Sec. 193.2445  Sources of power.

    (a) Electrical control systems, means of communication, emergency 
lighting, and firefighting systems must have at least two sources of 
power which function so that failure of one source does not affect the 
capability of the other source.
    (b) Where auxiliary generators are used as a second source of 
electrical power:
    (1) They must be located apart or protected from components so that 
they are not unusable during a controllable emergency; and
    (2) Fuel supply must be protected from hazards.