[Code of Federal Regulations]
[Title 46, Volume 7]
[Revised as of October 1, 2004]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR183.340]

[Page 291-293]
 
                           TITLE 46--SHIPPING
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 183_ELECTRICAL INSTALLATION--Table of Contents
 
            Subpart C_Power Sources and Distribution Systems
 
Sec. 183.340  Cable and wiring requirements.

    (a) If individual wires, rather than cable, are used in systems 
greater than 50 volts, the wire must be in conduit.
    (b) All cable and wire must:
    (1) Have stranded copper conductors with sufficient current carrying 
capacity for the circuit in which they are used;
    (2) Be installed in a manner to avoid or reduce interference with 
radio reception and compass indication;
    (3) Be protected from the weather;
    (4) Be installed with metal supports spaced not more than 610 
millimeters (24 inches) apart, and in such a manner as to avoid chafing 
and other damage. The use of plastic tie wraps must be limited to 
bundling or retention of multiple cable installations, and not used as a 
means of support, except that on vessels of not more than 19.8 meters 
(65 feet) in length, installations in accordance with paragraph 14.h of 
ABYC E-8, and paragraph 15.h of ABYC E-9, are acceptable as meeting the 
requirements of this section;
    (5) Not be installed with sharp bends;
    (6) Be protected by metal coverings or other suitable means if in 
areas subject to mechanical abuse. Horizontal pipes used for protection 
shall have 6 millimeter (.25 inch) holes for drainage every 1,520 
millimeters (5 feet);
    (7) Be suitable for low temperature and high humidity if installed 
in refrigerated compartments;
    (8) Not be located in a tank unless the cable provides power to 
equipment in the tank; and
    (9) Have sheathing or wire insulation compatible with the fluid in a 
tank when installed as allowed by paragraph (b)(8) of this section.
    (c) Conductors in power and lighting circuits must be No. 14 
American Wire Gauge (AWG) or larger. Conductors in control and indicator 
circuits must be No. 22 AWG or larger.
    (d) Cable and wire for power and lighting circuits must:
    (1) Meet Section 310-13 of the NEC (NFPA 70), except that asbestos 
insulated cable and dry location cables cannot be used;
    (2) Be listed by Underwriters Laboratories (UL), as UL Boat or UL 
Marine cable; or
    (3) Meet Sec. 111.60-1 in subchapter J of this chapter for cable, 
and Sec. 111.60-11 in subchapter J of this chapter for wire.
    (e) Cable or wire serving vital systems listed in Sec. 182.710 of 
this chapter or emergency loads must be routed as far as practicable 
from high risk fire areas, such as galleys, laundries, and machinery 
spaces.
    (f) Cable or wire serving duplicated equipment must be separated so 
that a casualty that affects one cable does not affect the other.
    (g) Each connection to a conductor or terminal part of a conductor 
must be made within an enclosure and have either:
    (1) A pressure type connector on each conductor;
    (2) A solder lug on each conductor;

[[Page 292]]

