Sec. 193.2615  Isolating and purging.

    (a) Before personnel begin maintenance activities on components 
handling flammable fluids which are isolated for maintenance, the 
component must be purged in accordance with a procedure which meets the 
requirements of AGA ``Purging Principles and Practices,'' unless the 
maintenance procedures under Sec. 193.2605 provide that the activity 
can be safely performed without purging.
    (b) If the component or maintenance activity provides an ignition 
source, a technique in addition to isolation valves (such as removing 
spool pieces or valves and blank flanging the piping, or double block 
and bleed valving) must be used to ensure that the work area is free of 
flammable fluids.