Sec. 192.163  Compressor stations: Design and construction.

    (a) Location of compressor building. Except for a compressor 
building on a platform located offshore or in inland navigable waters, 
each main compressor building of a compressor station must be located on 
property under the control of the operator. It must be far enough away 
from adjacent property, not under control of the operator, to minimize 
the possibility of fire being communicated to the compressor building 
from structures on adjacent property. There must be enough open space 
around the main compressor building to allow the free movement of fire-
fighting equipment.
    (b) Building construction. Each building on a compressor station 
site must be made of noncombustible materials if it contains either--
    (1) Pipe more than 2 inches (51 millimeters) in diameter that is 
carrying gas under pressure; or
    (2) Gas handling equipment other than gas utilization equipment used 
for domestic purposes.
    (c) Exits. Each operating floor of a main compressor building must 
have at least two separated and unobstructed exits located so as to 
provide a convenient possibility of escape and an unobstructed passage 
to a place of safety. Each door latch on an exit must be of a type which 
can be readily opened from the inside without a key. Each swinging door 
located in an exterior wall must be mounted to swing outward.
    (d) Fenced areas. Each fence around a compressor station must have 
at least two gates located so as to provide a convenient opportunity for 
escape to a place of safety, or have other facilities affording a 
similarly convenient exit from the area. Each gate located within 200 
feet (61 meters) of any compressor plant building must open outward and, 
when occupied, must be openable from the inside without a key.

[[Page 44]]

    (e) Electrical facilities. Electrical equipment and wiring installed 
in compressor stations must conform to the National Electrical Code, 
ANSI/NFPA 70, so far as that code is applicable.