[Code of Federal Regulations]
[Title 40, Volume 11]
[Revised as of July 1, 2003]
From the U.S. Government Printing Office via GPO Access
[CITE: 40CFR63.1257]

[Page 122-155]
 
                   TITLE 40--PROTECTION OF ENVIRONMENT
 
         CHAPTER I--ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)
 
PART 63--NATIONAL EMISSION STANDARDS FOR HAZARDOUS AIR POLLUTANTS FOR SOURCE CATEGORIES--Table of Contents
 
 Subpart GGG--National Emission Standards for Pharmaceuticals Production
 
Sec. 63.1257   Test methods and compliance procedures.

    (a) General. Except as specified in paragraph (a)(5) of this 
section, the procedures specified in paragraphs (c), (d), (e), and (f) 
of this section are required to demonstrate initial compliance with 
Secs. 63.1253, 63.1254, 63.1256, and 63.1252(e), respectively. The 
provisions in paragraphs (a) (2) through (3) apply to performance tests 
that are specified in paragraphs (c), (d), and (e) of this section. The 
provisions in paragraph (a)(5) of this section are used to demonstrate 
initial compliance with the alternative standards specified in 
Secs. 63.1253(d) and 63.1254(c). The provisions in paragraph (a)(6) of 
this section are used to comply with the outlet concentration 
requirements specified in Secs. 63.1253(c), 63.1254 (a)(2)(i) and 
(a)(3)(ii)(B), 63.1254(b)(i) and 63.1256(h)(2).
    (1) Design evaluation. To demonstrate that a control device meets 
the required control efficiency, a design evaluation must address the 
composition and organic HAP concentration of the vent stream entering 
the control device. A design evaluation also must address other vent 
stream characteristics and control device operating parameters as 
specified in any one of paragraphs (a)(1) (i) through (vi) of this 
section, depending on the type of control device that is used. If the 
vent stream is not the only inlet to the control device, the efficiency 
demonstration also must consider all other vapors, gases, and liquids, 
other than fuels, received by the control device.
    (i) For an enclosed combustion device used to comply with the 
provisions of 63.1253 (b)(2) or (c)(2), or 63.1256(h)(2)(i)(C) with a 
minimum residence time of 0.5 seconds and a minimum temperature of 760 
C, the design evaluation must document that these conditions exist.
    (ii) For a combustion control device that does not satisfy the 
criteria in paragraph (a)(1)(i) of this section, the design evaluation 
must document control efficiency and address the following 
characteristics, depending on the type of control device:
    (A) For a thermal vapor incinerator, the design evaluation must 
consider the autoignition temperature of the organic HAP, must consider 
the vent stream flow rate, and must establish the design minimum and 
average temperature in the combustion zone and the combustion zone 
residence time.
    (B) For a catalytic vapor incinerator, the design evaluation shall 
consider the vent stream flow rate and shall establish the design 
minimum and average temperatures across the catalyst bed inlet and 
outlet.
    (C) For a boiler or process heater, the design evaluation shall 
consider the vent stream flow rate; shall establish the design minimum 
and average flame zone temperatures and combustion zone residence time; 
and shall describe the method and location where the vent stream is 
introduced into the flame zone.
    (iii) For a condenser, the design evaluation shall consider the vent 
stream flow rate, relative humidity, and temperature and shall establish 
the design outlet organic HAP compound concentration level, design 
average temperature of the condenser exhaust vent

[[Page 123]]

stream, and the design average temperatures of the coolant fluid at the 
condenser inlet and outlet. The temperature of the gas stream exiting 
the condenser must be measured and used to establish the outlet organic 
HAP concentration.
    (iv) For a carbon adsorption system that regenerates the carbon bed 
directly onsite in the control device such as a fixed-bed adsorber, the 
design evaluation shall consider the vent stream flow rate, relative 
humidity, and temperature and shall establish the design exhaust vent 
stream organic compound concentration level, adsorption cycle time, 
number and capacity of carbon beds, type and working capacity of 
activated carbon used for carbon beds, design total regeneration stream 
mass or volumetric flow over the period of each complete carbon bed 
regeneration cycle, design carbon bed temperature after regeneration, 
design carbon bed regeneration time, and design service life of carbon. 
For vacuum desorption, the pressure drop shall be included.
    (v) For a carbon adsorption system that does not regenerate the 
carbon bed directly onsite in the control device such as a carbon 
canister, the design evaluation shall consider the vent stream mass or 
volumetric flow rate, relative humidity, and temperature and shall 
establish the design exhaust vent stream organic compound concentration 
level, capacity of carbon bed, type and working capacity of activated 
carbon used for carbon bed, and design carbon replacement interval based 
on the total carbon working capacity of the control device and source 
operating schedule.
    (vi) For a scrubber, the design evaluation shall consider the vent 
stream composition; constituent concentrations; liquid-to-vapor ratio; 
scrubbing liquid flow rate and concentration; temperature; and the 
reaction kinetics of the constituents with the scrubbing liquid. The 
design evaluation shall establish the design exhaust vent stream organic 
compound concentration level and will include the additional information 
in paragraphs (a)(1)(vi)(A) and (B) of this section for trays and a 
packed column scrubber.
    (A) Type and total number of theoretical and actual trays;
    (B) Type and total surface area of packing for entire column, and 
for individual packed sections if column contains more than one packed 
section.
    (2) Calculation of TOC or total organic HAP concentration. The TOC 
concentration or total organic HAP concentration is the sum of the 
concentrations of the individual components. If compliance is being 
determined based on TOC, the owner or operator shall compute TOC for 
each run using Equation 6 of this subpart. If compliance with the 
wastewater provisions is being determined based on total organic HAP, 
the owner or operator shall compute total organic HAP using Equation 6 
of this subpart, except that only the organic HAP compounds shall be 
summed; when determining compliance with paragraph (e)(3)(i) of this 
section, only the soluble and partially soluble HAP compounds shall be 
summed.
[GRAPHIC] [TIFF OMITTED] TR21SE98.003

where:
    CGT=total concentration of TOC in vented gas stream, 
average of samples, dry basis, ppmv
CGSi,j=concentration of sample components in vented gas 
stream for sample j, dry basis, ppmv
i=identifier for a compound
n=number of components in the sample
j=identifier for a sample
m=number of samples in the sample run

    (3) Outlet concentration correction for supplemental gases. (i) 
Combustion devices. Except as provided in Sec. 63.1258(b)(5)(ii)(A), for a 
combustion device used to comply with an outlet concentration standard, 
the actual TOC, organic HAP, and hydrogen halide and halogen must be 
corrected to 3 percent oxygen if supplemental gases, as defined in Sec. 
63.1251, are added to the vent stream or manifold. The integrated 
sampling and analysis procedures of Method 3B of 40 CFR part 60, 
appendix A, shall be used to determine the actual oxygen concentration 
(%O2d). The samples shall be taken during the same time that 
the TOC or

[[Page 124]]

total organic HAP or hydrogen halides and halogen samples are taken. The 
concentration corrected to 3 percent oxygen (Cd) shall be 
computed using Equation 7A of this subpart:
[GRAPHIC] [TIFF OMITTED] TR29AU00.002

Where:

Cc = concentration of TOC or total organic HAP or hydrogen 
halide and halogen corrected to 3 percent oxygen, dry basis, ppmv
Cm = total concentration of TOC or total organic HAP or 
hydrogen halide and halogen in vented gas stream, average of samples, 
dry basis, ppmv
%O2d = concentration of oxygen measured in vented gas stream, 
dry basis, percent by volume

    (ii) Noncombustion devices. Except as provided in Sec. 
63.1258(b)(5)(ii)(B), if a control device other than a combustion device 
is used to comply with a TOC, organic HAP, or hydrogen halide outlet 
concentration standard, the owner or operator must correct the actual 
concentration for supplemental gases using Equation 7B of this subpart; 
process knowledge and representative operating data may be used to 
determine the fraction of the total flow due to supplemental gas.
[GRAPHIC] [TIFF OMITTED] TR29AU00.003

Where:

Ca = corrected outlet TOC, organic HAP, and hydrogen halides 
and halogens concentration, dry basis, ppmv
Cm = actual TOC, organic HAP, and hydrogen halides and 
halogens concentration measured at control device outlet, dry basis, 
ppmv
Va = total volumetric flow rate of all gas streams vented to 
the control device, except supplemental gases
Vs = total volumetric flow rate of supplemental gases

    (4) Exemptions from compliance demonstrations. An owner or operator 
using any control device specified in paragraphs (a)(4)(i) through (iv) 
of this section is exempt from the initial compliance provisions in 
paragraphs (c), (d), and (e) of this section.
    (i) A boiler or process heater with a design heat input capacity of 
44 megawatts or greater.
    (ii) A boiler or process heater into which the emission stream is 
introduced with the primary fuel.
    (iii) A boiler or process heater burning hazardous waste for which 
the owner or operator:
    (A) Has been issued a final permit under 40 CFR part 270 and 
complies with the requirements of 40 CFR part 266, subpart H, or
    (B) Has certified compliance with the interim status requirements of 
40 CFR part 266, subpart H.
    (iv) A hazardous waste incinerator for which the owner or operator 
has been issued a final permit under 40 CFR part 270 and complies with 
the requirements of 40 CFR part 264, subpart O, or has certified 
compliance with the interim status requirements of 40 CFR part 265, 
subpart O.
    (5) Initial compliance with alternative standard. Initial compliance 
with the alternative standards in Secs. 63.1253(d) and 63.1254(c) for 
combustion devices is demonstrated when the outlet TOC concentration is 
20 ppmv or less, and the outlet hydrogen halide and halogen 
concentration is 20 ppmv or less. Initial compliance with the 
alternative standards in Secs. 63.1253(d) and 63.1254(c) for 
noncombustion devices is demonstrated when the outlet TOC concentration 
is 50 ppmv or less, and the outlet hydrogen halide and hydrogen 
concentration is 50 ppmv or less. To demonstrate initial compliance, the 
owner or operator shall be in compliance with the monitoring provisions 
in Sec. 63.1258(b)(5) on the initial compliance date. The owner or operator 
shall use Method 18 to determine the predominant organic HAP in the 
emission stream if the TOC monitor is calibrated on the predominant HAP.
    (6) Initial compliance with the 20 ppmv outlet limit. Initial 
compliance with the 20 ppmv TOC and hydrogen halide and halogen 
concentration is demonstrated when the outlet TOC concentration is 20 
ppmv or less, and the outlet hydrogen halide and halogen concentration

[[Page 125]]

is 20 ppmv or less. To demonstrate initial compliance, the operator 
shall use test methods described in paragraph (b) of this section. The 
owner or operator shall comply with the monitoring provisions in Sec. 
63.1258(b)(1) through (4) on the initial compliance date.
    (b) Test methods. When testing is conducted to measure emissions 
from an affected source, the test methods specified in paragraphs (b)(1) 
through (10) of this section shall be used.
    (1) EPA Method 1 or 1A of appendix A of part 60 is used for sample 
and velocity traverses.
    (2) EPA Method 2, 2A, 2C, or 2D of appendix A of part 60 is used for 
velocity and volumetric flow rates.
    (3) EPA Method 3 of appendix A of part 60 is used for gas analysis.
    (4) EPA Method 4 of appendix A of part 60 is used for stack gas 
moisture.
    (5) [Reserved]
    (6) The following methods are specified for concentration 
measurements:
    (i) Method 18 may be used to determine HAP concentration in any 
control device efficiency determination.
    (ii) Method 25 of appendix A of part 60 may be used to determine 
total gaseous nonmethane organic concentration for control efficiency 
determinations in combustion devices.
    (iii) Method 26 or 26A of appendix A of part 60 shall be used to 
determine hydrogen chloride, hydrogen halide and halogen concentrations 
in control device efficiency determinations or in the 20 ppmv outlet 
hydrogen halide concentration standard.
    (iv) Method 25A of appendix A of part 60 may be used to determine 
the HAP or TOC concentration for control device efficiency 
determinations under the conditions specified in Method 25 of appendix A 
for direct measurement of an effluent with a flame ionization detector, 
or in demonstrating compliance with the 20 ppmv TOC outlet standard. If 
Method 25A is used to determine the concentration of TOC for the 20 ppmv 
standard, the instrument shall be calibrated on methane or the 
predominant HAP. If calibrating on the predominant HAP, the use of 
Method 25A shall comply with paragraphs (b)(6)(iv)(A) through (C) of 
this section.
    (A) The organic HAP used as the calibration gas for Method 25A, 40 
CFR part 60, appendix A, shall be the single organic HAP representing 
the largest percent by volume.
    (B) The use of Method 25A, 40 CFR part 60, appendix A, is acceptable 
if the response from the high level calibration gas is at least 20 times 
the standard deviation of the response from the zero calibration gas 
when the instrument is zeroed on the most sensitive scale.
    (C) The span value of the analyzer must be less than 100 ppmv.
    (7) Testing conditions for continuous processes. Testing of 
emissions on equipment operating as part of a continuous process will 
consist of three l-hour runs. Gas stream volumetric flow rates shall be 
measured every 15 minutes during each 1-hour run. The HAP concentration 
shall be determined from samples collected in an integrated sample over 
the duration of each l-hour test run, or from grab samples collected 
simultaneously with the flow rate measurements (every 15 minutes). If an 
integrated sample is collected for laboratory analysis, the sampling 
rate shall be adjusted proportionally to reflect variations in flow 
rate. For continuous gas streams, the emission rate used to determine 
compliance shall be the average emission rate of the three test runs.
    (8) Testing and compliance determination conditions for batch 
processes. Testing of emissions on equipment where the flow of gaseous 
emissions is intermittent (batch operations) shall be conducted as 
specified in paragraphs (b)(8)(i) through (iii) of this section.
    (i) Except as provided in paragraph (b)(9) of this section for 
condensers, testing shall be conducted at absolute worst-case conditions 
or hypothetical worst-case conditions. Gas stream volumetric flow rates 
shall be measured at 15-minute intervals. The HAP or TOC concentration 
shall be determined from samples collected in an integrated sample over 
the duration of the test, or from grab samples collected simultaneously 
with the flow rate measurements (every 15 minutes). If an integrated 
sample is collected for laboratory analysis, the sampling rate shall be 
adjusted proportionally to reflect variations in flow rate. The absolute 
worst-case or hypothetical worst-case

