Sec. 36.27  Fire protection.

    (a) The radiation room at a panoramic irradiator must have heat and 
smoke detectors. The detectors must activate an audible alarm. The alarm 
must be capable of alerting a person who is prepared to summon 
assistance promptly. The sources must automatically become fully 
shielded if a fire is detected.
    (b) The radiation room at a panoramic irradiator must be equipped 
with a fire extinguishing system capable of extinguishing a fire without 
the entry of personnel into the room. The system for the radiation room 
must have a shut-off valve to control flooding into unrestricted areas.