Sec. 195.205  Repair, alteration and reconstruction of aboveground breakout 
tanks that have been in service.

    (a) Aboveground breakout tanks that have been repaired, altered, or 
reconstructed and returned to service must be capable of withstanding 
the internal pressure produced by the hazardous liquid to be stored 
therein and any anticipated external loads.
    (b) After October 2, 2000, compliance with paragraph (a) of this 
section requires the following for the tanks specified:
    (1) For tanks designed for approximately atmospheric pressure 
constructed of carbon and low alloy steel, welded or riveted, and non-
refrigerated and tanks built to API Standard 650 or its predecessor 
Standard 12C, repair, alteration, and reconstruction must be in 
accordance with API Standard 653.
    (2) For tanks built to API Specification 12F or API Standard 620, 
the repair, alteration, and reconstruction must be in accordance with 
the design, welding, examination, and material requirements of those 
respective standards.
    (3) For high pressure tanks built to API Standard 2510, repairs, 
alterations, and reconstruction must be in accordance with API 510.

[Amdt. 195-66, 64 FR 15935, Apr. 2, 1999]