[[Page 126]]

conditions shall be characterized by the criteria presented in 
paragraphs (b)(8)(i)(A) and (B)of this section. In all cases, a site-
specific plan shall be submitted to the Administrator for approval prior 
to testing in accordance with Sec. 63.7(c) and Sec. 63.1260(l). The test plan 
shall include the emission profile described in paragraph (b)(8)(ii) of 
this section.
    (A) Absolute worst-case conditions are defined by the criteria 
presented in paragraph (b)(8)(i)(A)(1) or (2) of this section if the 
maximum load is the most challenging condition for the control device. 
Otherwise, absolute worst-case conditions are defined by the conditions 
in paragraph (b)(8)(i)(A)(3) of this section. The owner or operator must 
consider all relevant factors, including load and compound-specific 
characteristics in defining absolute worst-case conditions.
    (1) The period in which the inlet to the control device will contain 
at least 50 percent of the maximum HAP load (in lb) capable of being 
vented to the control device over any 8 hour period. An emission profile 
as described in paragraph (b)(8)(ii)(A) of this section shall be used to 
identify the 8-hour period that includes the maximum projected HAP load.
    (2) A 1-hour period of time in which the inlet to the control device 
will contain the highest HAP mass loading rate, in lb/hr, capable of 
being vented to the control device. An emission profile as described in 
paragraph (b)(8)(ii)(A) of this section shall be used to identify the 1-
hour period of maximum HAP loading.
    (3) The period of time when the HAP loading or stream composition 
(including non-HAP) is most challenging for the control device. These 
conditions include, but are not limited to the following:
    (i) Periods when the stream contains the highest combined VOC and 
HAP load, in lb/hr, described by the emission profiles in paragraph 
(b)(8)(ii) of this section;
    (ii) Periods when the streams contain HAP constituents that approach 
limits of solubility for scrubbing media;
    (iii) Periods when the streams contain HAP constituents that 
approach limits of adsorptivity for carbon adsorption systems.
    (B) Hypothetical worst-case conditions are simulated test conditions 
that, at a minimum, contain the highest hourly HAP load of emissions 
that would be predicted to be vented to the control device from the 
emissions profile described in paragraph (b)(8)(ii)(B) or (C) of this 
section.
    (ii) Emissions profile. The owner or operator may choose to perform 
tests only during those periods of the worst-case conditions that the 
owner or operator selects to control as part of achieving the required 
emission reduction. The owner or operator must develop an emission 
profile for the vent to the control device that describes the 
characteristics of the vent stream at the inlet to the control device 
under worst case conditions. The emission profile shall be developed 
based on any one of the procedures described in (b)(8)(ii)(A) through 
(C) of this section, as required by paragraph (b)(8)(i).
    (A) Emission profile by process. The emission profile must consider 
all emission episodes that could contribute to the vent stack for a 
period of time that is sufficient to include all processes venting to 
the stack and shall consider production scheduling. The profile shall 
describe the HAP load to the device that equals the highest sum of 
emissions from the episodes that can vent to the control device in any 
given hour. Emissions per episode shall be calculated using the 
procedures specified in paragraph (d)(2) of this section. Emissions per 
episode shall be divided by the duration of the episode only if the 
duration of the episode is longer than 1 hour.
    (B) Emission profile by equipment. The emission profile must consist 
of emissions that meet or exceed the highest emissions, in lb/hr, that 
would be expected under actual processing conditions. The profile shall 
describe equipment configurations used to generate the emission events, 
volatility of materials processed in the equipment, and the rationale 
used to identify and characterize the emission events. The emissions may 
be based on using a compound more volatile than compounds actually used 
in the process(es), and the emissions may be generated from

[[Page 127]]

all equipment in the process(es) or only selected equipment.
    (C) Emission profile by capture and control device limitation. The 
emission profile shall consider the capture and control system 
limitations and the highest emissions, in lb/hr, that can be routed to 
the control device, based on maximum flowrate and concentrations 
possible because of limitations on conveyance and control equipment 
(e.g., fans, LEL alarms and safety bypasses).
    (iii) Three runs, at a minimum of 1 hour each and a maximum of 8 
hours each, are required for performance testing. Each run must occur 
over the same worst-case conditions, as defined in paragraph (b)(8)(i) 
of this section.
    (9) Testing requirements for condensers. For emission streams 
controlled using condensers, continuous direct measurement of condenser 
outlet gas temperature to be used in determining concentrations per the 
design evaluation described in Sec. 63.1257(a)(1)(iii) is required.
    (10) Wastewater testing. Wastewater analysis shall be conducted in 
accordance with paragraph (b)(10)(i), (ii), (iii), (iv), or (v) of this 
section.
    (i) Method 305. Use procedures specified in Method 305 of 40 CFR 
part 63, appendix A, and comply with requirements specified in paragraph 
(b)(10)(vi) of this section.
    (ii) EPA Method 624, 625, 1624, 1625, 1666, or 1671. Use procedures 
specified in EPA Method 624, 625, 1624, 1625, 1666, or 1671 of 40 CFR 
part 136, appendix A, and comply with requirements in paragraph 
(b)(10)(vi) of this section.
    (iii) Method 8260 or 8270. Use procedures specified in Method 8260 
or 8270 in ``Test Methods for Evaluating Solid Waste, Physical/Chemical 
Methods,'' EPA Publication No. SW-846, Third Edition, September 1986, as 
amended by Update I, November 15, 1992. As an alternative, an owner or 
operator may use any more recent, updated version of Method 8260 or 8270 
approved by the EPA. For the purpose of using Method 8260 or 8270 to 
comply with this subpart, the owner or operator must maintain a formal 
quality assurance program consistent with either Section 8 of Method 
8260 or Method 8270, and this program must include the following 
elements related to measuring the concentrations of volatile compounds:
    (A) Documentation of site-specific procedures to minimize the loss 
of compounds due to volatilization, biodegradation, reaction, or 
sorption during the sample collection, storage, and preparation steps.
    (B) Documentation of specific quality assurance procedures followed 
during sampling, sample preparation, sample introduction, and analysis.
    (C) Measurement of the average accuracy and precision of the 
specific procedures, including field duplicates and field spiking of the 
material source before or during sampling with compounds having similar 
chemical characteristics to the target analytes.
    (iv) Other EPA methods. Use procedures specified in the method, 
validate the method using the procedures in paragraph (b)(10)(iv)(A) or 
(B) of this section, and comply with the procedures in paragraph 
(b)(10)(vi) of this section.
    (A) Validate the method according to section 5.1 or 5.3 of Method 
301 of 40 CFR part 63, appendix A.
    (B) Follow the procedure as specified in ``Alternative Validation 
Procedure for EPA Waste Methods'' 40 CFR part 63, appendix D.
    (v) Methods other than an EPA method. Use procedures specified in 
the method, validate the method using the procedures in paragraph 
(b)(10)(iv)(A) of this section, and comply with the requirements in 
paragraph (b)(10)(vi) of this section.
    (vi) Sampling plan. The owner or operator shall prepare a sampling 
plan. Wastewater samples shall be collected using sampling procedures 
which minimize loss of organic compounds during sample collection and 
analysis and maintain sample integrity. The sample plan shall include 
procedures for determining recovery efficiency of the relevant partially 
soluble and soluble HAP compounds. An example of an acceptable sampling 
plan would be one that incorporates similar sampling and sample handling 
requirements to those of Method 25D of 40 CFR part 60, appendix A. The 
sampling plan shall be maintained at the facility.
    (c) Initial compliance with storage tank provisions. The owner or 
operator of an

[[Page 128]]

affected storage tank shall demonstrate initial compliance with Sec. 
63.1253(b) or (c), as applicable, by fulfilling the requirements of 
paragraph (c)(1),or (c)(2), or (c)(3) of this section.
    (1) Performance test. If this option is chosen to demonstrate 
initial compliance with the percent reduction requirement of Sec. 
63.1253(b)(1) or (c)(1)(i), the efficiency of the control device shall 
be calculated using performance test data as specified in paragraphs 
(c)(1)(i) through (iii) of this section. To demonstrate initial 
compliance with the outlet concentration requirements in Sec. 63.1253(b)(2) 
and (c)(2), the owner or operator must conduct a performance test and 
fulfill the requirements of paragraph (a)(6) of this section.
    (i) Equations 8 and 9 of this subpart shall be used to calculate the 
mass rate of total HAP reasonably expected maximum filling rate at the 
inlet and outlet of the control device for standard conditions of 20 C: 
where:
[GRAPHIC] [TIFF OMITTED] TR21SE98.005

[GRAPHIC] [TIFF OMITTED] TR21SE98.006

where:

Cij, Coj = concentration of sample component j of 
the gas stream at the inlet and outlet of the control device, 
respectively, dry basis, ppmv
Ei, Eo = mass rate of total HAP at the inlet and 
outlet of the control device, respectively, dry basis, kg/hr
Mij, Moj = molecular weight of sample component j 
of the gas stream at the inlet and outlet of the control device, 
respectively, gram/gram-mole
Qi, Qo = flow rate of gas stream at the inlet and 
outlet of the control device, respectively, dry standard cubic meter per 
minute
K2 = constant, 2.494 x 10-6 (parts per million) 
-1 (gram-mole per standard cubic meter) (kilogram/gram) 
(minute/hour), where standard temperature is 20 C
n = number of sample components in the gas stream

    (ii) The percent reduction in total HAP shall be calculated using 
Equation 10 of this subpart:
[GRAPHIC] [TIFF OMITTED] TR21SE98.007

where:

R = control efficiency of control device, percent
Ei = mass rate of total HAP at the inlet to the control 
device as calculated under paragraph (c)(1)(i) of this section, 
kilograms organic HAP per hour
Eo = mass rate of total HAP at the outlet of the control 
device, as calculated under paragraph (c)(1)(i) of this section, 
kilograms organic HAP per hour

    (iii) A performance test is not required to be conducted if the 
control device used to comply with Sec. 63.1253 (storage tank provisions) 
is also used to comply with Sec. 63.1254 (process vent provisions), and 
compliance with Sec. 63.1254 has been demonstrated in accordance with 
paragraph (d) of this section.
    (2) Design evaluation. If this option is chosen to demonstrate 
initial compliance with the percent reduction requirement of Sec. 
63.1253(b) or (c), a design evaluation shall be prepared in accordance 
with the provisions in paragraph (a)(1) of this section. The design 
evaluation shall include documentation demonstrating that the control 
device being used achieves the required control efficiency during 
reasonably expected maximum filling rate.
    (3) Floating roof. If the owner or operator of an affected source 
chooses to comply with the provisions of Sec. 63.1253(b) or (c) by 
installing a floating roof, the owner or operator shall comply with the 
procedures described in Secs. 63.119(b), (c), (d), and 63.120(a), (b), 
and (c), with the differences noted in paragraphs (c)(3)(i) through (v) 
of this section for the purposes of this subpart.
    (i) When the term ``storage vessel'' is used in Secs. 63.119 and 
63.120, the definition of ``storage tank'' in Sec. 63.1251 shall apply for 
the purposes of this subpart.
    (ii) When December 31, 1992 is referred to in Sec. 63.119, April 2, 
1997 shall

