Sec. 193.10-10  Fire hydrants and hose.

    (a) The size of fire hydrants, hose, and nozzles and the length of 
hose required shall be as noted in Table 193.10-5(a).
    (b) In lieu of the 2\1/2\-inch hose and hydrants specified in Table 
193.10-5(a), on vessels over 1,500 gross tons, the hydrants in interior 
locations may have siamese connections for 1\1/2\-inch hose. In these 
cases the hose shall be 75 feet in length, and only one hose will be 
required at each fire station; however, if all such stations can be 
satisfactorily served with 50-foot lengths, 50-foot hose may be used.
    (c) On vessels of 500 gross tons and over there must be at least one 
shore connection to the fire main available to each side of the vessel 
in an accessible location. Suitable cutout valves and check valves must 
be provided for furnishing the vessel's shore connections with couplings 
mating those on the shore fire lines. Vessels of 500 gross tons and over 
on an international voyage, must be provided with at least one 
international shore connection complying with ASTM F 1121 (incorporated 
by reference, see Sec. 193.01-3). Facilities must be available enabling 
an international shore connection to be used on either side of the 
vessel.
    (d) Fire hydrants must be of sufficient number and so located that 
any part of the vessel, other than main machinery spaces, may be reached 
with at least 2 streams of water from separate outlets, at least one of 
which must be from a single length of hose. In main machinery spaces, 
all portions of such spaces must be capable of being reached by at least 
2 streams of water, each of which must be from a single length of hose 
from separate outlets; however, this requirement need not apply to shaft 
alleys containing no assigned space for the stowage of combustibles. 
Fire hydrants must be numbered as required by Sec. 196.37-15 of this 
subchapter.
    (e) All parts of the fire main located on exposed decks shall either 
be protected against freezing or be fitted with cutout valves and drain 
valves so that the entire exposed parts of such piping may be shut off 
and drained in freezing weather. Except when closed to prevent freezing, 
such valves shall be sealed open.
    (f) The outlet at the fire hydrant shall be limited to any position 
from the horizontal to the vertical pointing downward, so that the hose 
will lead horizontally or downward to minimize the possibility of 
kinking.
    (g) Each fire hydrant shall be provided with a single length of hose 
with nozzle attached and a spanner. A suitable hose rack or other device 
shall be provided for the proper stowage of the hose. If the hose is not 
stowed in the open or behind glass so as to be readily seen, the 
enclosures shall be marked in accordance with Sec. 196.37-15 of this 
subchapter.
    (h) Fire hose shall be connected to the outlets at all times. 
However, at open decks where no protection is afforded to the hose in 
heavy weather, the hose may be temporarily removed from the hydrant and 
stowed in an accessible nearby location.
    (i) Each fire hydrant must have at least 1 length of firehose. Each 
firehose must have a combination solid stream

[[Page 373]]

and water spray nozzle that is approved under subpart 162.027 of this 
subchapter, except 19 millimeters (3/4 inch) hose may have a garden hose 
nozzle that is bronze or metal with strength and corrosion resistance 
equivalent to bronze. Combination solid stream and water spray nozzles 
previously approved under subpart 162.027 of this chapter may be 
retained so long as they are maintained in good condition to the 
satisfaction of the Officer in Charge, Marine Inspection.
    (j) When the firehose nozzle in the below locations was previously 
approved under subpart 162.027 of this chapter, a low-velocity water 
spray applicator, also previously approved under subpart 162.027, of 
this chapter must be installed as follows:
    (1) At least 1 length of firehose on each fire hydrant outside and 
in the immediate vicinity of each laboratory;
    (2) Each firehose in each propulsion machinery space containing oil-
fired boiler, internal combustion machinery, or oil fuel unit on a 
vessel of 1000 gross tons or more--the length of each applicator must be 
1.2 meters (4 feet).
    (k) Fixed brackets, hooks, or other means for stowing an applicator 
must be next to each fire hydrant that has an applicator under paragraph 
(j) of this section.
    (l) Firehose shall not be used for any other purpose than fire 
extinguishing, drills, and testing.
    (m) Fire hydrants, nozzles, and other fittings shall have threads to 
accommodate the hose connections noted in this paragraph. Firehose and 
couplings shall be as follows:
    (1) Couplings shall be of brass, bronze, or other equivalent metal. 
National Standard firehose coupling threads shall be used for the 1\1/
2\-inch and 2\1/2\-inch sizes, i.e., 9 threads per inch for 1\1/2\-inch 
hose and 7\1/2\ threads per inch for 2\1/2\-inch hose.
    (2) Unlined hose shall not be used in the machinery spaces.
    (3) Where \3/4\-inch hose is permitted by Table 193.10-5(a), the 
hose and couplings shall be of good commercial grade.
    (4) Each section of fire hose used after January 1, 1980 must be 
lined commercial fire hose that conforms to Underwriters' Laboratories, 
Inc. Standard 19 or Federal Specification ZZ-H-451E. Hose that bears the 
label of Underwriters' Laboratories, Inc. as lined fire hose is accepted 
as conforming to this requirement. Each section of replacement fire hose 
or any section of new fire hose placed aboard a vessel after January 1, 
1977 must also conform to the specification required by this paragraph.