[Code of Federal Regulations]
[Title 40, Volume 18]
[Revised as of July 1, 2003]
From the U.S. Government Printing Office via GPO Access
[CITE: 40CFR92.114]
[Page 433-442]
TITLE 40--PROTECTION OF ENVIRONMENT
CHAPTER I--ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)
PART 92--CONTROL OF AIR POLLUTION FROM LOCOMOTIVES AND LOCOMOTIVE ENGINES--
Table of Contents
Subpart B--Test Procedures
Sec. 92.114 Exhaust gas and particulate sampling and analytical system.
(a) General. (1) During emission testing, the engine exhaust is
routed through an exhaust duct connected to, or otherwise adjacent to
the outlet of the locomotive exhaust system. Emission samples are
collected as specified in paragraphs (b) and (c) of this section.
Exhaust duct requirements are specified in paragraph (d) of this
section.
(2) The systems described in this section are appropriate for use
with locomotives or engines employing a single exhaust.
(i) For testing where the locomotive or engine has multiple exhausts
all exhaust streams shall be combined into a single stream prior to
sampling, except as allowed by paragraph (a)(2)(ii) of this section.
(ii) For locomotive testing where the locomotive has multiple
exhaust stacks, proportional samples may be collected from each exhaust
outlet instead of ducting the exhaust stacks together, provided that the
CO2 concentrations in each exhaust stream are shown (either
prior to testing or during testing) to be within 5 percent of each other
for each test mode.
(3) All vents, including analyzer vents, bypass flow, and pressure
relief vents of regulators, should be vented in such a manner to avoid
endangering personnel in the immediate area.
(4) Additional components, not specified here, such as instruments,
valves, solenoids, pumps, switches, and so forth, may be employed to
provide additional information and coordinate the functions of the
component systems, provided that their use is consistent with good
engineering practice. Any variation from the specifications in this
subpart including performance specifications and emission detection
methods may be used only with prior approval by the Administrator.
(b) Raw exhaust sampling for gaseous emissions. (1)(i) An example of
the type of sampling and analytical system which is to be used for
gaseous emissions testing under this subpart is shown in Figure B114-1
of this section. All components or parts of components that are wetted
by the sample or corrosive calibration gases shall be either chemically
cleaned stainless steel or other inert material, for example,
polytetrafluoroethylene resin. The use of ``gauge savers'' or
``protectors'' with nonreactive diaphragms to reduce dead volumes is
permitted. Additional components such as instruments, valves, solenoids,
pumps, switches, etc. may be employed to provide additional information
and coordinate the functions of the component systems.
[[Page 434]]
(ii) System components list. The following is a list of components
shown in Figure B114-1 of this section by numeric identifier.
(A) Filters. Glass fiber filter paper is permitted for the fine
particulate filters (F1, F2, and F3). Optional filter F4 is a coarse
filter for large particulates. Filters F3 and F4 are heated filters
(B) Flowmeters. Flowmeters FL1 and FL2 indicate sample flow rates
through the CO and CO2 analyzers. Flowmeters FL3, FL4, FL5,
and FL6 indicate bypass flow rates.
(C) Gauges. Downstream gauges are required for any system used for
testing under this subpart. Upstream gauges may be required under this
subpart. Upstream gauges G1 and G2 measure the input to the CO and
CO2 analyzers. Downstream gauges G3 and G4 measure the exit
pressure of the CO and CO2 analyzers. If the normal operating
range of the downstream gauges is less than 3 inches of water, then the
downstream gauges must be capable of reading both pressure and vacuum.
Gauges G3 and G4 are not necessary if the analyzers are vented directly
to atmospheric pressure.
(D) Pressure gauges. P1 is a bypass pressure gauge; P2, P3, P4, and
P5 are for sample or span pressure at inlet to flow control valves.
(E) Water traps. Water traps WT1 and WT2 to remove water from the
sample. A water trap performing the function of WT1 is required for any
system used for testing under this subpart. Chemical dryers are not an
acceptable method of removing the water. Water removal by condensation
is acceptable. If water is removed by condensation, the sample gas
temperature or sample dew point must be monitored either within the
water trap or downstream; it may not exceed 45 deg.F (7 deg.C). Means
other than condensation may be used only with prior approval from the
Administrator.
