22 NSF
    Urinal (Men's restroom), 22 NSF

    (5) Public Restrooms: Space determinations for separate structures 
for public restrooms will be considered on an individual basis.
    (6) Other Interment Structures: Space determinations for other 
support facilities such as columbaria, mausolea or garden crypts, etc., 
will be considered on an individual basis in accordance with paragraph 
(a)(4) of this section.
    (d) Architectural Design Standards--(1) Architectural and Structural 
Requirements--(i) Life Safety Code. The 1981 edition of the Code for 
Safety to Life from Fire in Buildings and Structures (NFPA 101) 
published by the National

[[Page 725]]

Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA, 
02269, will be the design criteria. The 1981 edition of the Life Safety 
Code (NFPA 101) is hereby incorporated by reference into this section as 
though set forth in full herein. This incorporation by reference was 
approved by the Director of the Federal Register on October 28, 1982. 
This code is incorporated as it was on the date of approval and a notice 
of any change in this code will be published in the Federal Register. 
This code is available for inspection at the Office of Federal Register, 
800 North Capitol Street, NW., suite 700, Washington, DC. Fire safety 
construction features not included in NFPA 101 shall be designed in 
accordance with the standards of the 1976 edition (R1977) of the 
National Building Code published by the American Insurance Association 
Engineering and Safety Services, 85 John Street, New York, NY 10038. The 
1976 edition (R1977) of the National Building Code is hereby 
incorporated by reference into this section as though set forth in full 
herein. This incorporation by reference was approved by the Director of 
the Federal Register on October 28, 1982. This code is incorporated as 
it was on the date of approval and a notice of any change in this code 
will be published in the Federal Register. This code is available for 
inspection at the Office of the Federal Register, 800 North Capitol 
Street, NW., suite 700, Washington, DC. Where the adopted codes state 
conflicting requirements, the National Fire Codes shall govern.
    (ii) State and Local Codes. In addition to compliance with the 
standards set forth in this document, all applicable local and State 
building codes and regulations must be observed. In areas not subject to 
local or State building codes, the recommendations contained in the 1976 
edition (R1977) of the National Building Code (see Sec. 39.8(d)(1)(i)) 
shall apply insofar as such recommendations are not in conflict with the 
standards set forth in this document.
    (iii) Occupational safety and health standards. Applicable standards 
as contained in the Occupational Safety and Health Act must be observed.
    (2) Mechanical requirements. The heating system, boilers, steam 
system, ventilation system and air-conditioning system shall be 
furnished and installed to meet all requirements of the local and State 
codes and regulations.
    (3) Plumbing requirements. Plumbing systems shall comply with all 
applicable local and State codes, the requirements of the State 
Department of Health, and the minimum general standards as set forth in 
this part. Where no State or local codes are in force, the 1978 edition 
of the National Standard Plumbing Code, published jointly by the 
American Society of Plumbing Engineers and the National Association of 
Plumbing-Heating-Cooling Contractors, 1016 20th Street, NW., Washington, 
DC 20036, shall apply. The 1978 edition of the National Standard 
Plumbing Code is hereby incorporated by reference into this section as 
though set forth in full herein. This incorporation by reference was 
approved by the Director of the Federal Register on October 28, 1982. 
This code is incorporated as it was on the date of approval and a notice 
of any change in this code will be published in the Federal Register. 
This code is available for inspection at the Office of the Federal 
Register, 800 North Capitol Street, NW., suite 700, Washington, DC.
    (4) Electrical requirements. The installation of electrical work and 
equipment shall comply with the 1981 National Electrical Code (NFPA No. 
70), all State and local codes and laws applicable to electrical 
installations, and the minimum general standards as set forth in this 
part. The regulations of the local utility company shall govern service 
connections. Aluminum busways should not be used as a conducting medium 
in the electrical distribution system. The 1981 edition of the National 
Electrical Code is hereby incorporated by reference into this section as 
though set forth in full herein. This incorporation by reference was 
approved by the Director of the Federal Register on October 28, 1982. 
This code is incorporated as it was on the date of approval and a notice 
of any change in this code will be published in the Federal Register. 
This code is available