[[Page 129]]

apply instead for the purposes of this subpart.
    (iii) When April 22, 1994 is referred to in Sec. 63.119, September 21, 
1998 shall apply instead for the purposes of this subpart.
    (iv) When the phrase ``the compliance date specified in Sec. 63.100 of 
subpart F of this part'' is referred to in Sec. 63.120, the phrase ``the 
compliance date specified in Sec. 63.1250'' shall apply for the purposes of 
this subpart.
    (v) When the phrase ``the maximum true vapor pressure of the total 
organic HAP's in the stored liquid falls below the values defining Group 
1 storage vessels specified in table 5 or table 6 of this subpart'' is 
referred to in Sec. 63.120(b)(1)(iv), the phrase ``the maximum true vapor 
pressure of the total organic HAP in the stored liquid falls below 13.1 
kPa'' shall apply for the purposes of this subpart.
    (4) Initial compliance with alternative standard. Initial compliance 
with Sec. 63.1253(d) is demonstrated by fulfilling the requirements of 
paragraph (a)(5) of this section.
    (5) Planned maintenance. The owner or operator shall demonstrate 
compliance with the requirements of Sec. 63.1253(e) by including the 
periods of planned routine maintenance specified by date and time in 
each Periodic Report required by Sec. 63.1260.
    (d) Initial compliance with process vent provisions. An owner or 
operator of an affected source complying with the process vent standards 
in Sec. 63.1254 shall demonstrate compliance using the procedures described 
in paragraphs (d)(1) through (4) of this section.
    (1) Except as provided in paragraph (a)(4) of this section, initial 
compliance with the process vent standards in Sec. 63.1254 shall be 
demonstrated using the procedures specified in paragraphs (d)(1)(i) 
through (iv), as applicable.
    (i) Initial compliance with Sec. 63.1254(a)(2)(i) is demonstrated when 
the actual emissions of HAP from the sum of all process vents within a 
process is less than or equal to 900 kg/yr. Initial compliance with Sec. 
63.1254(a)(2)(ii) is demonstrated when the actual emissions of HAP from 
the sum of all process vents in compliance with Sec. 63.1254(a)(2)(i) is 
less than or equal to 1,800 kg/yr. Uncontrolled HAP emissions and 
controlled HAP emissions shall be determined using the procedures 
described in paragraphs (d)(2) and (3) of this section. Controlled 
emissions during periods of planned routine maintenance of a CCCD as 
specified in Sec. 63.1252(h), must be calculated assuming the HAP emissions 
are reduced by 93 percent.
    (ii) Initial compliance with the percent reduction requirements in Sec. 
63.1254(a)(1)(i), (a)(3), and (b) is demonstrated by:
    (A) Determining controlled HAP emissions using the procedures 
described in paragraph (d)(3) of this section, and uncontrolled HAP 
emissions determined using the procedures described in paragraph (d)(2) 
of this section, and demonstrating that the reductions required by Sec. 
63.1254(a)(1)(i), (a)(3), and (b) are met; or
    (B) Controlling the process vents using a device meeting the 
criteria specified in paragraph (a)(4) of this section.
    (iii) Initial compliance with the outlet concentration requirements 
in Sec. 63.1254(a)(1)(ii)(A), (a)(3), and (b)(1) is demonstrated when the 
outlet TOC concentration is 20 ppmv or less and the outlet hydrogen 
halide and halogen concentration is 20 ppmv or less. The owner or 
operator shall demonstrate compliance by fulfilling the requirements in 
paragraph (a)(6) of this section.
    (iv) Initial compliance with Sec. 63.1254(c) is demonstrated by 
fulfilling the requirements of paragraph (a)(5) of this section.
    (2) Uncontrolled emissions. An owner or operator of an affected 
source complying with the emission limitation required by Sec. 
63.1254(a)(1), or emissions reductions specified in Sec. 63.1254(a)(2), 
(a)(3), or (b), for each process vent within a process, shall calculate 
uncontrolled emissions from all equipment in the process according to 
the procedures described in paragraph (d)(2)(i) or (ii) of this section, 
as appropriate.
    (i) Emission estimation procedures. Owners or operators shall 
determine uncontrolled emissions of HAP using measurements and/or 
calculations for each batch emission episode within each unit operation 
according to the engineering evaluation methodology in

[[Page 130]]

paragraphs (d)(2)(i)(A) through (H) of this section. Except where 
variations are noted, individual HAP partial pressures in multicomponent 
systems shall be determined by the following methods: If the components 
are miscible in one another, use Raoult's law to calculate the partial 
pressures; if the solution is a dilute aqueous mixture, use Henry's law 
to calculate partial pressures; if Raoult's law or Henry's law are not 
appropriate or available, use experimentally obtained activity 
coefficients or models such as the group-contribution models, to predict 
activity coefficients, or assume the components of the system behave 
independently and use the summation of all vapor pressures from the HAP 
as the total HAP partial pressure. Chemical property data can be 
obtained from standard reference texts.
    (A) Vapor displacement. Emissions from vapor displacement due to 
transfer of material shall be calculated using Equation 11 of this 
subpart. The individual HAP partial pressures may be calculated using 
Raoult's law.
[GRAPHIC] [TIFF OMITTED] TR21SE98.008

where:

E = mass of HAP emitted
V = volume of gas displaced from the vessel
R = ideal gas law constant
T = temperature of the vessel vapor space; absolute
Pi = partial pressure of the individual HAP
MWi = molecular weight of the individual HAP
n = number of HAP compounds in the emission stream i = identifier for a 
HAP compound

    (B) Purging. Emissions from purging shall be calculated using 
Equation 12 of this subpart. The partial pressures of individual 
condensable compounds may be calculated using Raoult's law, the pressure 
of the vessel vapor space may be set equal to 760 mmHg, and the partial 
pressure of HAP shall be assumed to be 25 percent of the saturated value 
if the purge flow rate is greater than 100 standard cubic feet per 
minute (scfm).
[GRAPHIC] [TIFF OMITTED] TR21SE98.009

Where:
E = mass of HAP emitted
V = purge flow rate at the temperature and pressure of the vessel vapor 
space
R = ideal gas law constant
T = temperature of the vessel vapor space; absolute
Pi = partial pressure of the individual HAP
Pj = partial pressure of individual condensable VOC compounds 
(including HAP)
PT = pressure of the vessel vapor space
MWi = molecular weight of the individual HAP
t = time of purge
n = number of HAP compounds in the emission stream
i = identifier for a HAP compound
j = identifier for a condensable compound
m = number of condensable compounds (including HAP) in the emission 
stream

    (C) Heating. Emissions caused by the heating of a vessel to a 
temperature equal to or lower than 10 K below the boiling point shall be 
calculated using the procedures in either paragraph (d)(2)(i)(C)(1) or 
(3) of this section. Emissions caused by heating a vessel to a 
temperature that is higher than 10 K below the boiling point and less 
than the boiling point, must be calculated using the procedures in 
either paragraph (d)(2)(i)(C) (2) or (3) of this section. If the 
contents of a vessel are

[[Page 131]]

heated to the boiling point, emissions must be calculated using the 
procedures in paragraph (d)(2)(i)(C)(4) of this section.
    (1) This paragraph describes procedures to calculate emissions if 
the final temperature to which the vessel contents are heated is 10 K 
below the boiling point of the HAP in the vessel, or lower. The owner or 
operator shall calculate the mass of HAP emitted per episode using 
either Equation 13 or 14 of this subpart. The moles of noncondensable 
gas displaced are calculated using Equation 15 of this subpart. The 
initial and final pressure of the noncondensable gas in the vessel shall 
be calculated using Equation 16 of this subpart. The average molecular 
weight of HAP in the displaced gas shall be calculated using Equation 17 
of this subpart.
[GRAPHIC] [TIFF OMITTED] TR29AU00.004

[GRAPHIC] [TIFF OMITTED] TR21SE98.011

[GRAPHIC] [TIFF OMITTED] TR21SE98.012

[GRAPHIC] [TIFF OMITTED] TR21SE98.013

[GRAPHIC] [TIFF OMITTED] TR21SE98.014

Where:

E = mass of HAP vapor displaced from the vessel being heated
xi = mole fraction of each HAP in the liquid phase
xj = mole fraction of each condensable VOC (including HAP) in 
the liquid phase
Pi* = vapor pressure of each HAP in the vessel headspace at 
any temperature between the initial and final heatup temperatures, mmHg.
Pj* = vapor pressure of each condensable VOC (including HAP) 
in the vessel headspace at any temperature between the initial and final 
heatup temperatures, mmHg.
760 = atmospheric pressure, mmHg
MWHAP = the average molecular weight of HAP present in the 
displaced gas
[Delta][eta] = number of moles of noncondensable gas displaced
V = volume of free space in the vessel
R = ideal gas law constant
T1 = initial temperature of vessel contents, absolute
T2 = final temperature of vessel contents, absolute
Pan = partial pressure of noncondensable gas in the vessel 
headspace at

[[Page 132]]

initial (n=1) and final (n=2) temperature
Patm = atmospheric pressure (when [Delta][eta] is used in 
Equation 13 of this subpart, Patm may be set equal to 760 
mmHg for any vessel)
(Pj)Tn = partial pressure of each condensable 
compound (including HAP) in the vessel headspace at the initial 
temperature (n=1) and final (n=2) temperature
m = number of condensable compounds (including HAP) in the displaced 
vapor
j = identifier for a condensable compound
(Pi)Tn = partial pressure of each HAP in the 
vessel headspace at initial (T1) and final (T2) 
temperature
MWi = molecular weight of the individual HAP
n = number of HAP compounds in the emission stream
i = identifier for a HAP compound

    (2) If the vessel contents are heated to a temperature that is 
higher than 10 K below the boiling point and less than the boiling 
point, emissions must be calculated using the procedures in paragraph 
(d)(2)(i)(C)(2)(i), or (ii), or (iii) of this section.
    (i) Use Equation 13 of this subpart. In Equation 13 of this subpart, 
the HAP vapor pressures must be determined at the temperature 10 K below 
the boiling point. In the calculation of [Delta][eta] for Equation 13 of 
this subpart, T2 must be the temperature 10 K below the 
boiling point, and Pa2 must be determined at the temperature 
10 K below the boiling point.
    (ii) Use Equation 14 of this subpart. In Equation 14 of this 
subpart, the HAP partial pressures must be deter mined at the 
temperature 10 K below the boiling point. In the calculation of 
[Delta][eta] for Equation 14 of this subpart, T2 must be the 
temperature 10 K below the boiling point, and Pa2 must be 
determined at the temperature 10 K below the boiling point. In the 
calculation of MWHAP, the HAP partial pressures must be 
determined at the temperature 10 K below the boiling point.
    (iii) Use Equation 14 of this subpart over specific temperature 
increments. If the initial temperature is lower than 10 K below the 
boiling point, emissions must be calculated as the sum over two 
increments; one increment is from the initial temperature to 10 K below 
the boiling point, and the second is from 10 K below the boiling point 
to the lower of either the final temperature or the temperature 5 K 
below the boiling point. If the initial temperature is higher than 10 K 
below the boiling point, emissions are calculated over one increment 
from the initial temperature to the lower of either the final 
temperature or the temperature 5 K below the boiling point.
    (3)(i) Emissions caused by heating a vessel are calculated using 
Equation 18 of this subpart.
[GRAPHIC] [TIFF OMITTED] TR21SE98.015

Where:

E = mass of HAP vapor displaced from the vessel being heated
Navg = average gas space molar volume during the heating 
process
PT= total pressure in the vessel
Pi,1 = partial pressure of the individual HAP compounds at 
T1
Pi,2 = partial pressure of the individual HAP compounds at 
T2
MWHAP = average molecular weight of the HAP compounds
ni,1 = number of moles of condensable in the vessel headspace 
at T1
ni,2 = number of moles of condensable in the vessel headspace 
at T2

[[Page 133]]

n = number of HAP compounds in the emission stream

    (ii) The average gas space molar volume during the heating process 
is calculated using Equation 19 of this subpart.
[GRAPHIC] [TIFF OMITTED] TR21SE98.016

Where:

Navg = average gas space molar volume during the heating 
process
V = volume of free space in vessel
PT = total pressure in the vessel
R = ideal gas law constant
T1 = initial temperature of the vessel
T2 = final temperature of the vessel

    (iii) The difference in the number of moles of condensable in the 
vessel headspace between the initial and final temperatures is 
calculated using Equation 20 of this subpart.
[GRAPHIC] [TIFF OMITTED] TR21SE98.017

Where:

V = volume of free space in vessel
R = ideal gas law constant
T1 = initial temperature in the vessel
T2 = final temperature in the vessel
Pi,1 = partial pressure of the individual HAP compounds at 
T1
Pi,2 = partial pressure of the individual HAP compounds at 
T2
n = number of HAP compounds in the emission stream

    (4) If the vessel contents are heated to the boiling point, 
emissions must be calculated using the procedure in paragraphs 
(d)(2)(i)(C)(4)(i) and (ii) of this section.
    (i) Use either of the procedures in paragraph (d)(3)(i)(B)(3) of 
this section to calculate the emissions from heating to the boiling 
point (note that Pa2=0 in the calculation of; and
    (ii) While boiling, the vessel must be operated with a properly 
operated process condenser. An initial demonstration that a process 
condenser is properly operated is required for some process condensers, 
as described in paragraph (d)(3)(iii) of this section.
    (D) Depressurization. Emissions from depressurization shall be 
calculated using the procedures in either paragraphs (d)(2)(i)(D)(1) 
through (4), paragraphs (d)(2)(i)(D)(5) through (9), or paragraph 
(d)(2)(i)(D)(10) of this section.
    (1) Equations 21 and 22 of this subpart are used to calculate the 
initial and final volumes of noncondensable gas present in the vessel, 
adjusted to atmospheric pressure. The HAP partial pressures may be 
calculated using Raoult's law.
[GRAPHIC] [TIFF OMITTED] TR21SE98.018

[GRAPHIC] [TIFF OMITTED] TR21SE98.019

Where:

Vnc1 = initial volume of noncondensable gas in the vessel
Vnc2 = final volume of noncondensable gas in the vessel
V = free volume in the vessel being depressurized
Pnc1 = initial partial pressure of the noncondensable gas, as 
calculated using Equation 23 of this subpart, mmHg
Pnc2 = final partial pressure of the noncondensable gas, as 
calculated

[[Page 134]]

using Equation 24 of this subpart, mmHg
760 = atmospheric pressure, mmHg

    (2) The initial and final partial pressures of the noncondensable 
gas in the vessel are determined using Equations 23 and 24 of this 
subpart:
[GRAPHIC] [TIFF OMITTED] TR21SE98.020

