[Code of Federal Regulations]
[Title 46, Volume 1]
[Revised as of Octobery 1, 2004]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR38.15-1]
[Page 496]
TITLE 46--SHIPPING
CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
PART 38_LIQUEFIED FLAMMABLE GASES--Table of Contents
Subpart 38.15_Special Requirements
Sec. 38.15-1 Filling of tanks--TB/ALL.
(a) Refrigerated and semirefrigerated tanks shall be filled so that
there is an outage of at least 2 percent of the volume of the tank at
the temperature corresponding to the vapor pressure of the cargo at the
safety relief valve setting. A reduction in the required outage may be
permitted by the Commandant when warranted by special design
considerations. Normally then, the maximum volume to which a tank may be
loaded is:
VL=0.98dr V/dL
where:
VL=maximum volume to which tank may be loaded.
V=volume of tank.
dr=density of cargo at the temperature required for a cargo
vapor pressure equal to the relief valve setting.
dL=density of cargo at the loading temperature and pressure.
(b) Nonrefrigerated tanks shall be filled so that their filling
densities shall not exceed the ratios indicated in Table 38.15-1(b).
(c) The ``filling density'' is defined as the percent ratio of the
weight of the gas in a tank to the weight of water the tank will hold at
60[deg] F.
Table 38.15-1(b)--Maximum Permissible Filling Densities for Tanks
Operating At or Near Ambient Temperature
------------------------------------------------------------------------
Maximum permitted filling
density
-------------------------------
Unlagged tanks--
water capacity
Specific gravity at 60 [deg]F. Lagged
-------------------- tanks--all
1,200 Over capacities
gal. and 1,200
under gal.
------------------------------------------------------------------------
0.473-0.480............................. 38 41 42
0.481-0.488............................. 39 42 43
0.489-0.495............................. 40 43 44
0.496-0.503............................. 41 44 45
0.504-0.510............................. 42 45 46
0.511-0.519............................. 43 46 47
0.520-0.527............................. 44 47 48
0.528-0.536............................. 45 48 49
0.537-0.544............................. 46 49 50
0.545-0.552............................. 47 50 51
0.553-0.560............................. 48 51 52
0.561-0.568............................. 49 52 53
0.569-0.576............................. 50 53 54
0.577-0.584............................. 51 54 55
0.585-0.592............................. 52 55 56
0.593-0.600............................. 53 56 57
0.601-0.608............................. 54 57 58
0.609-0.617............................. 55 58 59
0.618-0.626............................. 56 59 60
0.627-0.634............................. 57 60 61
------------------------------------------------------------------------
Note: Increase in filling densities to provide for seasonal changes may
be considered by the Commandant upon presentation of factual evidence
that safe operation can be effected.