[[Page 726]]

for inspection at the Office of the Federal Register, 800 North Capitol 
Street, NW., suite 700, Washington, DC.
    (e) Plan preparation--(1) General. The requirements contained herein 
have been established for the guidance of the state agency and the 
architect to provide a standard for preparation of drawings, 
specifications and estimates.
    (2) Predesign conferences. A conference is recommended for all major 
construction projects primarily to ensure that the State agency becomes 
oriented to VA procedures and requirements plus any technical comments 
pertaining to the project.
    (3) Preapplication requirements. No plans and specifications will be 
required with the preapplication submission to the VA. The program 
narrative shall describe the need, objectives, method of accomplishment, 
projected interment rate, benefits expected to be obtained from the 
assistance and include design concepts, space outline, geographical 
location (i.e., a location map showing the location of the project and 
all appropriate demographic boundaries), etc.
    (4) Formal application requirements--(i) Boundary and site survey 
and soil investigation. (A) The State agency shall provide for a survey 
and soil investigation of the site and furnish a legal description of 
the site. The purpose of this survey and soil investigation is to obtain 
data necessary for the evaluation of the site as a cemetery, structural 
design and utility service connections. A boundary and site survey need 
not be submitted if one was submitted for a previously approved project 
and there have been no changes. Relevant information may then be shown 
on the site plan.
    (B) If required the survey shall show:
    (1) The outline and location referenced to boundaries, of all 
existing buildings, streets, alleys (whether public or private), block 
boundaries, easements, encroachments, the names of streets, railroads 
and streams, and other information as hereinafter specified. If there is 
nothing of this character affecting the property, the Surveyor shall so 
state on the drawings.
    (2) The point of beginning, bearing, distances, and interior angles. 
Closures computations shall be furnished with the survey and error of 
closure shall not exceed 1 foot each 10,000 feet or lineal traverse. 
Boundaries of an unusual nature (curvilinear, off-set, or having other 
change or direction between corners), shall be referenced with curve 
data (including measurement chord) and other data sufficient for 
replacement and such information shall be shown on the map. For 
boundaries of such nature, coordinates shall be given for all angles and 
other pertinent points.
    (3) The area of the parcel in acres or in square feet.
    (4) The location of all monuments.
    (5) Delineation of 100-year floodplain and source.
    (6) The signature and certification of the Surveyor.
    (C) Soil investigation of the scope necessary to ascertain site 
characteristics for construction and burial or to determine foundation 
requirements. A new soil investigation is not required if one was done 
for a previously approved project on the same site and information 
contained is adequate and unchanged. Soil investigation, when done, 
shall be documented in a signed report.
    (1) Adequate investigation shall be made to determine the subsoil 
conditions. The investigation shall include a sufficient number of test 
pits or test borings as will determine, in the judgment of the 
architect, the true conditions.
    (2) The following information shall be covered in the report:
    (i) Thickness, consistency, character, and estimated safe bearing 
value where needed for structural foundation design of the various 
strata encountered in each pit or boring.
    (ii) Amount and elevation of ground water encountered in each pit or 
boring, its probable variation with the seasons, and effect on the 
subsoil.
    (iii) The elevation of rock, if known and the probability of 
encountering quicksand.
    (3) The elevations and location of tops of workings relative to the 
site, if the site is underlaid with mines, or old workings are located 
in the vicinity.

[[Page 727]]