    (3) A splice made with a pressure type connector to a flexible lead 
or conductor; or
    (4) A splice that is soldered, brazed, or welded to a flexible lead 
or conductor.
    (h) A connector or lug of the set screw type must not be used with a 
stranded conductor smaller than No. 14 AWG except if there is a 
nonrotating follower that travels with the set screw and makes pressure 
contact with the conductor.
    (i) Each pressure type wire connector and lug must meet UL 486A, 
``Electric Wire Connectors and Soldering Lugs for Use With Copper 
Conductors,'' or other standard specified by the Commandant. The use of 
twist-on type wire nuts is permitted under the following conditions:
    (1) The connections must be made within an enclosure and the 
insulated cap of the connector must be secured to prevent loosening due 
to vibration; and
    (2) Twist-on type connectors may not be used for making joints in 
cables, facilitating a conductor splice, or extending the length of a 
circuit.
    (j) Each terminal block must have 6-32 terminal screws or larger.
    (k) Wire connectors utilized in conjunction with screw type terminal 
blocks must be of the captive type such as the ring or the flanged spade 
type.
    (l) A cable must not be spliced in a hazardous location.
    (m) A cable may be spliced in a location, other than a hazardous 
location, under the following conditions:
    (1) A cable installed in a subassembly may be spliced to a cable 
installed in another subassembly;
    (2) For a vessel receiving alterations, a cable may be spliced to 
extend a circuit;
    (3) A cable having a large size or exceptional length may be spliced 
to facilitate its installation; and
    (4) A cable may be spliced to replace a damaged section of the cable 
if, before replacing the damaged section, the insulation resistance of 
the remainder of the cable is measured, and it is determined that the 
condition of the insulation is unimpaired.
    (n) All material in a cable splice must be chemically compatible 
with all other material in the splice and with the materials in the 
cable.
    (o) Ampacities of wires must meet Section 310-15 of the NEC (NFPA 
70), or other standard specified by the Commandant. Ampacities of cable 
must meet table A6 of Institute of Electrical and Electronic Engineers 
(IEEE) Standard 45, ``Recommended Practice for Electrical Installations 
on Shipboard,'' or other standard specified by the Commandant. 
Ampacities for Navy cable must meet NAVSEA Design Data Sheet (DDS) 304-2 
``Electrical Cable, Ratings and Characteristics'' as appropriate.
    (p) Conductors for direct current systems must be sized so that the 
voltage drop at the load terminals does not exceed 10 percent. Table 
183.340(p) indicates the size of conductor required for corresponding 
lengths and steady state (stable) values to obtain not more than this 
voltage drop at the load terminals of a two conductor circuit.

                                                 Table 183.340(p)--Conductor Sizes for Amperes--Lengths
--------------------------------------------------------------------------------------------------------------------------------------------------------
                                                           Length of conductor in meters (feet) from source of current to most distant fixture
       Total current on circuit, amperes        --------------------------------------------------------------------------------------------------------
                                                 3.1(10)  4.5(15)  6.1(20)  7.6(25)  9.2(30)  10.7(35)  12.2(40)  13.7(45)  15.2(50)  16.8(55)  18.3(60)
--------------------------------------------------------------------------------------------------------------------------------------------------------
                                                                          12-volts, 2 wire--10 percent drop wire sizes (A.W.G.)
5..............................................      14       14       14       14       14        14        14        14        12        12        12
10.............................................      14       14       14       12       12        12        10        10        10        10         8
15.............................................      14       14       12       10       10        10         8         8         8         8         8
20.............................................      12       12       10       10        8         8         8         8         6         6         6
25.............................................      10       10       10        8        8         8         6         6         6         6         4
--------------------------------------------------------------------------------------------------------------------------------------------------------

    Other values can be computed by means of the following formula:
    [GRAPHIC] [TIFF OMITTED] TR10JA96.010
    

[[Page 293]]


Where:

cm=Circular-mil area of conductor
K=3.28 ohms/mil-meter (metric)
 =10.75 ohm/mil-foot (english)
    (a constant representing the resistance of copper).
I=Load current, in amperes.
L=length of conductor from center of distribution, in meters (feet).
E=Voltage drop at load, in volts.

    (q) If used, each armored cable metallic covering must:
    (1) Be electrically continuous; and
    (2) Be grounded at each end of the run to:
    (i) The metallic hull; or
    (ii) The common ground plate on nonmetallic vessels; and
    (3) Have final sub-circuits grounded at the supply end only.
    (r) A portable or temporary electric cord or cable must be 
constructed and used in compliance with the requirements of Sec. 
111.60-13 in subchapter J of this chapter for a flexible electric cord 
or cable.

[CGD 85-080, 61 FR 997, Jan. 10, 1996; 61 FR 20557, May 7, 1996, as 
amended by CGD 97-057, 62 FR 51050, Sept. 30, 1997; CGD 85-080, 62 FR 
51358, Sept. 30, 1997]