Sec. 181.400  Where required.


    (a) The following spaces must be equipped with a fixed gas fire 
extinguishing system, in compliance with Sec. 181.410, or other fixed 
fire extinguishing system specifically approved by the Commandant, 
except as otherwise allowed by paragraph (b) of this section:
    (1) A space containing propulsion machinery;
    (2) A space containing an internal combustion engine of more than 
37.3 kW (50 hp);
    (3) A space containing an oil fired boiler;

[[Page 261]]

    (4) A space containing machinery powered by gasoline or other fuels 
having a flash point of 43.3[deg] C (110[deg] F) or lower;
    (5) A space containing a fuel tank for gasoline or any other fuel 
having a flash point of 43.3[deg] C (110[deg] F) or lower;
    (6) A space containing combustible cargo or ship's stores 
inaccessible during the voyage (in these types of spaces only carbon 
dioxide, and not Halon, systems will be allowed);
    (7) A paint locker; and
    (8) A storeroom containing flammable liquids (including liquors of 
80 proof or higher where liquor is packaged in individual containers of 
9.5 liters (2.5 gallons) capacity or greater).
    (b) Alternative system types and exceptions to the requirements of 
paragraph (a) of this section are:
    (1) A fixed gas fire extinguishing system, which is capable of 
automatic discharge upon heat detection, may only be installed in a 
normally unoccupied space with a gross volume of not more than 170 cubic 
meters (6,000 cubic feet);
    (2) A pre-engineered fixed gas fire extinguishing system must be in 
compliance with Sec. 181.420 of this part and may only be installed in a 
normally unoccupied machinery space, a paint locker, or a storeroom 
containing flammable liquids (including liquors of 80 proof or higher 
where liquor is packaged in individual containers of 9.5 liters (2.5 
gallons) capacity or greater), with a gross volume of not more than 57 
cubic meters (2,000 cubic feet);
    (3) A B-II portable fire extinguisher installed outside the space 
may be substituted for a fixed gas fire extinguishing system in a 
storeroom containing flammable liquids (including liquors of 80 proof or 
higher where liquor is packaged in individual containers of 9.5 liters 
(2.5 gallons) capacity or greater) or a paint locker, with a volume of 
not more that 5.7 cubic meters (200 cubic feet);
    (4) A space which is so open to the atmosphere that a fixed gas fire 
extinguishing system would be ineffective, as determined by the 
cognizant OCMI, is not required to have a fixed gas fire extinguishing 
system; and
    (5) Where the amount of carbon dioxide gas required in a fixed fire 
extinguishing system can be supplied by one portable extinguisher or a 
semiportable extinguisher, such an extinguisher may be used subject to 
the following:
    (i) The cylinder shall be installed in a fixed position outside the 
space protected;
    (ii) The applicator shall be installed in a fixed position so as to 
discharge into the space protected; and
    (iii) Controls shall be installed in an accessible location outside 
the space protected.
    (c) The following spaces must be equipped with a fire detecting 
system of an approved type that is installed in accordance with 
Sec. 76.27 in subchapter H of this chapter, except when a fixed gas fire 
extinguishing system that is capable of automatic discharge upon heat 
detection is installed or when the space is manned:
    (1) A space containing propulsion machinery;
    (2) A space containing an internal combustion engine of more than 50 
hp;
    (3) A space containing an oil fired boiler;
    (4) A space containing machinery powered by gasoline or any other 
fuels having a flash point of 43.3[deg] C (110[deg] F) or lower; and
    (5) A space containing a fuel tank for gasoline or any other fuel 
having a flash point of 43.3[deg] C (110[deg] F) or lower.
    (d) All griddles, broilers, and deep fat fryers must be fitted with 
a grease extraction hood in compliance with Sec. 181.425.
    (e) Each overnight accommodation space on a vessel with overnight 
accommodations for passengers must be fitted with an independent modular 
smoke detecting and alarm unit in compliance with Sec. 181.450.
    (f) An enclosed vehicle space must be fitted with an automatic 
sprinkler system that meets the requirements of Sec. 76.25 in subchapter 
H of this chapter; and
    (1) A fire detecting system of an approved type that is installed in 
accordance with Sec. 76.27 in subchapter H of this chapter; or
    (2) A smoke detecting system of an approved type that is installed 
in accordance with Sec. 76.33 in subchapter H of this chapter.

[[Page 262]]

    (g) A partially enclosed vehicle space must be fitted with a manual 
sprinkler system that meets the requirements of Sec. 76.23 in subchapter 
H of this chapter.