[Code of Federal Regulations]
[Title 46, Volume 2]
[Revised as of October 1, 2004]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR62.35-20]

[Page 305-306]
 
                           TITLE 46--SHIPPING
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 62_VITAL SYSTEM AUTOMATION--Table of Contents
 
Subpart 62.35_Requirements for Specific Types of Automated Vital Systems
 
Sec. 62.35-20  Oil-fired main boilers.

    (a) General. (1) All main boilers, regardless of intended mode of 
operation, must be provided with the automatic safety trip control 
system(s) of paragraphs (h)(1), (h)(2)(i), (h)(2) (ii), and (i) of this 
section to prevent unsafe conditions after light off.
    (2) Manual alternate control of boilers must be located at the 
boiler front.
    (3) A fully automatic main boiler must include--
    (i) Automatic combustion control;
    (ii) Programing control;
    (iii) Automatic feedwater control;
    (iv) Safety controls; and
    (v) An alarm system.
    (4) Following system line-up and starting of auxiliaries, fully 
automatic main boilers must only require the operator to initiate the 
following sequences:
    (i) Boiler pre-purge.
    (ii) Trial for ignition of burners subsequent to successful initial 
burner light-off.
    (iii) Normal shutdown.
    (iv) Manual safety trip control operation.
    (v) Adjustment of primary control setpoints.
    (5) All requirements for programing control subsystems and safety 
control systems must be met when a boiler--
    (i) Automatically sequences burners;
    (ii) Is operated from a location remote from the boiler front; or
    (iii) Is fully automatic.
    (6) Where light oil pilots are used, the programing control and 
burner safety trip controls must be provided for the light oil system. 
Trial for ignition must not exceed 15 seconds and the main burner trial 
for ignition must not proceed until the pilot flame is proven.
    (b) Feedwater control. Automatic feedwater control subsystems must 
sense, at a minimum, boiler water level and steam flow.
    (c) Combustion control. Automatic combustion control subsystems must 
provide--
    (1) An air/fuel ratio which ensures complete combustion and stable 
flame with the fuel in use, under light off, steady state, and transient 
conditions; and
    (2) Stable boiler steam pressure and outlet temperatures under 
steady state and transient load conditions; and
    (3) A low fire interlock to prevent high firing rates and 
superheater damage during boiler warm up.

[[Page 306]]

    (d) Programing control. The programing control must provide a 
programed sequence of interlocks for the safe ignition and normal 
shutdown of the boiler burners. The programing control must prevent 
ignition if unsafe conditions exist and must include the following 
minimum sequence of events and interlocks:
    (1) Prepurge. Boilers must undergo a continuous purge of the 
combustion chamber and convecting spaces to make sure of a minimum of 5 
changes of air. The purge must not be less than 15 seconds in duration, 
and must occur immediately prior to the trial for ignition of the 
initial burner of a boiler. All registers and dampers must be open and 
an air flow of at least 25 percent of the full load volumetric air flow 
must be proven before the purge period commences. The prepurge must be 
complete before trial for ignition of the initial burner.

    Note: A pre-purge is not required immediately after a complete post-
purge.

    (2) Trial for ignition and ignition. (i) Only one burner per boiler 
is to be in trial for ignition at any time.
    (ii) Total boiler air flow during light off must be sufficient to 
prevent pocketing and explosive accumulations of combustible gases.
    (iii) The burner igniter must be in position and proven energized 
before admission of fuel to the boiler. The igniter must remain 
energized until the burner flame is established and stable, or until the 
trial for ignition period ends.
    (iv) The trial for ignition period must be as short as practical for 
the specific installation, but must not exceed 15 seconds.
    (v) Failure of the burner to ignite during a trial for ignition must 
automatically actuate the burner safety trip controls.
    (3) Post-purge. (i) Immediately after normal shutdown of the boiler, 
an automatic purge of the boiler equal to the volume and duration of the 
prepurge must occur.
    (ii) Following boiler safety trip control operation, the air flow to 
the boiler must not automatically increase. Post purge in such cases 
must be under manual control.
    (e) Burner fuel oil valves. Each burner must be provided with a 
valve that is--
    (1) Automatically closed by the burner or boiler safety trip control 
system; and
    (2) Operated by the programming control or combustion control 
subsystems, as applicable.
    (f) Master fuel oil valves. Each boiler must be provided with a 
master fuel oil valve to stop fuel to the boiler automatically upon 
actuation by the boiler safety trip control system.
    (g) Valve closure time. The valves described in paragraphs (e) and 
(f) of this section must close within 4 seconds of automatic detection 
of unsafe trip conditions.
    (h) Burner safety trip control system. (1) Each burner must be 
provided with at least one flame detector.
    (2) The burner valve must automatically close when--
    (i) Loss of burner flame occurs;
    (ii) Actuated by the boiler safety trip control system;
    (iii) The burner is not properly seated or in place; or
    (iv) Trial for ignition fails, if a programing control is provided.
    (i) Boiler safety trip control system. (1) Each boiler must be 
provided with a safety trip control system that automatically closes the 
master and all burner fuel oil valves upon--
    (i) Boiler low-low water level;
    (ii) Inadequate boiler air flow to support complete combustion;
    (iii) Loss of boiler control power;
    (iv) Manual safety trip operation; or
    (v) Loss of flame at all burners.
    (2) The low-low water level safety trip control must account for 
normal vessel motions and operating transients.

[CGD 81-030, 53 FR 17838, May 18, 1988, as amended by USCG-2002-13058, 
67 FR 61278, Sept. 30, 2002]