[Code of Federal Regulations] [Title 41, Volume 3] [Revised as of July 1, 2004] From the U.S. Government Printing Office via GPO Access [CITE: 41CFR102-80.105] [Page 276] TITLE 41--PUBLIC CONTRACTS AND PROPERTY MANAGEMENT CHAPTER 102--FEDERAL MANAGEMENT REGULATION PART 102-80_SAFETY AND ENVIRONMENTAL MANAGEMENT--Table of Contents Subpart C_Accident and Fire Prevention Sec. 102-80.105 What information must be included in an equivalent level of safety analysis? The equivalent level of life safety evaluation is to be performed by a qualified fire protection engineer. The analysis should include a narrative discussion of the features of the building structure, function, operational support systems and occupant activities that impact fire protection and life safety. Each analysis should describe potential reasonable worst case fire scenarios and their impact on the building occupants and structure. Specific issues that must be addressed include rate of fire growth, type and location of fuel items, space layout, building construction, openings and ventilation, suppression capability, detection time, occupant notification, occupant reaction time, occupant mobility, and means of egress.