[Code of Federal Regulations]
[Title 49, Volume 2]
[Revised as of October 1, 2003]
From the U.S. Government Printing Office via GPO Access
[CITE: 49CFR180.209]

[Page 1060-1064]
 
                        TITLE 49--TRANSPORTATION
 
 CHAPTER I--RESEARCH AND SPECIAL PROGRAMS ADMINISTRATION, DEPARTMENT OF 
                             TRANSPORTATION
 
PART 180_CONTINUING QUALIFICATION AND MAINTENANCE OF PACKAGINGS--Table of 
Contents
 
        Subpart C_Qualification, Maintenance and Use of Cylinders
 
Sec.  180.209  Requirements for requalification of specification cylinders.

    (a) Periodic qualification of cylinders. (1) Each specification 
cylinder that becomes due for periodic requalification, as specified in 
the following table, must be requalified and marked in conformance with 
the requirements of this subpart. Requalification records must be 
maintained in accordance with Sec.  180.215. Table 1 follows:

                Table 1--Requalification of Cylinders \1\
------------------------------------------------------------------------
  Specification under which       Minimum test         Requalification
      cylinder was made       pressure  (psig) \2\     period  (years)
------------------------------------------------------------------------
DOT 3.......................  3000 psig...........  5
DOT 3A, 3AA.................  5/3 times service     5, 10, or 12 (see
                               pressure, except      Sec.   180.209(b),
                               noncorrosive          (f), (h), and (j)
                               service (see Sec.
                               180.209(g)).
DOT 3AL.....................  5/3 times service     5 or 12 (see Sec.
                               pressure.             180.209(j))
DOT 3AX, 3AAX...............  5/3 times service     5
                               pressure.
3B, 3BN.....................  2 times service       5 or 10 (see Sec.
                               pressure (see Sec.    180.209(f))
                                180.209(g)).
3E..........................  Test not required...
3HT.........................  5/3 times service     3 (see Sec.  Sec.
                               pressure.             180.209(k) and
                                                     180.213(c))
3T..........................  5/3 times service     5
                               pressure.
4AA480......................  2 times service       5 or 10 (see Sec.
                               pressure (see Sec.    180.209(h))
                                180.209(g)).
4B, 4BA, 4BW, 4B-240ET......  2 times service       5, 10, or 12 (see
                               pressure, except      Sec.   180.209(e),
                               non-corrosive         (f), and (j))
                               service (see Sec.
                               180.209(g)).
4D, 4DA, 4DS................  2 times service.....  5
DOT 4E......................  2 times service       5
                               pressure, except
                               non-corrosive (see
                               Sec.   180.209(g)).
4L..........................  Test not required...
8, 8AL......................  ....................  10 or 20 (see Sec.
                                                     180.209(i))
Exemption cylinder..........  See current           See current
                               exemption.            exemption
Foreign cylinder (see Sec.    As marked on          5 (see Sec.  Sec.
 173.301(j) of this            cylinder, but not     180.209(l) and
 subchapter for restrictions   less than 5/3 of      180.213(d)(2))
 on use).                      any service or
                               working pressure
                               marking.
------------------------------------------------------------------------
\1\ Any cylinder not exceeding 2 inches outside diameter and less than 2
  feet in length is excepted from volumetric expansion test.
\2\ For cylinders not marked with a service pressure, see Sec.
  173.301a(b) of this subchapter.

    (b) DOT 3A or 3AA cylinders. (1) A cylinder conforming to 
specification DOT 3A or 3AA with a water capacity of 56.7 kg (125 lb) or 
less that is removed from any cluster, bank, group, rack, or vehicle 
each time it is filled, may be requalified every ten years instead of 
every five years, provided the cylinder conforms to all of the following 
conditions:
    (i) The cylinder was manufactured after December 31, 1945.
    (ii) The cylinder is used exclusively for air; argon; cyclopropane; 
ethylene; helium; hydrogen; krypton; neon; nitrogen; nitrous oxide; 
oxygen; sulfur