(F) Regulators. R1, R3, R4, and R6 are line pressure regulators to
control span pressure at inlet to flow control valves; R2 and R5 are
back pressure regulators to control sample pressure at inlet to flow
control valves.
(G) Valves. V1, V7, V8, and V14 are selector valves to select zero
or calibration gases; V2 are optional heated selector valves to purge
the sample probe, perform leak checks, or to perform hang-up checks; V3
and V5 are selector valves to select sample or span gases; V4, V6, and
V15 are flow control valves; V9 and V13--heated selector valve to select
sample or span gases; V10 and V12--heated flow control valves; V11--
Selector valve to select NOX or bypass mode in the
chemiluminescence analyzer; V16--heated selector valve to perform leak
checks.
(H) Pump. Sample transfer pump to transport sample to analyzers.
(I) Temperature sensor. A temperature sensor (T1) to measure the
NO2 to NO converter temperature is required for any system
used for testing under this subpart.
(J) Dryer. Dryers D1 and D2 to remove the water from the bypass
flows to prevent condensation in flowmeters FL3, FL4, and FL6.
(2) The following requirements must be incorporated in each gaseous
sampling system used for testing under this subpart:
(i) The exhaust is analyzed for gaseous emissions using analyzers
meeting the specifications of Sec. 92.109, and all analyzers must obtain
the sample to be analyzed from the same sample probe, and internally
split to the different analyzers.
(ii) Sample transfer lines must be heated as specified in paragraph
(b)(4) of this section.
(iii) Carbon monoxide and carbon dioxide measurements must be made
on a dry basis. Specific requirements for the means of drying the sample
can be found in paragraph (b)(1)(ii)(E) of this section.
(iv) All NDIR analyzers must have a pressure gauge immediately
downstream of the analyzer. The gauge tap must be within 2 inches of the
analyzer exit port. Gauge specifications can be found in paragraph
(b)(1)(ii)(C) of this section.
(v) All bypass and analyzer flows exiting the analysis system must
be measured. Capillary flows such as in HFID and CL analyzers are
excluded. For each NDIR analyzer with a flow meter located upstream of
the analyzer, an upstream pressure gauge must be used. The gauge tap
must be
[[Page 435]]
within 2 inches of the analyzer entrance port.
(vi) Calibration or span gases for the NOX measurement
system must pass through the NO2 to NO converter.
(vii) The temperature of the NO2 to NO converter must be
displayed continuously.
(3) Gaseous sample probe. (i) The gaseous emissions sample probe
shall be a straight, closed end, stainless steel, multi-hole probe. The
inside diameter shall not be greater than the inside diameter of the
sample line by more than 0.01 inches (0.03 cm). The wall thickness of
the probe shall not be greater than 0.04 inches (0.10 cm). The fitting
that attaches the probe to the exhaust duct shall be as small as
practical in order to minimize heat loss from the probe.
(ii) The gaseous emissions sample probe shall have a minimum of
three holes in each 3 inch segment of length of the probe. The spacing
of the radial planes for each hole in the probe must be such that they
cover approximately equal cross-sectional areas of the exhaust duct. The
angular spacing of the holes must be approximately equal. The angular
spacing of any two holes in one plane may not be 180
deg.20 deg. (see section view C-C of Figure B114-2 of this
section). The holes should be sized such that each has approximately the
same flow. If only three holes are used in each 3 inch segment of probe
length, they may not all be in the same radial plane.
(iii) The sample probe shall be so located in the center of the
exhaust duct to minimize stratification, with respect to both
concentration and velocity, present in the exhaust stream. The probe
shall be located between two feet and five feet downstream of the
locomotive exhaust outlet (or nearest practical equivalent during engine
testing), and at least 1 foot upstream of the outlet of the exhaust duct
to the atmosphere.
(iv) If the exhaust duct is circular in cross section, the sample
probe should extend approximately radially across the exhaust duct, and
approximately through the center of the duct. The sample probe must
extend across at least 80 percent of the diameter of the duct.
(v) If the exhaust duct is not circular in cross section, the sample
probe should extend across the exhaust duct approximately parallel to
the longest sides of the duct, or along the longest axis of the duct
which is not a diagonal, and through the approximate center of the duct.
