Sec. 64.63  Minimum emergency venting capacity.

    (a) The total emergency venting capacity (Q) of the relief devices 
of an uninsulated MPT must be in accordance with Table 1 or the 
following formula based upon the pressure relief device operating at a 
pressure not to exceed the test pressure:
[GRAPHIC] [TIFF OMITTED] TC13NO91.047

where:

Q=Minimum required rate of discharge in cubic feet per minute of free 
air at standard conditions (60 [deg]F and 14.7 psia).
M=Molecular weight of the product, or 86.7.
T=Temperature, degrees Rankine (460[deg] + temperature in degrees F of 
gas at relieving temperature), or 710[deg] Rankine.
A=Total external surface area of the tank compartment in square feet.
L=Latent heat of the product being vaporized at relieving conditions in 
Btu per pound, or 144 Btu per pound.
Z=Compressibility factor of the gas at relieving conditions, or 1.0.
C=Constant based on relation of specific heats, in accordance with 
Appendix J of Division 1 of Section VIII of the ASME Code, 1974 edition, 
or 315.

    (b) The total emergency venting capacity (Q) of an insulated 
portable tank may have a reduction if--
    (1) It is shown to the Coast Guard that the insulation reduces the 
heat transmission to the tank;

[[Page 322]]

    (2) The present reduction of the emergency venting capacity (Q) is 
limited to the percent reduction of the heat transmission to the tank or 
50 percent, whichever is less; and
    (3) The insulation is sheathed.

Table 1--Minimum emergency venting capacity in cubic feet: free air/hour
                     (14.7 lb/in\2\a and 60 [deg]F)
------------------------------------------------------------------------
  Exposed area      Cubic feet free     Exposed area    Cubic feet free
 square feet \1\     air per hour     square feet \1\     air per hour
------------------------------------------------------------------------
         20               27,600              275            237,000
         30               38,500              300            256,000
         40               48,600              350            289,500
         50               58,600              400            322,100
         60               67,700              450            355,900
         70               77,000              500            391,000
         80               85,500              550            417,500
         90               94,800              600            450,000
        100              104,000              650            479,000
        120              121,000              700            512,000
        140              136,200              750            540,000
        160              152,100              800            569,000
        180              168,200              850            597,000
        200              184,000              900            621,000
        225              199,000              950            656,000
        250              219,500            1,000           685,000
------------------------------------------------------------------------
\1\ Interpolate for intermediate sizes.