    (ii) Preliminary site plan. A site plan showing the proposed layout 
of all facilities on the selected site shall be included as an exhibit 
to the formal application. If the project is to be phased into different 
year programs, the phasing shall be indicated. The preliminary site plan 
shall be submitted on standard 28 inch by 42 inch plan sheets at a scale 
sufficiently large to show necessary details or dimensions.
    (iii) Preliminary architectural drawings. All buildings are to be 
shown on drawings accompanying the application. The drawings must comply 
with the following requirements:
    (A) A site plan of the immediate area around the building shall be 
drawn to a convenient scale and shall show the building room plan, 
utility services, walks, gates, walls or fences, flagpoles, drives, 
parking areas, indication of handicapped provisions, landscaping, north 
arrow and any other appropriate items.
    (B) Floor plans of all levels at a convenient scale shall be double 
line drawings and shall show overall dimensions, construction materials, 
door swings, names and square feet for each space, toilet room fixtures 
and interior finish schedule.
    (C) Elevations of the exteriors of all buildings shall be drawn to 
the same scale as the plan and shall include all material indications.
    (D) Preliminary mechanical and electrical layout plans shall be 
drawn at a convenient scale and shall have an equipment and plumbing 
fixture schedule.
    (f) Final working drawings and specifications. Prior to the release 
of funds for the construction of any project being sponsored under this 
program, VA must approve the final working drawings and specifications. 
The approval by VA is notification to the applicant that the project 
complies with the terms and conditions prescribed by VA and does not 
constitute approval of the contract documents. It is the responsibility 
of the State to ascertain that all State and Federal requirements have 
been met and that the drawings and specifications are acceptable for bid 
purposes.
    (1) Final working drawings shall be prepared so that clear and 
distinct prints may be obtained, accurately dimensioned and include all 
necessary explanatory notes, schedules and legends. Working drawings 
shall be complete and adequate for complete VA review and comment. 
Separate drawings shall be prepared for each of the following types of 
work: architectural, structural, heating and ventilating, plumbing and 
electrical. They shall include the following:
    (i) Architectural drawings. Site plan showing all new topography, 
grades, existing buildings, roadways, walks and areas to be seeded. All 
structures and other work to be removed; all floor plans and a room plan 
if any new work is involved; all elevations which are affected by the 
alterations; building sections; demolition drawings. All details to 
complete the proposed work and finish schedules.
    (ii) Planting drawings. (A) All proposed features such as roads, 
buildings, walks, utility lines, burial layout, etc.
    (B) Contours, scale, north arrow, legend showing existing trees.
    (C) A graphic or keyed method of showing plant types as well as 
quantities of each plant.
    (D) Plant list with the following: Key, quantity, botanical name, 
common name, size and remarks (i.e., balled and burlaped, container, 3 
stem clump, specimen, etc.)
    (E) Typical tree and shrub planting details.
    (F) Areas to be seeded or sodded.
    (G) Areas to be mulched.
    (iii) Layout drawings. Submit a layout plan which shows the 
following:
    (A) Roadways, walks, buildings, scale and north arrow, boundary 
lines and fence lines.
    (B) Section layout with permanent section monument markers and 
lettering system.
    (C) Gravesite layout and numbering system.
    (D) Gravesites which are obstructed.
    (E) Direction the headstone faces.

If the cemetery is existing and the project is expansion or renovation, 
show available, occupied, obstructed and reserved gravesites.
    (iv) Equipment drawings. Large scale drawings of typical special 
rooms indicating all fixed equipment and major

[[Page 728]]

items of furniture and moveable equipment.
    (v) Structural drawings. Complete foundation and framing plans and 
details. General notes to include: Governing code, material strengths, 
live loads, windloads, foundation design values, and seismic zone.
    (vi) Mechanical drawings. Heating and ventilation drawings showing 
complete systems and details of air conditioning, heating, ventilation 
and exhaust. Plumbing drawings showing sizes and elevations of soil and 
waste systems; sizes of all hot and cold water piping; drainage and vent 
systems; plumbing fixtures and riser diagrams.
    (vii) Electrical drawings. Separate drawings for lighting and power. 
Service entrance, feeders and all characteristics. All panel, breaker, 
switchboard and fixture schedule. All lighting outlets, receptacles, 
switches, power outlets and circuits. Telephone layout, fire alarm 
systems and emergency lighting.
    (2) Final specifications (to be used for bid purposes) shall be in 
completed format. Specifications shall include the invitations for bids, 
cover of title sheet, index, general requirements, form of bid bond, 
form of agreement, performance and payment bond forms, and sections 
describing materials and workmanship in detail for each class of work.
    (3) Show in convenient form and detail the estimated total cost of 
the work to be performed under the contract including provisions of 
fixed equipment shown by the plans and specifications, if applicable, to 
reflect the changes of the approved financial plan. Estimates shall be 
summarized and totaled under each trade or type of work.
    (4) All of the above requirements must be met and approved prior to 
the State agency advertising for bids.
    (g) Final review and approval--(Bid tabulations and cost estimates). 
(1) The State agency shall submit itemized bid tabulations; assurance, 
if required; and a revised grant application form reflecting project 
cost(s) based on bids. If there are non-VA participating area(s), these 
should be itemized separately.
    (2) Following VA approval of bid tabulations and cost estimates, the 
grant will be awarded by a Notification of Award of Federal Grant Funds.


(Authority: 38 U.S.C. 2408)

(Information collection requirements in paragraphs (b)(2)(xiii)(D), (c), 
and (e) were approved by the Office of Management and Budget under 
control number 2900-0375)

[47 FR 49395, Nov. 1, 1982, as amended at 54 FR 34988, Aug. 23, 1989