                           TITLE 46--SHIPPING
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 62_VITAL SYSTEM AUTOMATION--Table of Contents
 
   Subpart 62.25_General Requirements for All Automated Vital Systems
 
Sec. 62.25-10  Manual alternate control systems.

    (a) Manual alternate control systems must--
    (1) Be operable in an emergency and after a remote or automatic 
primary control system failure;
    (2) Be suitable for manual control for prolonged periods;
    (3) Be readily accessible and operable; and
    (4) Include means to override automatic controls and interlocks, as 
applicable.
    (b) Permanent communications must be provided between primary remote 
control locations and manual alternate control locations if operator 
attendance is necessary to maintain safe alternate control.

    Note: Typically, this includes main boiler fronts and local 
propulsion control.