[GRAPHIC] [TIFF OMITTED] TR21SE98.021

Where:
Pnc1 = initial partial pressure of the noncondensable gas
Pnc2 = final partial pressure of the noncondensable gas
P1 = initial vessel pressure
P2 = final vessel pressure
Pj* = vapor pressure of each condensable (including HAP) in 
the emission stream
xj = mole fraction of each condensable (including HAP) in the 
liquid phase
m = number of condensable compounds (including HAP) in the emission 
stream
j = identifier for a condensable compound

    (3) The average ratio of moles of noncondensable to moles of an 
individual HAP in the emission stream is calculated using Equation 25 of 
this subpart; this calculation must be repeated for each HAP in the 
emission stream:
[GRAPHIC] [TIFF OMITTED] TR29AU00.005

Where:

nRi = average ratio of moles of noncondensable to moles of 
individual HAP
Pnc1 = initial partial pressure of the noncondensable gas, as 
calculated using Equation 23 of this subpart
Pnc2 = final partial pressure of the noncondensable gas, as 
calculated using Equation 24 of this subpart
Pi* = vapor pressure of each individual HAP
xi = mole fraction of each individual HAP in the liquid 
phase.
n = number of HAP compounds
i = identifier for a HAP compound

    (4) The mass of HAP emitted shall be calculated using Equation 26 of 
this subpart:
[GRAPHIC] [TIFF OMITTED] TR29AU00.006

Where:

E = mass of HAP emitted
Vnc1 = initial volume of noncondensable gas in the vessel, as 
calculated using Equation 21 of this subpart
Vnc2 = final volume of noncondensable gas in the vessel, as 
calculated using Equation 22 of this subpart
nRi = average ratio of moles of noncondensable to moles of 
individual HAP, as calculated using Equation 25 of this subpart
Patm = atmospheric pressure, standard
R = ideal gas law constant
T = temperature of the vessel, absolute
MWi = molecular weight of each HAP

    (5) The moles of HAP vapor initially in the vessel are calculated 
using the ideal gas law using Equation 27 of this subpart:

[[Page 135]]

[GRAPHIC] [TIFF OMITTED] TR21SE98.024

Where:

YHAP = mole fraction of HAP (the sum of the individual HAP 
fractions, [Sigma]Yi)
V = free volume in the vessel being depressurized
P1 = initial vessel pressure
R = ideal gas law constant
T = vessel temperature, absolute

    (6) The initial and final moles of noncondensable gas present in the 
vessel are calculated using Equations 28 and 29 of this subpart:
[GRAPHIC] [TIFF OMITTED] TR21SE98.025

[GRAPHIC] [TIFF OMITTED] TR21SE98.026

Where:

n1 = initial number of moles of noncondensable gas in the 
vessel
n2 = final number of moles of noncondensable gas in the 
vessel
V = free volume in the vessel being depressurized
Pnc1 = initial partial pressure of the noncondensable gas, as 
calculated using Equation 23 of this subpart
Pnc2 = final partial pressure of the noncondensable gas, as 
calculated using Equation 24 of this subpart
R = ideal gas law constant
T = temperature, absolute

    (7) The initial and final partial pressures of the noncondensable 
gas in the vessel are determined using Equations 23 and 24 of this 
subpart.
    (8) The moles of HAP emitted during the depressurization are 
calculated by taking an approximation of the average ratio of moles of 
HAP to moles of noncondensable and multiplying by the total moles of 
noncondensables released during the depressurization, using Equation 30 
of this subpart:
where:
[GRAPHIC] [TIFF OMITTED] TR21SE98.027

nHAP = moles of HAP emitted
n1 = initial number of moles of noncondensable gas in the 
vessel, as calculated using Equation 28 of this subpart
n2 = final number of moles of noncondensable gas in the 
vessel, as calculated using Equation 29 of this subpart

    (9) The mass of HAP emitted can be calculated using Equation 31 of 
this subpart:

E=[eta]HAP * MWHAP    (Eq. 31)

where:
E = mass of HAP emitted
[eta]HAP = moles of HAP emitted, as calculated using Equation 
30 of this subpart
MWHAP = average molecular weight of the HAP as calculated 
using Equation 17 of this subpart

    (10) Emissions from depressurization may be calculated using 
equation 32 of this subpart:
[GRAPHIC] [TIFF OMITTED] TR02AU01.034


[[Page 136]]


Where:

V = free volume in vessel being depressurized
R = ideal gas law constant
T = temperature of the vessel, absolute
P1 = initial pressure in the vessel
P2 = final pressure in the vessel
Pj = partial pressure of the individual condensable compounds 
(including HAP)
MWi = molecular weight of the individual HAP compounds
n = number of HAP compounds in the emission stream
m = number of condensable compounds (including HAP) in the emission 
stream
i = identifier for a HAP compound
j = identifier for a condensable compound.

    (E) Vacuum systems. Emissions from vacuum systems may be calculated 
using Equation 33 of this subpart if the air leakage rate is known or 
can be approximated. The individual HAP partial pressures may be 
calculated using Raoult's Law.
[GRAPHIC] [TIFF OMITTED] TR29AU00.007

Where:

E = mass of HAP emitted
Psystem = absolute pressure of receiving vessel or ejector 
outlet conditions, if there is no receiver
Pi = partial pressure of the HAP at the receiver temperature 
or the ejector outlet conditions
Pj = partial pressure of condensable (including HAP) at the 
receiver temperature or the ejector outlet conditions
La = total air leak rate in the system, mass/time
MWnc = molecular weight of noncondensable gas
t = time of vacuum operation
MWi = molecular weight of the individual HAP in the emission 
stream, with HAP partial pressures calculated at the temperature of the 
receiver or ejector outlet, as appropriate

    (F) Gas evolution. Emissions from gas evolution shall be calculated 
using Equation 12 of this subpart with V calculated using Equation 34 of 
this subpart:
[GRAPHIC] [TIFF OMITTED] TR21SE98.030

Where:

V = volumetric flow rate of gas evolution
Wg = mass flow rate of gas evolution
R = ideal gas law constant
T = temperature at the exit, absolute
PT = vessel pressure
MWg = molecular weight of the evolved gas

    (G) Air drying. Emissions from air drying shall be calculated using 
Equation 35 of this subpart:

[[Page 137]]

[GRAPHIC] [TIFF OMITTED] TR21SE98.031

Where:

E = mass of HAP emitted
B = mass of dry solids
PS1 = HAP in material entering dryer, weight percent
PS2 = HAP in material exiting dryer, weight percent

    (H) Empty vessel purging. Emissions from empty vessel purging shall 
be calculated using Equation 36 of this subpart (Note: The term 
e-Ft/v can be assumed to be 0):
[GRAPHIC] [TIFF OMITTED] TR21SE98.032

Where:

V = volume of empty vessel
R = ideal gas law constant
T = temperature of the vessel vapor space; absolute
Pi = partial pressure of the individual HAP at the beginning 
of the purge
(MWi) = molecular weight of the individual HAP
F = flowrate of the purge gas
t = duration of the purge
n = number of HAP compounds in the emission stream
i = identifier for a HAP compound

    (ii) Engineering assessments. The owner or operator shall conduct an 
engineering assessment to calculate uncontrolled HAP emissions for each 
emission episode that is not due to vapor displacement, purging, 
heating, depressurization, vacuum operations, gas evolution, or air 
drying. For emission episodes caused by any of these types of 
activities, the owner or operator also may calculate uncontrolled HAP 
emissions based on an engineering assessment if the owner or operator 
can demonstrate to the Administrator that the methods in paragraph 
(d)(2)(i) of this section are not appropriate. Modified versions of the 
engineering evaluation methods in paragraphs (d)(2)(i)(A) through (H) 
may be used if the owner or operator demonstrates that they have been 
used to meet other regulatory obligations, and they do not affect 
applicability assessments or compliance determinations under this 
subpart GGG.One criterion the owner or operator could use to demonstrate 
that the methods in paragraph (d)(2)(i) of this section are not 
appropriate is if previous test data are available that show a greater 
than 20 percent discrepancy between the test value and the estimated 
value. An engineering assessment includes, but is not limited to, the 
following:
    (A) Previous test results, provided the tests are representative of 
current operating practices at the process unit.
    (B) Bench-scale or pilot-scale test data representative of the 
process under representative operating conditions.
    (C) Maximum flow rate, HAP emission rate, concentration, or other 
relevant parameter specified or implied within a permit limit applicable 
to the process vent.
    (D) Design analysis based on accepted chemical engineering 
principles, measurable process parameters, or physical or chemical laws 
or properties. Examples of analytical methods include, but are not 
limited to:
    (1) Use of material balances based on process stoichiometry to 
estimate maximum organic HAP concentrations.
    (2) Estimation of maximum flow rate based on physical equipment 
design such as pump or blower capacities.
    (3) Estimation of HAP concentrations based on saturation conditions.

[[Page 138]]

    (E) All data, assumptions, and procedures used in the engineering 
assessment shall be documented in accordance with Sec. 63.1260(e). Data or 
other information supporting a finding that the emissions estimation 
equations are inappropriate shall be reported in the Precompliance 
report.
    (3) Controlled emissions. An owner or operator shall determine 
controlled emissions using the procedures in either paragraph (d)(3)(i) 
or (ii) of this section.
    (i) Small control devices. Except for condensers, controlled 
emissions for each process vent that is controlled using a small control 
device shall be determined by using the design evaluation described in 
paragraph (d)(3)(i)(A) of this section, or conducting a performance test 
in accordance with paragraph (d)(3)(ii) of this section. Whenever a 
small control device becomes a large control device, the owner or 
operator must comply with the provisions in paragraph (d)(3)(ii) of this 
section and submit the test report in the next Periodic report.
    (A) Design evaluation. The design evaluation shall include 
documentation demonstrating that the control device being used achieves 
the required control efficiency under worst-case conditions, as 
determined from the emission profile described in Sec. 63.1257(b)(8)(ii). 
The control efficiency determined from this design evaluation shall be 
applied to uncontrolled emissions to estimate controlled emissions. The 
documentation must be conducted in accordance with the provisions in 
paragraph (a)(1) of this section. The design evaluation shall also 
include the value(s) and basis for the parameter(s) monitored under Sec. 
63.1258.
    (B) Emission estimation equations. An owner or operator using a 
condenser as a control device shall determine controlled emissions using 
exhaust gas temperature measurements and calculations for each batch 
emission episode within each unit operation according to the engineering 
methodology in paragraphs (d)(3)(i)(B)(1) through (8) of this section. 
Individual HAP partial pressures shall be calculated as specified in 
paragraph (d)(2)(i) of this section.
    (1) Emissions from vapor displacement shall be calculated using 
Equation 11 of this subpart with T set equal to the temperature of the 
receiver and the HAP partial pressures determined at the temperature of 
the receiver.
    (2) Emissions from purging shall be calculated using Equation 12 of 
this subpart with T set equal to the temperature of the receiver and the 
HAP partial pressures determined at the temperature of the receiver.
    (3) Emissions from heating shall be calculated using either Equation 
13 of this subpart or Equation 37 of this subpart. In Equation 13, the 
HAP vapor pressures shall be determined at the temperature of the 
receiver. In Equations 13 and 37 of this subpart, [Delta][eta] is equal 
to the number of moles of noncondensable displaced from the vessel, as 
calculated using Equation 15 of this subpart. In Equations 13 and 37 of 
this subpart, the HAP average molecular weight shall be calculated using 
Equation 17 with the HAP partial pressures determined at the temperature 
of the receiver.
[GRAPHIC] [TIFF OMITTED] TR21SE98.033

Where:

E = mass of HAP emitted
[Delta][eta] = moles of noncondensable gas displaced
PT = pressure in the receiver
Pi = partial pressure of the individual HAP at the receiver 
temperature
Pj = partial pressure of the individual condensable 
(including HAP) at the receiver temperature
n = number of HAP compounds in the emission stream
i = identifier for a HAP compound
MWHAP = the average molecular weight of HAP in vapor exiting 
the receiver, as calculated using Equation 17 of this subpart
m = number of condensable compounds (including HAP) in the emission 
stream
    (4)(i) Emissions from depressurization shall be calculated using 
Equation 38 of this subpart.

