Sec. 192.113  Longitudinal joint factor (E) for steel pipe.

    The longitudinal joint factor to be used in the design formula in 
Sec. 192.105 is determined in accordance with the following table:

------------------------------------------------------------------------
                                                          Longitudinal
         Specification                Pipe class        joint factor (E)
------------------------------------------------------------------------
ASTM A 53......................  Seamless............               1.00
                                 Electric resistance                1.00
                                  welded.
                                 Furnace butt welded.                .60
ASTM A 106.....................  Seamless............               1.00
ASTM A 333/A 333M..............  Seamless............               1.00
                                 Electric resistance                1.00
                                  welded.
ASTM A 381.....................  Double submerged arc               1.00
                                  welded.
ASTM A 671.....................  Electric-fusion-                   1.00
                                  welded.
ASTM A 672.....................  Electric-fusion-                   1.00
                                  welded.
ASTM A 691.....................  Electric-fusion-                   1.00
                                  welded.
API 5 L........................  Seamless............               1.00
                                 Electric resistance                1.00
                                  welded.
                                 Electric flash                     1.00
                                  welded.
                                 Submerged arc welded               1.00
                                 Furnace butt welded.                .60
Other..........................  Pipe over 4 inches                  .80
                                  (102 millimeters).
Other..........................  Pipe 4 inches (102                  .60
                                  millimeters) or
                                  less.
------------------------------------------------------------------------


If the type of longitudinal joint cannot be determined, the joint factor 
to be used must not exceed that designated for ``Other.''