PART 63_AUTOMATIC AUXILIARY BOILERS--Table of Contents
 
                   Subpart 63.15_General Requirements
 
Sec. 63.15-1  General.


    (a) Each automatic auxiliary boiler must be designed and constructed 
for its intended service according to the requirements of the parts 
referenced in Sec. 54.01-5, Table 54.01-5(A) of this chapter.
    (b) Controls and safety devices for automatic auxiliary boilers must 
meet the applicable requirements of ANSI/ASME CSD-1/CSD-1a, except 
Paragraph CG-310.
    (c) All devices and components of an automatic auxiliary boiler must 
satisfactorily operate within the marine environment. The boiler must 
satisfactorily operate with a momentary roll of 30[deg], a list of 
15[deg], and a permanent trim of 5[deg] with it installed in a position 
as specified by the manufacturer.
    (d) An electrical control used to shut down the automatic auxiliary 
boiler must be installed in accordance with Sec. 58.01-25 of this 
chapter. This device

[[Page 314]]

must stop the fuel supply to the fuel burning equipment.
    (e) Mercury tube actuated controls are prohibited from being 
installed and used on automatic auxiliary boilers.