[[Page 139]]

[GRAPHIC] [TIFF OMITTED] TR21SE98.034

Where:

E = mass of HAP vapor emitted
Vnc1 = initial volume of noncondensable in the vessel, 
corrected to the final pressure, as calculated using Equation 39 of this 
subpart
Vnc2 = final volume of noncondensable in the vessel, as 
calculated using Equation 40 of this subpart
Pi = partial pressure of each individual HAP at the receiver 
temperature
Pj = partial pressure of each condensable (including HAP) at 
the receiver temperature
PT = receiver pressure
T = temperature of the receiver
R = ideal gas law constant
MWHAP = the average molecular weight of HAP calculated using 
Equation 17 of this subpart with partial pressures determined at the 
receiver temperature
i = identifier for a HAP compound
n = number of HAP compounds in the emission stream
m = number of condensable compounds (including HAP) in the emission 
stream
j = identifier for a condensable compound

    (ii) The initial and final volumes of noncondensable gas present in 
the vessel, adjusted to the pressure of the receiver, are calculated 
using Equations 39 and 40 of this subpart.
[GRAPHIC] [TIFF OMITTED] TR21SE98.035

[GRAPHIC] [TIFF OMITTED] TR21SE98.036

Where:

Vnc1 = initial volume of noncondensable gas in the vessel
Vnc2 = final volume of noncondensable gas in the vessel
V = free volume in the vessel being depressurized
Pnc1 = initial partial pressure of the noncondensable gas, as 
calculated using Equation 41 of this subpart
Pnc2 = final partial pressure of the noncondensable gas, as 
calculated using Equation 42 of this subpart
PT = pressure of the receiver

    (iii) Initial and final partial pressures of the noncondensable gas 
in the vessel are determined using Equations 41 and 42 of this subpart.
[GRAPHIC] [TIFF OMITTED] TR21SE98.037

[GRAPHIC] [TIFF OMITTED] TR21SE98.038

Where:

Pnc1 = initial partial pressure of the noncondensable gas in 
the vessel
Pnc2 = final partial pressure of the noncondensable gas in 
the vessel
P1 = initial vessel pressure
P2 = final vessel pressure
Pj = partial pressure of each condensable compound (including 
HAP) in the vessel
m = number of condensable compounds (including HAP) in the emission 
stream
j = identifier for a condensable compound

    (5) Emissions from vacuum systems shall be calculated using Equation 
33 of this subpart.
    (6) Emissions from gas evolution shall be calculated using Equation 
12 with V calculated using Equation 34 of this subpart, T set equal to 
the receiver temperature, and the HAP partial pressures determined at 
the receiver temperature. The term for time, t, in Equation 12 of this 
subpart is not

[[Page 140]]

needed for the purposes of this calculation.
    (7) Emissions from air drying shall be calculated using Equation 11 
of this subpart with V equal to the air flow rate and Pi 
determined at the receiver temperature.
    (8) Emissions from empty vessel purging shall be calculated using 
equation 43 of this subpart:
[GRAPHIC] [TIFF OMITTED] TR21SE98.039

Where:

V = volume of empty vessel
R = ideal gas law constant
T1 = temperature of the vessel vapor space at beginning of 
purge
T2 = temperature of the receiver, absolute
(Pi)T1 = partial pressure of the individual HAP at 
the beginning of the purge
(Pi)T2 = partial pressure of the individual HAP at 
the receiver temperature
MWi = molecular weight of the individual HAP
F = flowrate of the purge gas
t = duration of the purge
n = number of HAP compounds in the emission stream
i = identifier for a HAP compound

    (ii) Large control devices. Except for condensers, controlled 
emissions for each process vent that is controlled using a large control 
device shall be determined by applying the control efficiency of the 
large control device to the estimated uncontrolled emissions. The 
control efficiency shall be determined by conducting a performance test 
on the control device as described in paragraphs (d)(3)(ii)(A) through 
(C) of this section, or by using the results of a previous performance 
test as described in paragraph (d)(4) of this section. If the control 
device is intended to control only hydrogen halides and halogens, the 
owner or operator may assume the control efficiency of organic HAP is 
zero percent. If the control device is intended to control only organic 
HAP, the owner or operator may assume the control efficiency for 
hydrogen halides and halogen is zero percent. Owners and operators are 
not required to conduct performance tests for devices described in 
paragraphs (a)(4) and (d)(4) of this section that are large control 
devices, as defined in Sec. 63.1251.
    (A) The performance test shall be conducted by performing emission 
testing on the inlet and outlet of the control device following the test 
methods and procedures of Sec. 63.1257(b). Concentrations shall be 
calculated from the data obtained through emission testing according to 
the procedures in paragraph (a)(2) of this section.
    (B) Performance testing shall be conducted under absolute, or 
hypothetical worst-case conditions, as defined in paragraphs 
(b)(8)(i)(A) through (B) of this section.
    (C) The owner or operator may elect to conduct more than one 
performance test on the control device for the purpose of establishing 
more than one operating condition at which the control device achieves 
the required control efficiency.
    (iii) Initial compliance demonstration for condensers. (A) Air 
pollution control devices. During periods in which a condenser functions 
as an air pollution control device, controlled emissions shall be 
calculated using the emission estimation equations described in 
paragraph (d)(3)(i)(B) of this section.
    (B) Process condensers. During periods when the condenser is 
operating as a process condenser, the owner or operator is required to 
demonstrate that the process condenser is properly operated if the 
process condenser meets either of the criteria described in paragraphs 
(d)(3)(iii)(B)(1) and (2) of this

[[Page 141]]

section. The owner or operator must either measure the condenser exhaust 
gas temperature and show it is less than the boiling or bubble point of 
the substance(s) in the vessel, or perform a material balance around the 
vessel and condenser to show that at least 99 percent of the material 
vaporized while boiling is condensed. The initial demonstration shall be 
conducted for all appropriate operating scenarios and documented in the 
Notification of Compliance Status report described in Sec. 63.1260(f).
    (1) The process condenser is not followed by an air pollution 
control device; or
    (2) The air pollution control device following the process condenser 
is not a condenser or is not meeting the alternative standard of Sec. 
63.1254(c).
    (4) An owner or operator is not required to conduct a performance 
test for the following:
    (i) Any control device for which a previous performance test was 
conducted, provided the test was conducted using the same procedures 
specified in Sec. 63.1257(b) over conditions typical of the appropriate 
worst-case, as defined in Sec. 63.1257(b)(8)(i). The results of the 
previous performance test shall be used to demonstrate compliance.
    (e) Compliance with wastewater provisions. (1) Determining annual 
average concentration and annual load. To determine the annual average 
concentration and annual load of partially soluble and/or soluble HAP 
compounds in a wastewater stream, as required by Sec. 63.1256(a)(1), an 
owner or operator shall comply with the provisions in paragraphs 
(e)(1)(i) through (iii) of this section. A wastewater stream is exempt 
from the requirements of Sec. 63.1256(a)(2) if the owner or operator 
determines the annual average concentration and annual load are below 
all of the applicability cutoffs specified in Sec. 63.1256(a)(1)(i)(A) 
through (D). For annual average concentration, only initial rinses are 
included. Concentration measurements based on Method 305 shall be 
adjusted by dividing each concentration by the compound-specific Fm 
factor listed in Table 8 of this subpart. Concentration measurements 
based on methods other than Method 305 may not be adjusted by the 
compound-specific Fm factor listed in Table 8 of this subpart.
    (i) Annual average concentration definition. (A) When complying with 
Sec. 63.1256(a)(1)(i)(A), the annual average concentration means the total 
mass of partially soluble HAP compounds occurring in the wastewater 
stream during the calendar year divided by the total mass of the 
wastewater stream discharged during the same calendar year.
    (B) When complying with Sec. 63.1256(a)(1)(i) (B) or (C), the annual 
average concentration means the total mass of partially soluble and/or 
soluble HAP compounds occurring in the wastewater stream during the 
calendar year divided by the total mass of the wastewater stream 
discharged during the same calendar year.
    (C) When complying with Sec. 63.1256(a)(1)(i)(D), the annual average 
concentration means the total mass of soluble HAP compounds occurring in 
the wastewater stream during the calendar year divided by the total mass 
of the wastewater stream discharged during the same calendar year.
    (ii) Determination of annual average concentration. An owner or 
operator shall determine annual average concentrations of partially 
soluble and/or soluble HAP compounds in accordance with the provisions 
specified in paragraph (e)(1)(ii)(A), (B), or (C) of this section. The 
owner or operator may determine annual average concentrations by process 
simulation. Data and other information supporting the simulation shall 
be reported in the Precompliance Report for approval by the 
Administrator. The annual average concentration shall be determined 
either at the POD or downstream of the POD with adjustment for 
concentration changes made according to paragraph (e)(1)(ii)(D) of this 
section.
    (A) Test methods. The concentration of partially soluble HAP, 
soluble HAP, or total HAP shall be measured using any of the methods 
described in paragraphs (b)(10)(i) through (iv) of this section.
    (B) Knowledge of the wastewater stream. The concentration of 
partially soluble HAP, soluble HAP, or total HAP shall be calculated 
based on knowledge of the wastewater stream

[[Page 142]]

according to the procedures in paragraphs (e)(1)(ii)(B)(1) and (2) of 
this section. The owner or operator shall document concentrations in the 
Notification of Compliance Status report described in Sec. 63.1260(f).
    (1) Mass balance. The owner or operator shall calculate the 
concentrations of HAP compounds in wastewater considering the total 
quantity of HAP discharged to the water, the amount of water at the POD, 
and the amounts of water and solvent lost to other mechanisms such as 
reactions, air emissions, or uptake in product or other processing 
materials. The quantities of HAP and water shall be based on batch 
sheets, manufacturing tickets, or FDA bills of materials. In cases where 
a chemical reaction occurs that generates or consumes HAP, the amount of 
HAP remaining after a reaction shall be based on stoichometry assuming 
100 percent theoretical consumption or yield, as applicable.
    (2) Published water solubility data. For single components in water, 
owners and operators may use the water solubilities published in 
standard reference texts at the POD temperature to determine maximum HAP 
concentration.
    (C) Bench scale or pilot-scale test data. The concentration of 
partially soluble HAP, soluble HAP, or total HAP shall be calculated 
based on bench scale or pilot-scale test data. The owner or operator 
shall provide sufficient information to demonstrate that the bench-scale 
or pilot-scale test concentration data are representative of actual HAP 
concentrations. The owner or operator shall also provide documentation 
describing the testing protocol, and the means by which sample 
variability and analytical variability were accounted for in the 
determination of HAP concentrations. Documentation of the pilot-scale or 
bench scale analysis shall be provided in the precompliance report.
    (D) Adjustment for concentrations determined downstream of the POD. 
The owner or operator shall make corrections to the annual average 
concentration when the concentration is determined downstream of the POD 
at a location where: two or more wastewater streams have been mixed; one 
or more wastewater streams have been treated; or, losses to the 
atmosphere have occurred. The owner or operator shall make the 
adjustments either to the individual data points or to the final annual 
average concentration.
    (iii) Determination of annual load. An owner or operator shall 
calculate the partially soluble and/or soluble HAP load in a wastewater 
stream based on the annual average concentration determined in paragraph 
(e)(1)(ii) (A), (B), or (C) of this section and the total volume of the 
wastewater stream, based on knowledge of the wastewater stream in 
accordance with paragraphs (e)(1)(ii)(B) of this section. The owner or 
operator shall maintain records of the total liters of wastewater 
discharged per year as specified in Sec. 63.1259(b).
    (2) Compliance with treatment unit control provisions. (i) 
Performance tests and design evaluations-general. To comply with the 
control options in Sec. 63.1256(g) (10) or (13), neither a design 
evaluation nor a performance test is required. For any other 
nonbiological treatment process, the owner or operator shall conduct 
either a design evaluation as specified in paragraph (e)(2)(ii) of this 
section, or a performance test as specified in paragraph (e)(2)(iii) of 
this section to demonstrate that each nonbiological treatment process 
used to comply with Sec. 63.1256(g) (8), (9), and/or (12) achieves the 
conditions specified for compliance. The owner or operator shall 
demonstrate by the procedures in either paragraph (e)(2) (ii) or (iii) 
of this section that each closed biological treatment process used to 
comply with Sec. 63.1256 (g)(8)(ii), (g)(9)(ii), (g)(11), or (g)(12) 
achieves the conditions specified for compliance. If an open biological 
treatment unit is used to comply with Sec. 63.1256 (g)(8)(ii), (g)(9)(ii), 
(g)(11), or (g)(12), the owner or operator shall comply with the 
performance test requirements in paragraph (e)(2)(iii) of this section.
    (ii) Design evaluation. A design evaluation and supporting 
documentation that addresses the operating characteristics of the 
treatment process and that is based on operation at a wastewater stream 
flow rate and a concentration under which it would be

[[Page 143]]

most difficult to demonstrate compliance. For closed biological 
treatment processes, the percent reduction from removal/destruction in 
the treatment unit and control device shall be determined by a mass 
balance over the unit. The mass flow rate of soluble and/or partially 
soluble HAP compounds exiting the treatment process shall be the sum of 
the mass flow rate of soluble and/or partially soluble HAP compounds in 
the wastewater stream exiting the biological treatment process and the 
mass flow rate of the vented gas stream exiting the control device. The 
mass flow rate entering the treatment process minus the mass flow rate 
exiting the process determines the actual mass removal. Compounds that 
meet the requirements specified in paragraph (e)(2)(iii)(A)(4) of this 
section are not required to be included in the design evaluation; the 
term ``performance test'' in paragraph (e)(2)(iii)(A)(4) of this section 
shall mean ``design evaluation'' for the purposes of this paragraph.
    (iii) Performance tests. Performance tests shall be conducted using 
test methods and procedures that meet the applicable requirements 
specified in paragraphs (e)(2)(iii)(A) through (G) of this section.
    (A) General. This paragraph specifies the general procedures for 
performance tests that are conducted to demonstrate compliance of a 
treatment process with the control requirements specified in Sec. 
63.1256(g).
    (1) Representative process unit operating conditions. Compliance 
shall be demonstrated for representative operating conditions. 
Operations during periods of malfunction and periods of nonoperation 
shall not constitute representative conditions. The owner or operator 
shall record the process information that is necessary to document 
operating conditions during the test.
    (2) Representative treatment process operating conditions. 
Performance tests shall be conducted when the treatment process is 
operating at a representative inlet flow rate and concentration. If the 
treatment process will be operating at several different sets of 
representative operating conditions, the owner or operator shall comply 
with paragraphs (e)(2)(iii)(A)(2)(i) and (ii) of this section. The owner 
or operator shall record information that is necessary to document 
treatment process or control device operating conditions during the 
test.
    (i) Range of operating conditions. If the treatment process will be 
operated at several different sets of representative operating 
conditions, performance testing over the entire range is not required. 
In such cases, the performance test results shall be supplemented with 
modeling and/or engineering assessments to demonstrate performance over 
the operating range.
    (ii) Consideration of residence time. If concentration and/or flow 
rate to the treatment process are not relatively constant (i.e., 
comparison of inlet and outlet data will not be representative of 
performance), the owner or operator shall consider residence time, when 
determining concentration and flow rate.
    (3) Testing equipment. All testing equipment shall be prepared and 
installed as specified in the applicable test methods, or as approved by 
the Administrator.
    (4) Compounds not required to be considered in performance tests. 
Compounds that meet the requirements specified in (e)(2)(iii)(A)(4)(i), 
(ii), or (iii) of this section are not required to be included in the 
performance test. Concentration measurements based on Method 305 shall 
be adjusted by dividing each concentration by the compound-specific Fm 
factor listed in Table 8 of this subpart. Concentration measurements 
based on methods other than Method 305 shall not be adjusted by the 
compound-specific Fm factor listed in Table 8 of this subpart.
    (i) Compounds not used or produced by the PMPU; or
    (ii) Compounds with concentrations at the POD that are below 1 ppmw; 
or
    (iii) Compounds with concentrations at the POD that are below the 
lower detection limit where the lower detection limit is greater than 1 
ppmw. The method shall be an analytical method for wastewater which has 
the compound of interest as a target analyte.
    (5) Treatment using a series of treatment processes. In all cases 
where the wastewater provisions in this subpart allow or require the use 
of a treatment