[[Page 1061]]

hexafluoride; xenon; chlorinated hydrocarbons, fluorinated hydrocarbons, 
liquefied hydrocarbons, and mixtures thereof that are commercially free 
from corroding components; permitted mixtures of these gases (see Sec.  
173.301(d) of this subchapter); and permitted mixtures of these gases 
with up to 30 percent by volume of carbon dioxide, provided the gas has 
a dew point at or below minus (52 [deg]F) at 1 atmosphere.
    (iii) Before each refill, the cylinder is removed from any cluster, 
bank, group, rack or vehicle and passes the hammer test specified in CGA 
Pamphlet C-6 (incorporated by reference; see Sec.  171.7 of this 
subchapter).
    (iv) The cylinder is dried immediately after hydrostatic testing to 
remove all traces of water.
    (v) The cylinder is not used for underwater breathing.
    (vi) Each cylinder is stamped with a five-pointed star at least one-
fourth of an inch high immediately following the test date.
    (2) If, since the last required requalification, a cylinder has not 
been used exclusively for the gases specifically identified in paragraph 
(b)(1)(ii) of this section, but currently conforms with all other 
provisions of paragraph (b)(1) of this section, it may be requalified 
every 10 years instead of every five years, provided it is first 
requalified and examined as prescribed by Sec.  173.302a(b) (2), (3) and 
(4) of this subchapter.
    (3) Except as specified in paragraph (b)(2) of this section, if a 
cylinder, marked with a star, is filled with a compressed gas other than 
as specified in paragraph (b)(1)(ii) of this section, the star following 
the most recent test date must be obliterated. The cylinder must be 
requalified five years from the marked test date, or prior to the first 
filling with a compressed gas, if the required five-year requalification 
period has passed.
    (c) DOT 4-series cylinders. A DOT 4-series cylinder, except a 4L 
cylinder, that at any time shows evidence of a leak or of internal or 
external corrosion, denting, bulging or rough usage to the extent that 
it is likely to be weakened appreciably, or that has lost five percent 
or more of its official tare weight must be requalified before being 
refilled and offered for transportation. (Refer to CGA Pamphlet C-6 or 
C-6.3, as applicable, regarding cylinder weakening.) After testing, the 
actual tare weight must be recorded as the new tare weight.
    (d) Cylinders 5.44 kg (12 lb) or less with service pressures of 300 
psig or less. A cylinder of 5.44 (12 lb) or less water capacity 
authorized for service pressure of 300 psig or less must be given a 
complete external visual inspection at the time periodic requalification 
becomes due. External visual inspection must be in accordance with CGA 
Pamphlet C-6 or C-6.1 (incorporated by reference; see Sec.  171.7 of 
this subchapter). The cylinder may be proof pressure tested. The test is 
successful if the cylinder, when examined under test pressure, does not 
display a defect described in Sec.  180.205(i)(1) (ii) or (iii). Upon 
successful completion of the test and inspection, the cylinder must be 
marked in accordance with Sec.  180.213.
    (e) Proof pressure test A cylinder made in conformance with 
specifications DOT 4B, 4BA, 4BW, or 4E used exclusively for: liquefied 
petroleum gas that meets the detail requirement limits in Table I of 
ASTM D 1835, ``Standard Specification for Liquefied Petroleum (LP) 
Gases'' (incorporated by reference; see Sec.  171.7 of this subchapter) 
or an equivalent standard containing the same limits; anhydrous 
dimethylamine; anhydrous methylamine; anhydrous trimethylamine; methyl 
chloride; methylacetylene-propadiene stabilized; or 
dichlorodifluoromethane, difluoroethane, difluorochloroethane, 
chlorodifluoromethane, chlorotetrafluoroethane, trifluorochloroethylene, 
or mixture thereof, or mixtures of one or more with 
trichlorofluoromethane; and commercially free from corroding components 
and protected externally by a suitable corrosion-resistant coating (such 
as galvanizing or painting) may be requalified by volumetric expansion 
testing every 12 years instead of every five years. As an alternative, 
the cylinder may be subjected to a proof pressure test at least two 
times the marked service pressure, but this latter type of test must be 
repeated every seven years after expiration of the first 12-year period. 
When subjected to a proof