The sample probe must extend across at least 80 percent of the longest
axis of the duct which is not a diagonal, and be approximately parallel
to the longest sides of the duct.
(vi) Other sample probe designs and/or locations may be used only if
demonstrated (to the Administrator's satisfaction) to provides a more
representative sample.
(4) Sample transfer line(s). (i) The maximum inside diameter of the
gaseous emissions sample line shall not exceed 0.52 inches (1.32 cm).
(ii) If valve V2 is used, the sample probe must connect directly to
valve V2. The location of optional valve V2 may not be greater than 4
feet (1.22 m) from the exhaust duct.
(iii) The sample transport system from the engine exhaust duct to
the HC analyzer and the NOX analyzer must be heated as is
indicated in Figure B114-1 of this section.
(A) For diesel fueled and biodiesel fueled locomotives and engines,
the wall temperature of the HC sample line must be maintained at 375
20 deg.F (191 11 deg.C). An exception is
made for the first 4 feet (122 cm) of sample line from the exhaust duct.
The upper temperature tolerance for this 4 foot section is waived and
only the minimum temperature specification applies.
(B) For locomotives and engines using fuels other than diesel or
biodiesel, the heated components in the HC sample path shall be
maintained at a temperature approved by the Administrator, not exceeding
446 deg.F (230 deg.C).
(C) For all fuels, wall temperature of the NOX sample
line must be maintained between 140 deg.F (60 deg.C) and 446 deg.F
(230 deg.C). An exception is made for the first 4 feet (122 cm) of
sample line from the exhaust duct. The upper temperature tolerance for
this 4 foot section is waived and only the minimum temperature
specification applies.
(D) For each component (pump, sample line section, filters, etc.) in
the heated portion of the sampling system
[[Page 436]]
that has a separate source of power or heating element, use engineering
judgment to locate the coolest portion of that component and monitor the
temperature at that location. If several components are within an oven,
then only the surface temperature of the component with the largest
thermal mass and the oven temperature need be measured.
(c) Particulate emissions. (1)(i) Schematic drawing. An example of a
sampling system which may be used for particulate emissions testing
under this subpart is shown in Figure B114-3 of this section. All
components or parts of components that are wetted by the samples gases
upstream of the filter shall be either chemically cleaned stainless
steel or other inert material, for example, polytetrafluoroethylene
resin. The use of ``gauge savers'' or ``protectors'' with nonreactive
diaphragms to reduce dead volumes is permitted. Additional components
such as instruments, valves, solenoids, pumps, switches, etc. may be
employed to provide additional information and coordinate the functions
of the component systems.
(ii) The following requirements must be incorporated in each system
used for testing under this subpart:
(A) All particulate filters must obtain the sample from the same
sample probe located within the exhaust gas extension with internal
split to the different filters.
(B) The wall temperature of the sample transport system from the
probe to the dilution tunnel (excluding the first 4 feet of the
particulate transfer tube) must be maintained at 375 deg.F to 395
deg.F (191 deg.C to 202 deg.C).
(2) Particulate raw sample probe. (i) The sample probe for the raw
exhaust shall be a straight, closed end, stainless steel, multi-hole
probe of approximately 1.25 inch (3.2 cm) diameter. The inside diameter
shall not be greater than the inside diameter of the sample line by more
than 0.1 inches (0.3 cm). The wall thickness of the probe shall not be
greater than 0.06 inches (0.15 cm). The fitting that attaches the probe
to the exhaust duct shall be as small as practical in order to minimize
heat loss from the probe.
(ii) All sample collection holes in the probe shall be located so as
to face away from the direction of flow of the exhaust stream or at most
be tangential to the flow of the exhaust stream past the probe (see
Figure B114-4 of this section). Five holes shall be located in each
radial plane along the length of the probe in which sample holes are
placed. The spacing of the radial planes for each set of holes in the
probe must be such that they cover approximately equal cross-sectional
areas of the exhaust duct. For rectangular ducts, this means that the
sample hole-planes must be equidistant from each other. For circular
ducts, this means that the distance between the sample hole-planes must
be decreased with increasing distance from the center of the duct (see
Figure B114-4 of this section).
(Note: Particulate concentrations are expected to vary to some
extent as a function of the distance to the duct wall; thus each set of
sample holes collects a sample that is representative of a cross-
sectional disk at that approximate distance from the wall.)
