[Code of Federal Regulations]
[Title 46, Volume 7]
[Revised as of October 1, 2004]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR193.10-5]

[Page 371-372]
 
                           TITLE 46--SHIPPING
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 193_FIRE PROTECTION EQUIPMENT--Table of Contents
 
                Subpart 193.10_Fire Main System, Details
 
Sec. 193.10-5  Fire pumps.

    (a) Vessels shall be equipped with independently driven fire pumps 
in accordance with Table 193.10-5(a).

                            Table 193.10-5(a)
------------------------------------------------------------------------
       Gross tons                      Hose and     Nozzle
-------------------------   Minimum     hydrant     orifice    Length of
                           number of     size,       size,    hose, feet
    Over       Not over      pumps      inches      inches
------------------------------------------------------------------------
                   100        \1\ 1   \1\ 1\1/2\  \1\ \1/2\          50
      100        1,000            1      1\1/2\       \5/8\          50
    1,000        1,500            2      1\1/2\       \5/8\          50
    1,500    ...........          2   \2\ 2\1/2\  \2\ \7/8\     \2\ 50
------------------------------------------------------------------------
\1\ On vessels of 65 feet in length or less, \3/4\-inch hose of good
  commercial grade together with a commercial garden hose nozzle may be
  used. The pump may be hand operated and the length of hose shall be
  sufficient to assure coverage of all parts of the vessel.
\2\ 75 feet of 1\1/2\-inch hose and \5/8\-inch nozzle may be used where
  specified by Sec. 193.10-10(b) for interior locations and 50 feet
  1\1/2\-inch hose may be used in exterior locations on vessels in other
  than ocean or coastwise services.

    (b) On vessels of 1,000 gross tons and over on an international 
voyage, each required fire pump, while delivering water through the fire 
main system at a pressure corresponding to that required by paragraph 
(c) of this section, shall have a minimum capacity of at least two-
thirds of that required for an independent bilge pump. However, in no 
case shall the capacity of each fire pump be less than that otherwise 
required by this section.
    (c) Each pump must be capable of delivering water simultaneously 
from the outlets having the greatest pressure drop from the five pumps 
to the nozzles which may not always be the two highest outlets, at a 
Pitot tube pressure of not less than 50 p.s.i. Where 1\1/2\-inch hose is 
permitted in lieu of 2\1/2\-inch hose by footnote 2 of Table 193.10-
5(a), the pump capacity shall be determined on the same basis as if 2\1/
2\-inch hose had been permitted. Where \3/4\-inch hose is permitted by 
Table 193.10-5(a), the Pitot tube pressure may not be less than 35 
p.s.i.
    (d) Fire pumps shall be fitted on the discharge side with relief 
valves set to relieve at 25 p.s.i. in excess of the pressure necessary 
to maintain the requirements of paragraph (c) of this section or 125 
p.s.i., whichever is greater. Relief valves may be omitted if the pumps, 
operating under shutoff conditions, are not capable of developing a 
pressure exceeding this amount.
    (e) Fire pumps shall be fitted with a pressure gage on the discharge 
side of the pumps.
    (f) Fire pumps may be used for other purposes provided at least one 
of the required pumps is kept available for use on the fire system at 
all times. In no case shall a pump having connection to an oil line be 
used as a fire pump. Branch lines connected to the fire main for 
purposes other than fire and deck wash shall be so arranged that 
adequate water can be made continuously available for firefighting 
purposes.
    (g) The total area of the pipes leading from a pump shall not be 
less than the discharge area of the pump.
    (h) On vessels with oil fired boilers, either main or auxiliary, or 
with internal combustion propulsion machinery, where 2 fire pumps are 
required, they shall be located in separate spaces, and the arrangement, 
pumps, sea connections, and sources of power shall be such as to insure 
that a fire in any one space will not put all of the fire pumps out of 
operation. However, where it is shown to the satisfaction of the 
Commandant that it is unreasonable or impracticable to meet this 
requirement due to the size or arrangement of the vessel, or for other 
reasons, the installation of a total flooding carbon dioxide system may 
be accepted as an alternate method of extinguishing any fire which would 
affect the powering and operation for the required fire pumps.
    (i) Except as provided for in Sec. 193.10-10(e), a sufficient 
number of hose streams for fire fighting purposes must be immediately 
available from the fire main at all times by either of the following 
methods:
    (1) Maintenance of water pressure. (i) Water pressure must be 
maintained on

[[Page 372]]

the fire main at all times by the continuous operation of:
    (A) One of the fire pumps; or
    (B) Another suitable pump capable of supplying one hose stream at a 
Pitot tube pressure of not less than 50 p.s.i. (35 p.s.i. for \3/4\-inch 
hose); or,
    (C) A pressure tank capable of supplying one hose stream at a Pitot 
tube pressure of not less than 50 p.s.i. (35 p.s.i. for \3/4\-inch hose) 
for five minutes.
    (ii) An audible alarm must be installed to sound in a continuously 
manned space if the pressure in the fire main drops to less than that 
necessary to maintain the minimum Pitot tube pressures specified in 
Sec. 193.10-5(i)(1)(i).
    (2) Remote control of fire pumps. (i) At least one fire pump must be 
capable of remote activation and control.
    (ii) If the fire pump is in a continuously manned machinery space, 
the controls for operating it and the controls for all necessary valves 
must be located on the manned operating platform in that space.
    (iii) If the fire pump is in an unmanned machinery space, the 
controls for its operation and the controls for all necessary valves 
must be located in:
    (A) The fire control station, if any; or,
    (B) The bridge, if there is no fire control station; or,
    (C) A readily accessible space acceptable to the Officer in Charge, 
Marine Inspection.

[CGFR 67-83, 33 FR 1145, Jan. 27, 1968, as amended by CGD 75-031, 40 FR 
48349, Oct. 15, 1975; CGD 95-028, 62 FR 51220, Sept. 30, 1997]