[Code of Federal Regulations]
[Title 46, Volume 2]
[Revised as of October 1, 2004]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR56.50-30]

[Page 196-197]
 
                           TITLE 46--SHIPPING
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 56_PIPING SYSTEMS AND APPURTENANCES--Table of Contents
 
    Subpart 56.50_Design Requirements Pertaining to Specific Systems
 
Sec. 56.50-30  Boiler feed piping.

    (a) General requirements. (1) Steam vessels, and motor vessels 
fitted with steam driven electrical generators shall have at least two 
separate means of supplying feed water for the boilers. All feed pumps 
shall be fitted with the necessary connections for this purpose. The 
arrangement of feed pumps shall be in accordance with paragraph (d) or 
(e) of this section.
    (2) Feed pump supply to power boilers may utilize the group feed 
system or the unit feed system.
    (3) Feed discharge piping from the pump up to, but not including the 
required stop and stop-check valves, shall be designed for either the 
feed pump relief valve setting or the shutoff head of the pump if a 
relief valve is not fitted. (Refer to Sec. 56.07-10(b) for specific 
requirements.) Feed piping from the boiler, to and including the 
required stop and stop-check valves (see paragraph (b) of this section), 
shall have a design pressure which exceeds the maximum allowable working 
pressure of the boiler by either 25 percent or 225 pounds per square 
inch whichever is less. The value of allowable stress for design 
purposes shall be selected as described in Sec. 56.07-10(e) at a 
temperature not below that for saturated steam at the maximum allowable 
working pressure of the boiler.
    (4) Feed pumps for water tube boilers shall have fresh water 
connections only. Care shall be taken to prevent the accidental 
contamination of feed water from salt water or oil systems.
    (b) Feed valves. (1) Stop and stop-check valves shall be fitted in 
the main feed line and shall be attached as close as possible to drum 
feed inlet nozzles or to the economizer feed inlet nozzles on boilers 
fitted with integral economizers.
    (2) Where the installation will not permit the feed stop valve to be 
attached directly to the drum inlet nozzle on boilers not fitted with 
economizers, a distance piece may be installed between the stop valve 
and the inlet nozzle.
    (3) Feed stop or stop-check valves may be located near the operating 
platform on boilers fitted with economizers provided the piping between 
the valves and the economizer, exclusive of the feed valves and the 
economizer inlet nozzles, is installed with a minimum of intervening 
flanged connections.
    (4) Auxiliary feed lines shall be fitted with stop valves and stop-
check valves. Boilers not having auxiliary feed water nozzles, or where 
independent auxiliary feed lines are not installed, shall have the 
auxiliary feed line to the drum or economizer connected to the main feed 
line as close as possible to the main

[[Page 197]]

feed stop valves; and the valves in the auxiliary feed line shall be 
fitted as close as possible to the junction point.
    (5) Boilers fitted with economizers shall have a check valve fitted 
in the economizer discharge and located as close as possible to the drum 
fed inlet nozzle. When economizer bypasses are fitted, a stop-check 
valve shall be installed in lieu of the aforementioned check valve.
    (6) A sentinel valve is not required for vessels constructed after 
September 30, 1997, and for other vessels to which it has been shown to 
the satisfaction of the cognizant Officer in Charge, Marine Inspection 
or the Coast Guard Marine Safety Center, that a sentinel valve is not 
necessary for the safe operation of the particular boiler.
    (c) Feed water regulators, heaters, and grease extractors. (1) Where 
feed water regulators, tubular feed water heaters, and grease extractors 
are installed, an alternate means of operation with these devices 
bypassed shall be provided.
    (2) Feed water regulators designed with a built-in bypass for 
emergency use need not be fitted with an external bypass when installed 
in a feed system provided with an auxiliary feed line. All feed water 
regulators installed in a unit feed system shall be fitted with an 
external bypass. Feed water regulators bypasses shall be so arranged 
that the regular feed valves are in operation while the bypass is in 
use.
    (3) A feed water regulator may be interposed between the stop and 
stop-check valves in the feed lines.
    (d) Group feed system. Group feed systems shall be provided with 
pumps and piping as follows:
    (1) Oceangoing and Great Lakes steam vessels, having a feed pump 
attached to the main propelling unit, shall be provided with at least 
one independently driven feed pump. Each of these pumps shall be used 
exclusively for feed purposes and shall be capable of supplying the 
operating boilers at their normal capacity. In addition, a second 
independently driven pump, capable of supplying such boilers at 75 
percent of their normal capacity, shall be provided for emergency use. 
This second pump may be used for other purposes.
    (2) If two independently driven pumps are provided, each capable of 
supplying the boilers at their normal required operating capacity, and 
neither of which is used for other purposes, the third or emergency feed 
pump is not required. Where more than two independently driven feed 
pumps are provided, their aggregate capacity shall not be less than 200 
percent of that demanded by the boilers at their required normal 
operating capacity.
    (3) River or harbor steam vessels shall have at least two means for 
feeding the boilers; one of which shall be an independently driven pump, 
the other may be an attached pump, an additional independently driven 
pump, or an injector.
    (e) Unit feed system. Unit feed systems shall be provided with pumps 
and piping as follows:
    (1) The unit feed system may be used on vessels having two or more 
boilers. When the unit feed system is employed each boiler shall have 
its own independently driven main feed pump capable of supplying the 
boiler at its normal operating capacity. In addition these shall be an 
auxiliary independently driven feed pump of the same capacity which can 
be operated in place of and in conjunction with the main feed pump. In 
vessels with three or more boilers, not more than two boilers may be 
served by any one auxiliary pump. The auxiliary pump may be so 
interconnected that any pump can feed any boiler.
    (2) In the unit feed system, a separate feed line shall be provided 
for each boiler from its pumps. A separate auxiliary feed line is not 
required. The discharge from each pump and the feed supply to each 
boiler shall be automatically controlled by the level of the water in 
that boiler. In addition to the automatic control, manual control shall 
be provided.
    (f) Feedwater. The feedwater shall be introduced into a boiler as 
required by Sec. 52.01-105(b) of this subchapter.

[CGFR 68-82, 33 FR 18843, Dec. 18, 1968, as amended by CGD 95-028, 62 FR 
51201, Sept. 30, 1997; USCG-2002-13058, 67 FR 61278, Sept. 30, 2002]

[[Page 198]]