                           TITLE 46--SHIPPING
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 193_FIRE PROTECTION EQUIPMENT--Table of Contents
 
 Subpart 193.50_Hand Portable Fire Extinguishers and Semiportable Fire 
             Extinguishing Systems, Arrangements and Details
 
Sec. 193.50-10  Location.

    (a) Approved hand portable fire extinguishers and semiportable fire 
extinguishing systems shall be installed in accordance with Table 
193.50-10(a). The location of the equipment shall be to the satisfaction 
of the Officer in Charge, Marine Inspection. Nothing in this paragraph 
shall be construed as limiting the Officer in Charge, Marine Inspection, 
from requiring such additional equipment as he deems necessary for the 
proper protection of the vessel.
    (b) Semiportable fire extinguishing systems shall be located in the 
open so as to be readily seen.
    (c) If hand portable fire extinguishers are not located in the open 
or behind glass so that they may be readily seen, they may be placed in 
enclosures together with the firehose, provided such

[[Page 380]]

enclosures are marked as required by Sec. 196.37-15 of this subchapter.

         Table 193.50-10(a)--Hand Portable Fire Extinguisher and Semiportable Fire Extinguishing Systems
----------------------------------------------------------------------------------------------------------------
                                           Classification (see Sec.
                  Space                            193.50-5)                     Quantity and location
----------------------------------------------------------------------------------------------------------------
              Safety Areas1

Wheelhouse or fire control room.........  ..........................  None required.
Stairway and elevator enclosures........  ..........................   Do.
Communicating corridors.................  A-II......................  1 in each main corridor not more than 150
                                                                       feet apart. (May be located in
                                                                       stairways.)
Lifeboat embarkation and lowering         ..........................  None required.
 stations.
Radio room..............................  C-I 2.....................  2 in vicinity of exit.2

            Accommodations 1

Staterooms, toilet spaces, public         ..........................  None required.
 spaces, offices, lockers, isolated
 storerooms, and pantries open decks,
 etc.

             Service spaces

Galleys.................................  B-II or C-II..............  1 for each 2,500 square feet or fraction
                                                                       thereof suitable for hazards involved.

            Machinery spaces

Paint and lamp rooms....................  B-II......................  1 outside space in vicinity of exit.
Accessible baggage, mail, and specie      A-II......................  1 for each 2,500 square feet or fraction
 rooms, and storerooms.                                                thereof located in vicinity of exits,
                                                                       either inside or outside the spaces.
Carpenter shop and similar spaces.......  A-II......................  1 outside the space in vicinity of exit.

Coal-fired boilers: Bunker and boiler     ..........................  None required.
 space.
Oil-fired boilers: Spaces containing oil- B-II......................  2 required.3
 fired boilers, either main or            B-V.......................  1 required.4
 auxiliary, or their fuel-oil units.      B-V.......................
Internal combustion or gas turbine        B-II......................  1 for each 1,000 brake horsepower, but not
 propelling machinery spaces.                                          less than 2 nor more than 6.5
                                          B-III.....................  1 required.6, 7
Electric propulsive motors or generators  C-II......................  1 for each propulsion motor or generator
 of open type.                                                         unit.
Enclosed ventilating systems for motors   ..........................  None required.
 and generators of electric propelling
 machinery.
Auxiliary spaces:
  Internal combustion gas turbine.......  B-II......................  1 outside the space in vicinity of exit.
                                                                       \7\
  Electric emergency motors or            C-II......................  1 outside the space in vicinity of exit.
   generators.                                                         \8\
  Steam.................................  ..........................  None required.
Trunks to machinery spaces..............  ..........................   Do.
Fuel tanks..............................  ..........................   Do.

            Scientific spaces

Chemistry laboratory or scientific        C-II......................  1 dry chemical and 1 carbon dioxide for
 laboratory.                                                           each 300 square feet or fraction thereof,
                                                                       with one (1) of each kind located in the
                                                                       vicinity of the exit.
Chemical storeroom......................  C-II......................  Same as for the chemistry laboratory.
----------------------------------------------------------------------------------------------------------------
\1\ Two B-I hand portable fire extinguishers may be substituted for 1 B-II.
\2\ For vessels on an international voyage, substitute 1 C-II in vicinity of exit.
\3\ Vessels of less than 1,000 gross tons require 1.
\4\ Vessels of less than 1,000 gross tons may substitute 1 B-IV.
\5\ Only 1 required for motorboats.
\6\ If oil burning donkey boiler fitted in space, the B-V previously required for the protection of the boiler
  may be substituted. Not required where a fixed carbon dioxide system is installed.
\7\ Not required on vessels of less than 300 gross tons if fuel has a flash-point higher than 110[deg] F.
\8\ Not required on vessels of less than 300 gross tons.

    (d) Hand portable fire extinguishers and their stations shall be 
numbered in accordance with Sec. 196.37-15 of this subchapter.
    (e) Hand portable or semiportable extinguishers, which are required 
on their nameplates to be protected from freezing, shall not be located 
where freezing temperatures may be expected.