[Code of Federal Regulations]
[Title 46, Volume 2]
[Revised as of October 1, 2004]
From the U.S. Government Printing Office via GPO Access
[CITE: 46CFR63.25-3]

[Page 315-316]
 
                           TITLE 46--SHIPPING
 
   CHAPTER I--COAST GUARD, DEPARTMENT OF HOMELAND SECURITY (CONTINUED)
 
PART 63_AUTOMATIC AUXILIARY BOILERS--Table of Contents
 
  Subpart 63.25_Requirements for Specific Types of Automatic Auxiliary 
                                 Boilers
 
Sec. 63.25-3  Electric hot water supply boilers.

    (a) Electric hot water supply boilers which have a capacity not 
greater than 454 liters (120 U.S. gallons), a heat input rate not 
greater than 200,000 Btu/hr. (58.6 kilowatts), meet the requirements of 
ANSI/UL 174 or ANSI/UL 1453, and are protected by the relief device(s) 
required in Sec. 53.05-2 of this chapter do not have to meet any other 
requirements of this section except the periodic testing required by 
paragraph (j) of this section. Electric hot water supply boilers which 
meet the requirements of UL 174 may have temperature-pressure relief 
valves that meet the requirements of ANSI/AGA Z21.22 in lieu of subpart 
53.05 of this chapter.
    (b) Each hot water supply boiler must be constructed in accordance 
with the applicable requirements of part 52 or part 53 of this chapter.
    (c) Branch circuit conductors for hot water supply boilers which 
have a capacity not greater than 454 liters (120 U.S. gallons) must have 
a current carrying capacity of not less than 125 percent of the current 
rating of the appliance. Branch circuit conductors for hot water supply 
boilers with capacities of more than 454 liters (120 U.S. gallons) must 
have a current carrying capacity of not less than 100 percent of the 
current rating of the appliance. Wiring materials and methods must 
comply with part 111, subpart 111.60 of this chapter. A hot water supply 
boiler having a current rating of more than 48 amperes and employing 
resistance type heating elements must have the heating elements on 
subdivided circuits. Each subdivided load, except for an electric hot 
water supply boiler employing a resistance type immersion electric 
heating element, must not exceed 48 amperes, and it must be protected at 
not more than 60 amperes. An electric hot water supply boiler employing 
a resistance type immersion electric heating element may be subdivided 
into circuits not exceeding 120 amperes and protected at not more than 
150 amperes. Overcurrent protection devices must comply with part 111, 
subpart 111.50 of this chapter.
    (d) Heating elements must be insulated electrically from the water 
being heated, guarded against mechanical injury and contact with outside 
objects, and securely supported. Consideration must be given to sagging, 
opening, and other adverse conditions of the elements resulting from 
continuous heating, and flexion of supports and wiring due to alternate 
heating and cooling. Wrap-around elements must be secured in a manner 
which prevents loosening.
    (e) Iron and steel parts must be protected against corrosion by 
enameling, galvanizing, or plating. Iron and steel storage tanks having 
a wall thickness less than 6.4mm (\1/4\-inch) must have the inside 
surface protected against corrosion.
    (f) Each heating element must have a temperature regulating device. 
The device must limit the water from obtaining a temperature greater 
than 90 [deg]C (194 [deg]F). If the control has a marked off position, 
the control must disconnect the heating element from all ungrounded 
conductors, and it must not respond to temperature when placed in the 
off position.

[[Page 316]]

    (g) An independent temperature limiting device must prevent the 
water in the upper 25 percent of the tank from attaining a temperature 
higher than 99 [deg]C (210 [deg]F). This device must require manual 
resetting, be trip free from the operating means, open all ungrounded 
power supply conductors to the heater, and be readily accessible.
    (h) Electric hot water supply boilers must have pressure and 
temperature relieving valves. The valve temperature setting must not be 
more than 99 [deg]C (210 [deg]F). The pressure relief setting must not 
be higher than the marked working pressure of the boiler. The pressure 
and temperature relief valves must meet part 53, subpart 53.05 of this 
chapter. The pressure and temperature relief valves may be combined into 
a pressure-temperature relief valve.
    (i) Electric hot water supply boilers must be marked in a visible 
location with the manufacturer's name, model or other identification 
number, water capacity, and the electrical ratings of each heating 
element. When two or more heating elements are installed, the maximum 
wattage or current consumption must be indicated. The cold water inlet 
and the hot water outlet must each be clearly distinguished or marked 
for identification purposes.
    (j) All electric hot water supply boilers must have their pressure 
relief devices tested as required by part 52 or part 53 of this chapter, 
as applicable. Electric hot water supply boilers which meet the 
requirements of ANSI/UL 174 or ANSI/UL 1453 and have heating elements, 
temperature regulating controls, and temperature limiting controls are 
satisfactory for installation and service without further installation 
testing. All electric hot water supply boilers not meeting the 
requirements of ANSI/UL 174 or ANSI/UL 1453 must have their heating 
elements, temperature regulating controls, and temperature limiting 
controls tested by the marine inspector at the time of installation.

[CGD 88-057, 55 FR 24238, June 15, 1990, as amended by CGD 95-028, 62 FR 
51202, Sept. 30, 1997]