The spacing between sets of sample holes along the length of the probe
shall be no more than 4 inches (10 cm). The holes should be sized such
that each has approximately the same flow.
(iii)(A) The particulate sample probe shall be located in the
exhaust duct on an axis which is directly downstream of, and parallel to
the axis of the gaseous sample probe. The distance between the probes
shall be between 3 inches (7.6 cm) and 6 inches (15.2 cm). Greater
spacing is allowed for engine testing, where spacing of 3 inches (7.6
cm) to 6 inches (15.2 cm) is not practical.
(B) If the exhaust duct is circular in cross section, the sample
probe should extend approximately radially across the exhaust duct, and
approximately through the center of the duct. The sample probe must
extend across at least 80 percent of the diameter of the duct.
(C) If the exhaust duct is not circular in cross section, the sample
probe should extend across the exhaust duct approximately parallel to
the longest sides of the duct, or along the longest
[[Page 437]]
axis of the duct which is not a diagonal, and through the approximate
center of the duct. The sample probe must extend across at least 80
percent of the longest axis of the duct which is not a diagonal, and be
approximately parallel to the longest sides of the duct.
(3) Particulate sample transfer line. (i) The maximum inside
diameter of the particulate emissions sample line shall be approximately
2.5 inches (6.4 cm).
(ii) The sample transfer line shall be heated to maintain a wall
temperature above 375 deg.F.
(4) Dilution tunnel. The flow capacity of the blower moving the
mixture of sample and air through the tunnel must be sufficient to
maintain the diluted sample stream at a temperature of 125 deg.F (51.7
deg.C) or less, at the sampling zone in the dilution tunnel and at the
sample filter. A single measurement of diluted exhaust temperature is
required. The temperature shall also be maintained as required to
prevent condensation at any point in the dilution tunnel. A small
negative pressure is to be maintained in the dilution tunnel by
throttling at the source of the dilution air, and adjusted as necessary,
sufficient to draw sample through the probe and sample transfer line.
Direct sampling of the particulate material may take place (Figure B114-
3 of this section) at this point.
(i)(A) The dilution tunnel shall be:
(1) Small enough in diameter to cause turbulent flow (Reynolds
Number greater than 4000) and of sufficient length to cause complete
mixing of the exhaust and dilution air;
(2) 4 inches (10 cm) minimum inside diameter;
(3) Constructed of electrically conductive material which does not
react with the exhaust components; and
(4) Electrically grounded.
(B) The temperature of the diluted exhaust stream inside of the
dilution tunnel shall be sufficient to prevent water condensation.
(C) The engine exhaust shall be directed downstream at the point
where it is introduced into the dilution tunnel.
(ii) Dilution air:
(A) Shall be at a temperature of 68 deg.F (20 deg.C) or greater.
(B) May be filtered at the dilution air inlet.
(C) May be sampled to determine background particulate levels, which
can then be subtracted from the values measured in the exhaust stream.
(D) Shall be sampled to determine the background concentration of
CO2.
(iii) Dilute sample probe and collection system.
(A) The particulate sample probe in the dilution tunnel shall be:
(1) Installed facing upstream at a point where the dilution air and
exhaust are well mixed (i.e., on the tunnel centerline, approximately 10
tunnel diameters downstream of the point where the exhaust enters the
dilution tunnel).
(2) Sufficiently distant (radially) from other sampling probes so as
to be free from the influence of wakes or eddies produced by the other
probes.
(3) 0.5 in. (1.3 cm) minimum inside diameter.
(4) The distance from the sampling tip to the filter holder shall
not be more than 40 inches (102 cm).
(5) Designed to minimize the deposition of particulate during
transfer (i.e., bends should be as gradual as possible, protrusions (due
to sensors, etc.) should be smooth and not sudden, etc.).
(B) The gas meters or flow instrumentation shall be located
sufficiently distant from the tunnel so that the inlet gas temperature
remains constant (5 deg.F (2.8 deg.C)).
Alternately, the temperature of the sample may be monitored at the gas
meter, and the measured volume corrected to standard conditions.
(C) Particulate sampling filters. (1) Fluorocarbon-coated glass
fiber filters or fluorocarbon-based (membrane) filters are required.