[[Page 1062]]

pressure test, the cylinder must be carefully examined under test 
pressure and removed from service if a leak or defect is found.
    (f) Poisonous materials. A cylinder conforming to specification DOT 
3A, 3AA, 3B, 4BA, or 4BW having a service pressure of 300 psig or less 
and used exclusively for methyl bromide, liquid; mixtures of methyl 
bromide and ethylene dibromide, liquid; mixtures of methyl bromide and 
chlorpicrin, liquid; mixtures of methyl bromide and petroleum solvents, 
liquid; or methyl bromide and nonflammable, nonliquefied compressed gas 
mixtures, liquid; commercially free of corroding components, and 
protected externally by a suitable corrosion resistant coating (such as 
galvanizing or painting) and internally by a suitable corrosion 
resistant lining (such as galvanizing) may be tested every 10 years 
instead of every five years, provided a visual internal and external 
examination of the cylinder is conducted every five years in accordance 
with CGA Pamphlet C-6 (incorporated by reference; see Sec.  171.7 of 
this subchapter). The cylinder must be examined at each filling, and 
rejected if a dent, corroded area, leak or other condition indicates 
possible weakness.
    (g) Visual inspections. A cylinder conforming to a specification 
listed in the table in this paragraph and used exclusively in the 
service indicated may, instead of a periodic hydrostatic test, be given 
a complete external visual inspection at the time periodic 
requalification becomes due. External visual inspection must be in 
accordance with CGA Pamphlet C-6 or C-6.3, as applicable (incorporated 
by reference; see Sec.  171.7 of this subchapter). When this inspection 
is used instead of hydrostatic pressure testing, subsequent inspections 
are required at five-year intervals after the first inspection. After 
May 31, 2004, inspections must be made only by persons holding a current 
RIN and the results recorded and maintained in accordance with Sec.  
180.215. Records must include: date of inspection (month and year); DOT 
specification number; cylinder identification (registered symbol and 
serial number, date of manufacture, and owner); type of cylinder 
protective coating (including statement as to need of refinishing or 
recoating); conditions checked (e.g., leakage, corrosion, gouges, dents 
or digs in shell or heads, broken or damaged footring or protective ring 
or fire damage); disposition of cylinder (returned to service, returned 
to cylinder manufacturer for repairs or condemned). A cylinder passing 
requalification by the external visual inspection must be marked in 
accordance with Sec.  180.213. Specification cylinders must be in 
exclusive service as shown in the following table:

------------------------------------------------------------------------
       Cylinders conforming to--              Used exclusively for--
------------------------------------------------------------------------
DOT 3A, DOT 3AA, DOT 3A480X, DOT 4AA480  Anhydrous ammonia of at least
                                          99.95% purity.
DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B,     Butadiene, inhibited, that is
 DOT 4B, DOT 4BA, DOT 4BW.                commercially free from
                                          corroding components.
DOT 3A, DOT 3A480X, DOT 3AA, DOT 3B,     Cyclopropane that is
 DOT 4AA480, DOT 4B, DOT 4BA, DOT 4BW.    commercially free from
                                          corroding components.
DOT 3A, DOT 3AA, DOT 3A480X, DOT 4B,     Chlorinated hydrocarbons and
 DOT 4BA, DOT 4BW, DOT 4E.                mixtures thereof that are
                                          commercially free from
                                          corroding components.
DOT 3A, DOT 3AA, DOT 3A480X, DOT 4B,     Fluorinated hydrocarbons and
 DOT 4BA, DOT 4BW, DOT 4E.                mixtures thereof that are
                                          commercially free from
                                          corroding components.
DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B,     Liquefied hydrocarbon gas that
 DOT 4B, DOT 4BA, DOT 4BW, DOT 4E.        is commercially free from
                                          corroding components.
DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B,     Liquefied petroleum gas that
 DOT 4B, DOT 4BA, DOT 4BW, DOT 4E.        meets the detail requirements
                                          limits in Table 1 of ASTM
                                          1835, Standard Specification
                                          for Liquefied Petroleum (LP)
                                          Gases (incorporated by
                                          reference; see Sec.   171.7 of
                                          this subchapter) or an
                                          equivalent standard containing
                                          the same limits.
DOT 3A, DOT 3AA, DOT 3B, DOT 4B, DOT     Methylacetylene-propadiene,
 4BA, DOT 4BW, DOT 4E.                    stabilized, that is
                                          commercially free from
                                          corroding components.
DOT 3A, DOT 3AA, DOT 3B, DOT 4B, DOT     Anhydrous mono,
 4BA, DOT 4BW.                            di,trimethylamines that are
                                          commercially free from
                                          corroding components.
DOT 4B240, DOT 4BW240..................  Ethyleneimine, stabilized.
------------------------------------------------------------------------

    (h) Cylinders containing anhydrous ammonia. A cylinder conforming to 
specification DOT 3A, 3A480X, or 4AA480