[[Page 144]]

process to comply with emissions limitations, the owner or operator may 
use multiple treatment processes. The owner or operator complying with 
the requirements of Sec. 63.1256(g)(7)(i), when wastewater is conveyed by 
hard-piping, shall comply with either paragraph (e)(2)(iii)(A)(5)(i) or 
(ii) of this section. The owner or operator complying with the 
requirements of Sec. 63.1256(g)(7)(ii) shall comply with the requirements 
of paragraph (e)(2)(iii)(A)(5)(ii) of this section.
    (i) The owner or operator shall conduct the performance test across 
each series of treatment processes. For each series of treatment 
processes, inlet concentration and flow rate shall be measured either 
where the wastewater enters the first treatment process in a series of 
treatment processes, or prior to the first treatment process as 
specified in paragraph (e)(2)(iii)(A)(6) of this section. For each 
series of treatment processes, outlet concentration and flow rate shall 
be measured where the wastewater exits the last treatment process in the 
series of treatment processes, except when the last treatment process is 
an open or a closed aerobic biological treatment process demonstrating 
compliance by using the procedures in paragraphs (e)(2)(iii)(E) or (F) 
of this section. When the last treatment process is either an open or a 
closed aerobic biological treatment process demonstrating compliance by 
using the procedures in paragraphs (e)(2)(iii)(E) or (F) of this 
section, inlet and outlet concentrations and flow rates shall be 
measured at the inlet and outlet to the series of treatment processes 
prior to the biological treatment process and at the inlet to the 
biological treatment process, except as provided in paragraph 
(e)(2)(iii)(A)(6)(ii) of this section. The mass flow rate destroyed in 
the biological treatment process for which compliance is demonstrated 
using paragraph (e)(2)(iii)(E) or (F) of this section shall be added to 
the mass flow rate removed or destroyed in the series of treatment units 
before the biological treatment unit. This sum shall be used to 
calculate the overall control efficiency.
    (ii) The owner or operator shall conduct the performance test across 
each treatment process in the series of treatment processes. The mass 
flow rate removed or destroyed by each treatment process shall be added 
together and the overall control efficiency calculated to determine 
whether compliance has been demonstrated using paragraphs 
(e)(2)(iii)(C), (D), (E), (F), or (G) of this section, as applicable. If 
a biological treatment process is one of the treatment processes in the 
series of treatment processes, the inlet to the biological treatment 
process shall be the point at which the wastewater enters the biological 
treatment process, or the inlet to the equalization tank if all the 
criteria of paragraph (e)(2)(iii)(A)(6)(ii) of this section are met.
    (6) The owner or operator determining the inlet for purposes of 
demonstrating compliance with paragraph (e)(2)(iii)(E), or (F)of this 
section may elect to comply with paragraph (e)(2)(iii)(A)(6)(i) or (ii) 
of this section.
    (i) When wastewater is conveyed exclusively by hard-piping from the 
point of determination to a treatment process that is either the only 
treatment process or the first in a series of treatment processes (i.e., 
no treatment processes or other waste management units are used upstream 
of this treatment process to store, handle, or convey the wastewater), 
the inlet to the treatment process shall be at any location from the 
point of determination to where the wastewater stream enters the 
treatment process. When samples are taken upstream of the treatment 
process and before wastewater streams have converged, the owner or 
operator shall ensure that the mass flow rate of all affected wastewater 
is accounted for when using Sec. 63.1256(g)(8)(ii), (g)(9)(ii) or (g)(12) 
of this subpart to comply and that the mass flow rate of all wastewater, 
not just affected wastewater, is accounted for when using Sec. 
63.1256(g)(11) to comply, except as provided in paragraph 
(e)(2)(iii)(A)(4) of this section.
    (ii) The owner or operator may consider the inlet to the 
equalization tank as the inlet to the biological treatment process if 
the wastewater is conveyed by hard-piping from either the last previous 
treatment process or the point of determination to the equalization

[[Page 145]]

tank; or the wastewater is conveyed from the equalization tank 
exclusively by hard-piping to the biological treatment process and no 
treatment processes or other waste management units are used to store, 
handle, or convey the wastewater between the equalization tank and the 
biological treatment process; or the equalization tank is equipped with 
a fixed roof and a closed-vent system that routes emissions to a control 
device that meets the requirements of Sec. 63.1256(b)(1)(i) through (iv) 
and Sec. 63.1256(b)(2)(i). The outlet from the series of treatment 
processes prior to the biological treatment process is the point at 
which the wastewater exits the last treatment process in the series 
prior to the equalization tank, if the equalization tank and biological 
treatment process are part of a series of treatment processes. The owner 
or operator shall ensure that the mass flow rate of all affected 
wastewater is accounted for when using Sec. 63.1256(g)(9)(ii) or (12) to 
comply and that the mass flow rate of all wastewater, not just affected 
wastewater is accounted for when using Sec. 63.1256(g)(11) to comply, 
except as provided in paragraph (e)(2)(iii)(A)(4) of this section.
    (B) Noncombustion treatment process--concentration limits. This 
paragraph applies to performance tests that are conducted to demonstrate 
compliance of a noncombustion treatment process with the ppmw wastewater 
stream concentration limits at the outlet of the treatment process. This 
compliance option is specified in Sec. 63.1256(g)(8)(i) and (9)(i). 
Wastewater samples shall be collected using sampling procedures which 
minimize loss of organic compounds during sample collection and analysis 
and maintain sample integrity per paragraph (b)(10)(vi) of this section. 
Samples shall be collected and analyzed using the procedures specified 
in paragraphs (b)(10)(i) through (vi) of this section. Samples may be 
grab samples or composite samples. Samples shall be taken at 
approximately equally spaced time intervals over a 1-hour period. Each 
1-hour period constitutes a run, and the performance test shall consist 
of a minimum of three runs. Concentration measurements based on methods 
other than Method 305 may be adjusted by multiplying each concentration 
by the compound-specific Fm factor listed in Table 8 of this subpart. 
(For affected wastewater streams that contains both partially soluble 
and soluble HAP compounds, compliance is demonstrated only if the sum of 
the concentrations of partially soluble HAP compounds is less than 50 
ppmw, and the sum of the concentrations of soluble HAP compounds is less 
than 520 ppmw.)
    (C) Noncombustion, nonbiological treatment process: percent mass 
removal/destruction option. This paragraph applies to performance tests 
that are conducted to demonstrate compliance of a noncombustion, 
nonbiological treatment process with the percent mass removal limits 
specified in Sec. 63.1256(g)(8)(ii) and (9)(ii) for partially soluble and 
soluble HAP compounds, respectively. The owner or operator shall comply 
with the requirements specified in paragraphs (e)(2)(iii)(C)(1) through 
(5) of this section.
    (1) Concentration. The concentration of partially soluble and/or 
soluble HAP compounds entering and exiting the treatment process shall 
be determined as provided in this paragraph. Wastewater samples shall be 
collected using sampling procedures which minimize loss of organic 
compounds during sample collection and analysis and maintain sample 
integrity per paragraph (b)(10)(vi) of this section. The method shall be 
an analytical method for wastewater which has the compound of interest 
as a target analyte. Samples may be grab samples or composite samples. 
Samples shall be taken at approximately equally spaced time intervals 
over a 1-hour period. Each 1-hour period constitutes a run, and the 
performance test shall consist of a minimum of three runs. Concentration 
measurements based on Method 305 shall be adjusted by dividing each 
concentration by the compound-specific Fm factor listed in Table 8 of 
this subpart. Concentration measurements based on methods other than 
Method 305 shall not be adjusted by the compound-specific Fm factor 
listed in Table 8 of this subpart.
    (2) Flow rate. The flow rate of the entering and exiting wastewater 
streams shall be determined using inlet and outlet flow meters, 
respectively. Where

[[Page 146]]

the outlet flow is not greater than the inlet flow, a single flow meter 
may be used, and may be used at either the inlet or outlet. Flow rate 
measurements shall be taken at the same time as the concentration 
measurements.
    (3) Calculation of mass flow rate--for noncombustion, nonbiological 
treatment processes. The mass flow rates of partially soluble and/or 
soluble HAP compounds entering and exiting the treatment process are 
calculated using Equations 44 and 45 of this subpart.
[GRAPHIC] [TIFF OMITTED] TR21SE98.040

[GRAPHIC] [TIFF OMITTED] TR21SE98.041

Where:

QMWa, QMWb = mass flow rate of partially soluble 
or soluble HAP compounds, average of all runs, in wastewater entering 
(QMWa) or exiting (QMWb) the treatment process, 
kg/hr
[rho] = density of the wastewater, kg/m\3\
Qa,k, Qbb,k = volumetric flow rate of wastewater 
entering (Qa,k) or exiting (Qb,k) the treatment 
process during each run k, m3/hr
CT,a,k, CT,b,k = total concentration of partially 
soluble or soluble HAP compounds in wastewater entering 
(CT,a,k) or exiting (CT,b,k) the treatment process 
during each run k, ppmw
p = number of runs
k = identifier for a run
106 = conversion factor, mg/kg

    (4) Percent removal calculation for mass flow rate. The percent mass 
removal across the treatment process shall be calculated as follows:
[GRAPHIC] [TIFF OMITTED] TR21SE98.042

Where:

E = removal or destruction efficiency of the treatment process, percent
QMWa, QMWb = mass flow rate of partially soluble 
or soluble HAP compounds in wastewater entering (QMWa) and 
exiting (QMWb) the treatment process, kg/hr (as calculated 
using Equations 44 and 45 of this subpart)

    (5) Compare mass removal efficiency to required efficiency. Compare 
the mass removal efficiency (calculated in Equation 46 of this subpart) 
to the required efficiency as specified in Sec. 63.1256(g)(8)(ii) or 
(9)(ii). If complying with Sec. 63.1256(g)(8)(ii), compliance is 
demonstrated if the mass removal efficiency is 99 percent or greater. If 
complying with Sec. 63.1256(g)(9)(ii), compliance is demonstrated if the 
mass removal efficiency is 90 percent or greater.
    (D) Combustion treatment processes: percent mass removal/destruction 
option. This paragraph applies to performance tests that are conducted 
to demonstrate compliance of a combustion treatment process with the 
percent mass destruction limits specified in Sec. 63.1256(g)(8)(ii) for 
partially soluble HAP compounds, and/or Sec. 63.1256(g)(9)(ii) for soluble 
HAP compounds. The owner or operator shall comply with the requirements 
specified in paragraphs (e)(2)(iii)(D)(1) through (8) of this section.
    (1) Concentration in wastewater stream entering the combustion 
treatment process. The concentration of partially soluble and/or soluble 
HAP compounds entering the treatment process shall be determined as 
provided in this paragraph. Wastewater samples shall be collected using 
sampling procedures which minimize loss of organic compounds during 
sample collection and analysis and maintain sample integrity per 
paragraph (b)(10)(vi) of this section. The method shall be an analytical

[[Page 147]]

method for wastewater which has the compound of interest as a target 
analyte. Samples may be grab samples or composite samples. Samples shall 
be taken at approximately equally spaced time intervals over a 1-hour 
period. Each 1-hour period constitutes a run, and the performance test 
shall consist of a minimum of three runs. Concentration measurements 
based on Method 305 of appendix A of this part shall be adjusted by 
dividing each concentration by the compound-specific Fm factor listed in 
Table 8 of this subpart. Concentration measurements based on methods 
other than Method 305 shall not be adjusted by the compound-specific Fm 
factor listed in Table 8 of this subpart.
    (2) Flow rate of wastewater entering the combustion treatment 
process. The flow rate of the wastewater stream entering the combustion 
treatment process shall be determined using an inlet flow meter. Flow 
rate measurements shall be taken at the same time as the concentration 
measurements.
    (3) Calculation of mass flow rate in wastewater stream entering 
combustion treatment processes. The mass flow rate of partially soluble 
and/or soluble HAP compounds entering the treatment process is 
calculated as follows:
[GRAPHIC] [TIFF OMITTED] TR21SE98.043

Where:

QMWa = mass flow rate of partially soluble or soluble HAP 
compounds entering the combustion unit, kg/hr
[rho] = density of the wastewater stream, kg/m\3\
Qa,k = volumetric flow rate of wastewater entering the 
combustion unit during run k, m3/hr
CT,a,k = total concentration of partially soluble or soluble 
HAP compounds in the wastewater stream entering the combustion unit 
during run k, ppmw
k = identifier for a run
p = number of runs

    (4) Concentration in vented gas stream exiting the combustion 
treatment process. The concentration of partially soluble and/or soluble 
HAP compounds (or TOC) exiting the combustion treatment process in any 
vented gas stream shall be determined as provided in this paragraph. 
Samples may be grab samples or composite samples. Samples shall be taken 
at approximately equally spaced time intervals over a 1-hour period. 
Each 1-hour period constitutes a run, and the performance test shall 
consist of a minimum of three runs. Concentration measurements shall be 
determined using Method 18 of 40 CFR part 60, appendix A. Alternatively, 
any other test method validated according to the procedures in Method 
301 of appendix A of this part may be used.
    (5) Volumetric flow rate of vented gas stream exiting the combustion 
treatment process. The volumetric flow rate of the vented gas stream 
exiting the combustion treatment process shall be determined using 
Method 2, 2A, 2C, or 2D of 40 CFR part 60, appendix A, as appropriate. 
Volumetric flow rate measurements shall be taken at the same time as the 
concentration measurements.
    (6) Calculation of mass flow rate of vented gas stream exiting 
combustion treatment processes. The mass flow rate of partially soluble 
and/or soluble HAP compounds in a vented gas stream exiting the 
combustion treatment process shall be calculated as follows:
[GRAPHIC] [TIFF OMITTED] TR21SE98.044


[[Page 148]]


where:

QMGb = mass rate of TOC (minus methane and ethane) or total 
partially soluble and/or soluble HAP, in vented gas stream, exiting 
(QMGb) the combustion device, dry basis, kg/hr
CGb,i = concentration of TOC (minus methane and ethane) or 
total partially soluble and/or soluble HAP, in vented gas stream, 
exiting (CGb,i) the combustion device, dry basis, ppmv
MWi = molecular weight of a component, kilogram/kilogram-mole
QGb = flow rate of gas stream exiting (QGb) the 
combustion device, dry standard cubic meters per hour
K2 = constant, 41.57x10-9 (parts per 
million)-1 (gram-mole per standard cubic meter) (kilogram/
gram), where standard temperature (gram-mole per standard cubic meter) 
is 20 C
i = identifier for a compound
n = number of components in the sample

    (7) Destruction efficiency calculation. The destruction efficiency 
of the combustion unit for partially soluble and/or soluble HAP 
compounds shall be calculated as follows:
[GRAPHIC] [TIFF OMITTED] TR21SE98.045

Where:

E = destruction efficiency of partially soluble or soluble HAP compounds 
for the combustion unit, percent
QMW2a = mass flow rate of partially soluble or soluble HAP 
compounds entering the combustion unit, kg/hr
QMGb = mass flow rate of TOC (minus methane and ethane) or 
partially soluble and/or soluble HAP compounds in vented gas stream 
exiting the combustion treatment process, kg/hr
    (8) Compare mass destruction efficiency to required efficiency. 
Compare the mass destruction efficiency (calculated in Equation 49 of 
this subpart) to the required efficiency as specified in Sec. 
63.1256(g)(8)(ii) or (g)(9)(ii). If complying with Sec. 63.1256(g)(8)(ii), 
compliance is demonstrated if the mass destruction efficiency is 99 
percent or greater. If complying with Sec. 63.1256(g)(9)(ii), compliance is 
demonstrated if the mass destruction efficiency is 90 percent or 
greater.
    (E) Open or closed aerobic biological treatment processes: 95-
percent mass destruction option. This paragraph applies to performance 
tests that are conducted for open or closed aerobic biological treatment 
processes to demonstrate compliance with the 95-percent mass destruction 
provisions in Sec. 63.1256(g)(11) for partially soluble and/or soluble HAP 
compounds.
    (1) Concentration in wastewater stream. The concentration of 
partially soluble and/or soluble HAP as provided in this paragraph. 
Concentration measurements to determine E shall be taken as provided in 
paragraph (e)(2)(iii)(A)(5) of this section for a series of treatment 
processes. Wastewater samples shall be collected using sampling 
procedures which minimize loss of organic compounds during sample 
collection and analysis and maintain sample integrity per paragraph 
(b)(10)(vi) of this section. The method shall be an analytical method 
for wastewater which has the compound of interest as a target analyte. 
Samples may be grab samples or composite samples. Samples shall be taken 
at approximately equally spaced time intervals over a 1-hour period. 
Each 1-hour period constitutes a run, and the performance test shall 
consist of a minimum of three runs. Concentration measurements based on 
Method 305 shall be adjusted by dividing each concentration by the 
compound-specific Fm factor listed in Table 8 of this subpart. 
Concentration measurements based on methods other than Method 305 shall 
not be adjusted by the compound-specific Fm factor listed in Table 8 of 
this subpart.
    (2) Flow rate. Flow rate measurements to determine E shall be taken 
as provided in paragraph (e)(2)(iii)(A)(5) of this section for a series 
of treatment processes. Flow rate shall be determined using inlet and 
outlet flow measurement devices. Where the outlet flow is not greater 
than the inlet flow, a single flow measurement device may be used, and 
may be used at either the inlet or outlet. Flow rate measurements shall 
be taken at the same time as the concentration measurements.

[[Page 149]]

    (3) Destruction efficiency. The owner or operator shall comply with 
the provisions in either paragraph (e)(2)(iii)(E)(3)(i) or (ii) of this 
section. Compliance is demonstrated if the destruction efficiency, E, is 
equal to or greater than 95 percent.
    (i) If the performance test is performed across the open or closed 
biological treatment system only, compliance is demonstrated if E is 
equal to Fbio, where E is the destruction efficiency of 
partially soluble and/or soluble HAP compounds and Fbio is 
the site-specific fraction of partially soluble and/or soluble HAP 
compounds biodegraded. Fbio shall be determined as specified 
in paragraph (e)(2)(iii)(E)(4) of this section and appendix C of subpart 
G of this part.
    (ii) If compliance is being demonstrated in accordance with 
paragraphs (e)(2)(iii)(A)(5)(i) or (ii) of this section, the removal 
efficiency shall be calculated using Equation 50 of this subpart. When 
complying with paragraph (e)(2)(iii)(A)(5)(i) of this section, the 
series of nonbiological treatment processes comprise one treatment 
process segment. When complying with paragraph (e)(2)(iii)(A)(5)(ii) of 
this section, each nonbiological treatment process is a treatment 
process segment.
[GRAPHIC] [TIFF OMITTED] TR21SE98.046

Where:

QMWa,i = the soluble and/or partially soluble HAP load 
entering a treatment process segment
QMWb,i = the soluble and/or partially soluble HAP load 
exiting a treatment process segment
n = the number of treatment process segments
i = identifier for a treatment process element
QMWbio = the inlet load of soluble and/or partially soluble 
HAP to the biological treatment process. The inlet is defined in 
accordance with paragraph (e)(2)(iii)(A)(6) of this section. If 
complying with paragraph (e)(2)(iii)(A)(6)(ii) of this section, 
QMWbio is equal to QMWb,n
Fbio = site-specific fraction of soluble and/or partially 
soluble HAP compounds biodegraded. Fbio shall be determined 
as specified in paragraph (e)(2)(iii)(E)(4) of this section and Appendix 
C of subpart G of this part.
QMWall = the total soluble and/or partially soluble HAP load 
to be treated.

    (4) Site-specific fraction biodegraded (Fbio). The 
procedures used to determine the compound-specific kinetic parameters 
for use in calculating Fbio differ for the compounds listed 
in Tables 2 and 3 of this subpart. An owner or operator shall calculate 
Fbio as specified in either paragraph (e)(2)(iii)(E)(4)(i) or 
(ii) of this section.
    (i) For biological treatment processes that do not meet the 
definition for enhanced biological treatment in Sec. 63.1251, the owner or 
operator shall determine the Fbio for the compounds in Tables 
2 and 3 of this subpart using any of the procedures in appendix C to 
part 63, except procedure 3 (inlet and outlet concentration 
measurements). (The symbol ``Fbio'' represents the site-
specific fraction of an individual partially soluble or soluble HAP 
compound that is biodegraded.)
    (ii) If the biological treatment process meets the definition of 
``enhanced biological treatment process'' in Sec. 63.1251, the owner or 
operator shall determine Fbio for the compounds in Table 2 of 
this subpart using any of the procedures specified in appendix C to part 
63. The owner or operator shall calculate Fbio for the 
compounds in Table 3 of this subpart using the defaults for first order 
biodegradation rate constants (K1) in Table 9 of this subpart 
and follow the procedure explained in Form III of appendix C, 40 CFR 
part 63, or any of the procedures specified in appendix C of 40 CFR part 
63.

[[Page 150]]

    (F) Open or closed aerobic biological treatment processes: percent 
removal for partially soluble or soluble HAP compounds. This paragraph 
applies to the use of performance tests that are conducted for open or 
closed aerobic biological treatment processes to demonstrate compliance 
with the percent removal provisions for either partially soluble HAP 
compounds in Sec. 63.1256(g)(8)(ii) or soluble HAP compounds in Sec. 
63.1256(g)(9)(ii) or (g)(12). The owner or operator shall comply with 
the provisions in paragraph (e)(2)(iii)(E) of this section, except that 
compliance with Sec. 63.1256(g)(8)(ii) shall be demonstrated when E is 
equal to or greater than 99 percent, compliance with Sec. 63.1256(g)(9)(ii) 
shall be demonstrated when E is equal to or greater than 90 percent, and 
compliance with Sec. 63.1256(g)(12) shall be demonstrated when E is equal 
to or greater than 99 percent.
    (G) Closed biological treatment processes: percent mass removal 
option. This paragraph applies to the use of performance tests that are 
conducted for closed biological treatment processes to demonstrate 
compliance with the percent removal provisions in 
Secs. 63.1256(g)(8)(ii), (g)(9)(ii), (g)(11), or (g)(12). The owner or 
operator shall comply with the requirements specified in paragraphs 
(e)(2)(iii)(G) (1) through (4) of this section.
    (1) Comply with the procedures specified in paragraphs 
(e)(2)(iii)(C) (1) through (3) of this section to determine 
characteristics of the wastewater entering the biological treatment 
unit, except that the term ``partially soluble and/or soluble HAP'' 
shall mean ``soluble HAP'' for the purposes of this section if the owner 
or operator is complying with Sec. 63.1256(g)(9)(ii) or (g)(12), and it 
shall mean ``partially soluble HAP'' if the owner or operator is 
complying with Sec. 63.1256(g)(8)(ii).
    (2) Comply with the procedures specified in paragraphs 
(e)(2)(iii)(D) (4) through (6) of this section to determine the 
characteristics of gas vent streams exiting a control device, with the 
differences noted in paragraphs (e)(2)(iii)(G)(3) (i) and (ii) of this 
section.
    (i) The term ``partially soluble and/or soluble HAP'' shall mean 
``soluble HAP'' for the purposes of this section if the owner or 
operator is complying with Sec. 63.1256(g)(9)(ii) or (g)(12), and it shall 
mean ``partially soluble HAP'' if the owner or operator is complying 
with Sec. 63.1256(g)(8)(ii).
    (ii) The term ``combustion treatment process'' shall mean ``control 
device'' for the purposes of this section.
    (3) Percent removal/destruction calculation. The percent removal and 
destruction across the treatment unit and any control device(s) shall be 
calculated using Equation 51 of this subpart:
[GRAPHIC] [TIFF OMITTED] TR21SE98.047

Where:

E = removal and destruction efficiency of the treatment unit and control 
device(s), percent
QMWa, QMWb = mass flow rate of partially soluble 
and/or soluble HAP compounds in wastewater entering (QMWa) 
and exiting (QMWb) the treatment process, kilograms per hour 
(as calculated using Equations 44 and 45)
QMGb = mass flow rate of partially soluble and/or soluble HAP 
compounds in vented gas stream exiting the control device, kg/hr

    (4) Compare mass removal/destruction efficiency to required 
efficiency. Compare the mass removal/destruction efficiency (calculated 
using Equation 51 of this subpart) to the required efficiency as 
specified in Sec. 63.1256(g)(8)(ii), (g)(9)(ii), (g)(11), or (g)(12). If 
complying with Sec. 63.1256(g)(8)(ii), compliance is demonstrated if the 
mass removal/destruction is 99 percent or greater. If