(2) Particulate filters must have a diameter to maintain the average
face velocity of the sample across the filter between 35 and 80 cm/s.
(3) The dilute exhaust will be simultaneously sampled by a pair of
filters (one primary and one back-up filter) during each phase of the
test. The back-up filter shall be located no more than 4 inches (10 cm)
downstream of the primary filter. The primary and back-up filters shall
not be in contact with each other.
[[Page 438]]
(4) The recommended target loading on a primary 70-mm filter (60 mm
diameter stain area) is 1.3 milligrams. Equivalent loadings (0.5 mg/1075
mm2 stain area) shall be used as target loadings when other
filter sizes are used.
(D) Diluted CO2 sample collection system. (1) The
concentrations of CO2 in the dilution air and diluted exhaust
are determined by pumping a sample into a sample bag (made of a
nonreactive material) or directly to the analyzer, as shown in Figure
B114-3 of this section.
(2) The sample probe for the diluted exhaust shall be installed
facing upstream at a point where the dilution air and exhaust are well
mixed (i.e., on the tunnel centerline, approximately 10 tunnel diameters
downstream of the point where the exhaust enters the dilution tunnel).
It shall also be sufficiently distant (radially) from other sampling
probes so as to be free from the influence of any wakes or eddies
produced by the other probes.
(iv) Other sample flow handling and/or measurement systems may be
used if shown to yield equivalent results and if approved in advance by
the Administrator. (See Appendix IV of this part for guidance.)
(d) Exhaust system. The exhaust system shall meet the following
requirements:
(1) For locomotive testing, the engine exhaust shall be routed
through an exhaust duct with dimensions equal to or slightly larger than
the dimensions of the locomotive exhaust outlet. The exhaust duct shall
be designed so as to not significantly affect exhaust backpressure.
(2) For engine testing, either a locomotive-type or a facility-type
exhaust system (or a combination system) may be used. The exhaust
backpressure for engine testing shall be set between 90 and 100 percent
of the maximum backpressure that will result with the exhaust systems of
the locomotives in which the engine will be used. The facility-type
exhaust system shall meet the following requirements:
(i) It must be composed of smooth ducting made of typical in-use
steel or stainless steel.
(ii) If an aftertreatment system is employed, the distance from the
exhaust manifold flange(s), or turbocharger outlet to any exhaust
aftertreatment device shall be the same as in the locomotive
configuration unless the manufacturer is able to demonstrate equivalent
performance at another location.
(iii) If the exhaust system ducting from the exit of the engine
exhaust manifold or turbocharger outlet to smoke meter exceeds 12 feet
(3.7 m) in length, then all ducting shall be insulated consistent with
good engineering practice.
(iv) For engines designed for more than one exhaust outlet to the
atmosphere, a specially fabricated collection duct may be used. The
collection duct should be located downstream of the in-locomotive exits
to the atmosphere. Any potential increase in backpressure due to the use
of a single exhaust instead of multiple exhausts may be compensated for
by using larger than standard exhaust system components in the
construction of the collection duct.
(e) Dilute exhaust sampling for gaseous and particulate emissions.
(1) Dilution of the exhaust prior to sampling is allowed for gaseous
emissions. The equipment and methods used for dilution, sampling and
analysis shall comply with the requirements of subpart N of part 86 of
this chapter, with the following exceptions and additional requirements:
(i) Proportional sampling and heat exchangers are not required;
(ii) Larger minimum dimensions for the dilution tunnel(s) shall be
specified by the Administrator;
(iii) Other modifications may be made with written approval from the
Administrator.
(2) Dilution of only a portion of the exhaust is allowed, provided
that:
(i) The fraction of the total exhaust that is diluted is determined
for systems that determine mass emission rates (g/hr) from the total
volume of the diluted sample; or
(ii) The ratio of raw sample volume to diluted sample volume is
determined for systems that determine mass emission rates (g/hr) from
measured fuel flow rates.
[[Page 439]]
[GRAPHIC] [TIFF OMITTED] TR16AP98.001
[[Page 440]]
[GRAPHIC] [TIFF OMITTED] TR16AP98.002
[[Page 441]]
[GRAPHIC] [TIFF OMITTED] TR16AP98.003
[[Page 442]]
[GRAPHIC] [TIFF OMITTED] TR16AP98.004
[[Page 443]]