[[Page 1063]]

used exclusively for anhydrous ammonia, commercially free from corroding 
components, and protected externally by a suitable corrosion-resistant 
coating (such as paint) may be requalified every 10 years instead of 
every five years.
    (i) Requalification of DOT-8 series cylinders. (1) Each owner of a 
DOT-8 series cylinder used to transport acetylene must have the cylinder 
shell and the porous filler requalified in accordance with CGA Pamphlet 
C-13 (incorporated by reference; see Sec.  171.7 of this subchapter). 
Requalification must be performed in accordance with the following 
schedule:

----------------------------------------------------------------------------------------------------------------
                                         Shell (visual inspection)             Porous filler requalification
                                              requalification            ---------------------------------------
  Date of cylinder manufacture   ----------------------------------------
                                        Initial           Subsequent            Initial           Subsequent
----------------------------------------------------------------------------------------------------------------
Before January 1, 1991..........  Before January 1,   10 years..........  Before January 1,   Not required.
                                   2001.                                   2011.
On or after January 1, 1991.....  10 years \1\......  10 years..........  3 to 20 years \2\.  Not required.
----------------------------------------------------------------------------------------------------------------
\1\ Years from date of cylinder manufacture.
\2\ For a cylinder manufactured on or after January 1, 1991, requalification of the porous filler must be
  performed no sooner than 5 years, and no later than 20 years, from the date of manufacture.

    (2) Unless requalified and marked in accordance with CGA Pamphlet C-
13 (incorporated by reference; see Sec.  171.7 of this subchapter) 
before October 1, 1994, an acetylene cylinder must be requalified by a 
person who holds a current RIN.
    (3) If a cylinder valve is replaced, a cylinder valve of the same 
weight must be used or the tare weight of the cylinder must be adjusted 
to compensate for valve weight differential.
    (4) The person performing a visual inspection or requalification 
must record the results as specified in Sec.  180.215.
    (5) The person performing a visual inspection or requalification 
must mark the cylinder as specified in Sec.  180.213.
    (j) Cylinder used as a fire extinguisher. Only a DOT specification 
cylinder used as a fire extinguisher and meeting Special Provision 18 in 
Sec.  172.102(c)(1) of this subchapter may be requalified in accordance 
with this paragraph (j).
    (1) A DOT 4B, 4BA, 4B240ET or 4BW cylinder may be tested as follows:
    (i) For a cylinder with a water capacity of 5.44 kg (12 lb) or less, 
by volumetric expansion test using the water jacket method or by proof 
pressure test. A requalification must be performed by the end of 12 
years after the original test date and at 12-year intervals thereafter.
    (ii) For a cylinder having a water capacity over 5.44 kg (12 lb)--
    (A) By proof pressure test. A requalification must be performed by 
the end of 12 years after the original test date and at 7-year 
intervals; or
    (B) By volumetric expansion test using the water jacket method. A 
requalification must be performed 12 years after the original test date 
and at 12-year intervals thereafter.
    (2) A DOT 3A, 3AA, or 3AL cylinder must be requalified by volumetric 
expansion test using the water jacket method. A requalification must be 
performed 12 years after the original test date and at 12-year intervals 
thereafter.
    (k) 3HT cylinders. In addition to the other requirements of this 
section, a cylinder marked DOT-3HT must be requalified in accordance 
with CGA Pamphlet C-8.
    (l) Requalification of foreign cylinders filled for export. A 
cylinder manufactured outside the United States, other than as provided 
in Sec.  171.12a of this subchapter, that has not been manufactured, 
inspected, tested and marked in accordance with part 178 of this 
subchapter may be filled with compressed gas in the United States, and 
shipped solely for export if it meets the following requirements, in 
addition to other requirements of this subchapter:
    (1) It has been inspected, tested and marked (with only the month 
and year of test) in conformance with the procedures and requirements of 
this subpart or the Associate Administrator has authorized the filling 
company to fill foreign cylinders under an alternative method of 
qualification; and

[[Page 1064]]

    (2) It is offered for transportation in conformance with the 
requirements of Sec.  173.301(l) of this subchapter.

[67 FR 51660, Aug. 8, 2002, as amended at 68 FR 24662, May 8, 2003; 68 
FR 55544, Sept. 26, 2003; 68 FR 48572, Aug. 14, 2003]