[[Page 151]]

complying with Sec. 63.1256(g)(9)(ii), compliance is demonstrated if the 
mass removal/destruction efficiency is 90 percent or greater. If 
complying with Sec. 63.1256(g)(11), compliance is demonstrated if the mass 
removal/destruction efficiency is 95 percent or greater. If complying 
with Sec. 63.1256(g)(12), compliance is demonstrated if the mass removal/
destruction efficiency is 99 percent or greater.
    (3) Compliance with control device provisions. Except as provided in 
paragraph (e)(3)(iv) of this section, an owner or operator shall 
demonstrate that each control device or combination of control devices 
achieves the appropriate conditions specified in Sec. 63.1256(h)(2) by 
using one or more of the methods specified in paragraphs (e)(3)(i), 
(ii), or (iii) of this section.
    (i) Performance test for control devices other than flares. This 
paragraph applies to performance tests that are conducted to demonstrate 
compliance of a control device with the efficiency limits specified in Sec. 
63.1256(h)(2). If complying with the 95-percent reduction efficiency 
requirement, comply with the requirements specified in paragraphs 
(e)(3)(i) (A) through (J) of this section. If complying with the 20 ppm 
by volume requirement, comply with the requirements specified in 
paragraphs (e)(3)(i) (A) through (G) and (e)(3)(i)(J) of this section.
    (A) General. The owner or operator shall comply with the general 
performance test provisions in paragraphs (e)(2)(iii)(A) (1) through (4) 
of this section, except that the term ``treatment unit'' shall mean 
``control device'' for the purposes of this section.
    (B) Sampling sites. Sampling sites shall be selected using Method 1 
or 1A of 40 CFR part 60, appendix A, as appropriate. For determination 
of compliance with the 95 percent reduction requirement, sampling sites 
shall be located at the inlet and the outlet of the control device. For 
determination of compliance with the 20 ppmv limit, the sampling site 
shall be located at the outlet of the control device.
    (C) Concentration in gas stream entering or exiting the control 
device. The concentration of total organic HAP or TOC in a gas stream 
shall be determined as provided in this paragraph. Samples may be grab 
samples or composite samples (i.e., integrated samples). Samples shall 
be taken at approximately equally spaced time intervals over a 1-hour 
period. Each 1-hour period constitutes a run, and the performance test 
shall consist of a minimum of three runs. Concentration measurements 
shall be determined using Method 18 of 40 CFR part 60, appendix A. 
Alternatively, any other test method validated according to the 
procedures in Method 301 of appendix A of this part may be used.
    (D) Volumetric flow rate of gas stream entering or exiting the 
control device. The volumetric flow rate of the gas stream shall be 
determined using Method 2, 2A, 2C, or 2D of 40 CFR part 60, appendix A, 
as appropriate. Volumetric flow rate measurements shall be taken at the 
same time as the concentration measurements.
    (E) Calculation of TOC concentration. The owner or operator shall 
compute TOC in accordance with the procedures in paragraph (a)(2) of 
this section.
    (F) Calculation of total organic HAP concentration. The owner or 
operator determining compliance based on total organic HAP concentration 
shall compute the total organic HAP concentration in accordance with the 
provisions in paragraph (a)(2) of this section.
    (G) Requirements for combustion control devices. If the control 
device is a combustion device, the owner or operator shall correct TOC 
and organic HAP concentrations to 3 percent oxygen in accordance with 
the provisions in paragraph (a)(3) of this section, and demonstrate 
initial compliance with the requirements for halogenated streams in 
accordance with paragraph (a)(6) of this section.
    (H) Mass rate calculation. The mass rate of either TOC (minus 
methane and ethane) or total organic HAP for each sample run shall be 
calculated using the following equations. Where the mass rate of TOC is 
being calculated, all organic compounds (minus methane and ethane) 
measured by methods specified in paragraph (e)(3)(i)(C) of this section 
are summed using Equations 52 and 53 of this subpart. Where the mass 
rate of total organic HAP is being calculated, only soluble and 
partially

[[Page 152]]

soluble HAP compounds shall be summed using Equations 52 and 53.
[GRAPHIC] [TIFF OMITTED] TR21SE98.048

[GRAPHIC] [TIFF OMITTED] TR21SE98.049

Where:

CGa,i, CGb,i = concentration of TOC or total 
organic HAP, in vented gas stream, entering (CGa,i) and 
exiting (CGb,i) the control device, dry basis, ppmv
QMGa, QMGb = mass rate of TOC or total organic 
HAP, in vented gas stream, entering (QMGa) and exiting 
(QMGb) the control device, dry basis, kg/hr
Mwi = molecular weight of a component, kilogram/kilogram-mole
QGa,QGb = flow rate of gas stream entering 
(QGa) and exiting (QGb) the control device, dry 
standard cubic meters per hour
K2 = constant, 41.57 x 10-9 (parts per 
million)-1 (gram-mole per standard cubic meter) (kilogram/
gram), where standard temperature (gram-mole per standard cubic meter) 
is 20 C
i = identifier for a compound
n = number of components in the sample

    (I) Percent reduction calculation. The percent reduction in TOC or 
total organic HAP for each sample run shall be calculated using Equation 
54 of this subpart:
[GRAPHIC] [TIFF OMITTED] TR21SE98.050

where:

E = destruction efficiency of control device, percent
QMGa,QMGb = mass rate of TOC or total organic HAP, 
in vented gas stream entering and exiting (QMGb) the control 
device, dry basis, kilograms per hour

    (J) Compare mass destruction efficiency to required efficiency. If 
complying with the 95-percent reduction efficiency requirement, 
compliance is demonstrated if the mass destruction efficiency 
(calculated in Equation 51 of this subpart) is 95 percent or greater. If 
complying with the 20 ppmv limit, compliance is demonstrated if the 
outlet TOC concentration is 20 ppmv, or less.
    (ii) Design evaluation. A design evaluation conducted in accordance 
with the provisions in paragraph (a)(1) of this section. Compounds that 
meet the requirements specified in paragraph (e)(2)(iii)(A)(4) of this 
section are not required to be included in the design evaluation.
    (iii) Compliance demonstration for flares. When a flare is used to 
comply with Sec. 63.1256(h), the owner or operator shall comply with the 
flare provisions in Sec. 63.11(b). An owner or operator is not required to 
conduct a performance test to determine percent emission reduction or 
outlet organic HAP or TOC concentration when a flare is used.
    (iv) Exemptions from compliance demonstrations. An owner or operator 
using any control device specified in paragraph (a)(4) of this section 
is exempt from the requirements in paragraphs (e)(3)(i) through 
(e)(3)(iii) of this section and from the requirements in Sec. 63.6(f).
    (f) Pollution prevention alternative standard. The owner or operator 
shall demonstrate compliance with Sec. 63.1252(e)(2) using the procedures 
described in paragraph (f)(1) and (f)(3) of this section. The owner or 
operator shall demonstrate compliance with Sec. 63.1252(e)(3) using the 
procedures described in paragraphs (f)(2) and (f)(3) of this section.

[[Page 153]]

    (1) Compliance is demonstrated when the annual kg/kg factor, 
calculated according to the procedure in paragraphs (f)(1)(i) and (iii) 
of this section, is reduced by at least 75 percent as calculated 
according to the procedure in paragraph (f)(1)(i) and (ii) of this 
section.
    (i) The production-indexed HAP consumption factors shall be 
calculated by dividing annual consumption of total HAP by the annual 
production rate, per process. The production-indexed total VOC 
consumption factor shall be calculated by dividing annual consumption of 
total VOC by the annual production rate, per process.
    (ii) The baseline factor is calculated from yearly production and 
consumption data for the first 3-year period in which the PMPU was 
operational, beginning no earlier than the 1987 calendar year, or for a 
minimum period of 12 months from startup of the process until the 
present in which the PMPU was operational and data are available, 
beginning no earlier than the 1987 calendar year.
    (iii) The annual factor is calculated on the following bases:
    (A) For continuous processes, the annual factor shall be calculated 
every 30 days for the 12-month period preceding the 30th day (30-day 
rolling average).
    (B) For batch processes, the annual factor shall be calculated 
either every 10 batches for the 12-month period preceding the 10th batch 
(10-batch rolling average) or a maximum of once per month, if the number 
of batches is greater than 10 batches per month. The annual factor shall 
be calculated every 5 batches if the number of batches is less than 10 
for the 12-month period preceding the 10th batch and shall be calculated 
every year if the number of batches is less than 5 for the 12-month 
period preceding the 5th batch.
    (2) Compliance is demonstrated when the requirements of paragraphs 
(f)(2)(i) through (iv) of this section are met.
    (i) The annual kg/kg factor, calculated according to the procedure 
in paragraphs (f)(1)(i) and (f)(1)(iii) of this section, is reduced to a 
value equal to or less than 50 percent of the baseline factor calculated 
according to the procedure in paragraphs (f)(1)(i) and (ii) of this 
section.
    (ii) The yearly reductions associated with add-on controls that meet 
the criteria of Secs. 63.1252(h)(3)(ii)(A) through (D) must be equal to 
or greater than the amounts calculated in paragraphs (f)(2)(ii)(A) and 
(B) of this section:
    (A) The mass of HAP calculated using Equation 55 of this subpart:
    [GRAPHIC] [TIFF OMITTED] TR29AU00.008
    
Where:

[kg/kg]b = the baseline production-indexed HAP consumption 
factor, in kg/kg
Mprod = the annual production rate, in kg/yr
M = the annual reduction required by add-on controls, in kg/yr
PR = the fractional reduction in the annual kg/kg factor 
achieved using pollution prevention where PR is [ge]0.5

    (B) The mass of VOC calculated using Equation 56 of this subpart:

VOC reduced = (VFbase - VFP - 
VFannual) x Mprod    (Eq. 56)

Where:

VOCreduced = required VOC emission reduction from add-on 
controls, kg/yr
VFbase = baseline VOC factor, kg VOC emitted/kg production
VFp = reduction in VOC factor achieved by pollution 
prevention, kg VOC emitted/kg production
VFannual = target annual VOC factor, kg VOC emitted/kg 
production
Mprod = production rate, kg/yr

    (iii) Demonstration that the criteria in Sec. 63.1252(e)(3)(ii)(A) 
through (D) are met shall be accomplished through a description of the 
control device and of the material streams entering and exiting the 
control device.

[[Page 154]]

    (iv) The annual reduction achieved by the add-on control shall be 
quantified using the methods described in Sec. 63.1257(d).
    (3) Each owner or operator of a PMPU complying with the P2 standard 
shall prepare a P2 demonstration summary that shall contain, at a 
minimum, the following information:
    (i) Descriptions of the methodologies and forms used to measure and 
record daily consumption of HAP compounds reduced as part of the P2 
standard.
    (ii) Descriptions of the methodologies and forms used to measure and 
record daily production of products which are included in the P2 
standard.
    (iii) Supporting documentation for the descriptions provided in 
paragraphs (f)(3)(i) and (ii) including, but not limited to, operator 
log sheets and copies of daily, monthly, and annual inventories of 
materials and products.
    (g) Compliance with storage tank provisions by using emissions 
averaging. An owner or operator with two or more affected storage tanks 
may demonstrate compliance with Sec. 63.1253, as applicable, by fulfilling 
the requirements of paragraphs (g)(1) through (4) of this section.
    (1) The owner or operator shall develop and submit for approval an 
Implementation Plan containing all the information required in Sec. 
63.1259(e) 6 months prior to the compliance date of the standard. The 
Administrator shall have 90 days to approve or disapprove the emissions 
averaging plan after which time the plan shall be considered approved.
    (2) The annual mass rate of total organic HAP (ETi, 
ETo) shall be calculated for each storage tank included in 
the emissions average using the procedures specified in paragraph 
(c)(1), (2), or (3) of this section.
    (3) Equations 57 and 58 of this subpart shall be used to calculate 
total HAP emissions for those tanks subject to Sec. 63.1253(b) or (c):
[GRAPHIC] [TIFF OMITTED] TR21SE98.051

[GRAPHIC] [TIFF OMITTED] TR21SE98.052

Where:

Eij = yearly mass rate of total HAP at the inlet of the 
control device for tank j
Eoj = yearly mass rate of total HAP at the outlet of the 
control device for tank j
ETi = total yearly uncontrolled HAP emissions
ETo = total yearly actual HAP emissions
n = number of tanks included in the emissions average

    (4) The overall percent reduction efficiency shall be calculated as 
follows:
[GRAPHIC] [TIFF OMITTED] TR21SE98.053

where:

R = overall percent reduction efficiency
D = discount factor = 1.1 for all controlled storage tanks

    (h) Compliance with process vent provisions by using emissions 
averaging. An owner or operator with two or more affected processes 
complying with Sec. 63.1254 by using emissions averaging shall demonstrate 
compliance with paragraphs (h)(1), (2) and (3) of this section.
    (1) The owner or operator shall develop and submit for approval an 
Implementation Plan at least 6 months prior to the compliance date of 
the standard containing all the information required in Sec. 63.1259(e). 
The Administrator shall have 90 days to approve or disapprove the 
emissions averaging plan. The plan shall be considered approved if the 
Administrator either approves the plan in writing, or fails to 
disapprove the plan in writing. The 90-day period shall begin when the 
Administrator receives the request. If the request is denied, the owner 
or operator must still be in compliance with the standard by the 
compliance date.
    (2) Owners or operators shall calculate uncontrolled and controlled 
emissions of HAP by using the methods specified in paragraph (d)(2) and 
(3) of this section for each process included in the emissions average.
    (3) Equations 60 and 61 of this subpart shall be used to calculate 
total HAP emissions:

[[Page 155]]

[GRAPHIC] [TIFF OMITTED] TR29AU00.009

[GRAPHIC] [TIFF OMITTED] TR29AU00.010

Where:

EUi = yearly uncontrolled emissions from process i.
ECi = yearly actual emissions for process i.
ETU = total yearly uncontrolled emissions.
ETC = total yearly actual emissions.
n = number of processes included in the emissions average.

    (4) The overall percent reduction efficiency shall be calculated 
using Equation 62 of this subpart:
[GRAPHIC] [TIFF OMITTED] TR21SE98.056

where:

R = overall percent reduction efficiency
D = discount factor = 1.1 for all controlled emission points

[63 FR 50326, Sept. 21, 1998, as amended at 65 FR 52609, Aug. 29, 2000; 
66 FR 40134, Aug. 2, 2001]