                           TITLE 46--SHIPPING
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 61_PERIODIC TESTS AND INSPECTIONS--Table of Contents
 
   Subpart 61.30_Tests and Inspections of Fired Thermal Fluid Heaters
 
Sec. 61.30-20  Automatic control and safety tests.

    Operational tests and checks of all safety and limit controls, 
combustion controls, programming controls, and safety relief valves must 
be conducted by the owner, chief engineer, or person in charge at the 
inspection for certification, periodic inspection, and when directed by 
the Officer in Charge, Marine Inspection, to determine that the control 
components and safety devices are functioning properly and are in 
satisfactory operating condition. These tests and checks must be 
conducted in the presence of a marine inspector and must include the 
following: proper prepurge, burner ignition sequence checks, operation 
of the combustion controls, limit controls, fluid flow controls, fluid 
level controls, high temperature control, proper postpurge control, and 
verification of the flame safeguard.

[CGD 88-057, 55 FR 24237, June 15, 1990, as amended by USCG-1999-4976, 
65 FR 6501, Feb. 9, 2000]