                           TITLE 46--SHIPPING
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 193--FIRE PROTECTION EQUIPMENT--Table of Contents
 
      Subpart 193.15--Carbon Dioxide Extinguishing Systems, Details
 
Sec. 193.15-35  Enclosure openings.

    (a) Where mechanical ventilation is provided for spaces which are 
protected by carbon dioxide extinguishing systems provisions shall be 
made so that the ventilation system is automatically shut down with the 
operation of the system to that space.
    (b) Where natural ventilation is provided for spaces protected by a 
carbon dioxide extinguishing system, provisions shall be made for easily 
and effectively closing off the ventilation.
    (c) Means shall be provided for closing all other openings to the 
space protected from outside such space. In this respect, relatively 
tight doors, shutters, or dampers shall be provided for openings in the 
lower portion of the space. The construction shall be such that openings 
in the upper portion of the space can be closed off either by

[[Page 378]]

permanently installed means or by the use of canvas or other material 
which is normally carried by the vessel.