[Code of Federal Regulations] [Title 49, Volume 3] [Revised as of October 1, 2004] From the U.S. Government Printing Office via GPO Access [CITE: 49CFR193.2505] [Page 133] TITLE 49--TRANSPORTATION CHAPTER I--RESEARCH AND SPECIAL PROGRAMS ADMINISTRATION, DEPARTMENT OF TRANSPORTATION (CONTINUED) PART 193_LIQUEFIED NATURAL GAS FACILITIES: FEDERAL SAFETY STANDARDS-- Table of Contents Subpart F_Operations Sec. 193.2505 Cooldown. (a) The cooldown of each system of components that is subjected to cryogenic temperatures must be limited to a rate and distribution pattern that keeps thermal stresses within design limits during the cooldown period, paying particular attention to the performance of expansion and contraction devices. (b) After cooldown stabilization is reached, cryogenic piping systems must be checked for leaks in areas of flanges, valves, and seals.