[Code of Federal Regulations]
[Title 10, Volume 3]
[Revised as of January 1, 2005]
From the U.S. Government Printing Office via GPO Access
[CITE: 10CFR431.25]

[Page 311-312]
 
                            TITLE 10--ENERGY
 
                    CHAPTER II--DEPARTMENT OF ENERGY
 
PART 431_ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND INDUSTRIAL 
EQUIPMENT--Table of Contents
 
                        Subpart B_Electric Motors
 
Sec. 431.25  Energy conservation standards and effective dates.

    (a) Each electric motor manufactured (alone or as a component of 
another piece of equipment) after October 24, 1997, or in the case of an 
electric motor which requires listing or certification by a nationally 
recognized safety testing laboratory, after October 24, 1999, shall have 
a nominal full load efficiency of not less than the following:

----------------------------------------------------------------------------------------------------------------
                                                            Nominal full load efficiency
                                   -----------------------------------------------------------------------------
    Motor horsepower/ standard          Open motors (number of poles)        Enclosed motors (number of poles)
        kilowatt equivalent        -----------------------------------------------------------------------------
                                         6            4            2            6            4            2
----------------------------------------------------------------------------------------------------------------
1 / .75...........................         80.0         82.5  ...........         80.0         82.5         75.5
1.5 / 1.1.........................         84.0         84.0         82.5         85.5         84.0         82.5
2 / 1.5...........................         85.5         84.0         84.0         86.5         84.0         84.0
3 / 2.2...........................         86.5         86.5         84.0         87.5         87.5         85.5

[[Page 312]]


5 / 3.7...........................         87.5         87.5         85.5         87.5         87.5         87.5
7.5 / 5.5.........................         88.5         88.5         87.5         89.5         89.5         88.5
10 / 7.5..........................         90.2         89.5         88.5         89.5         89.5         89.5
15 / 11...........................         90.2         91.0         89.5         90.2         91.0         90.2
20 / 15...........................         91.0         91.0         90.2         90.2         91.0         90.2
25 / 18.5.........................         91.7         91.7         91.0         91.7         92.4         91.0
30 / 22...........................         92.4         92.4         91.0         91.7         92.4         91.0
40 / 30...........................         93.0         93.0         91.7         93.0         93.0         91.7
50 / 37...........................         93.0         93.0         92.4         93.0         93.0         92.4
60 / 45...........................         93.6         93.6         93.0         93.6         93.6         93.0
75 / 55...........................         93.6         94.1         93.0         93.6         94.1         93.0
100 / 75..........................         94.1         94.1         93.0         94.1         94.5         93.6
125 / 90..........................         94.1         94.5         93.6         94.1         94.5         94.5
150 / 110.........................         94.5         95.0         93.6         95.0         95.0         94.5
200 / 150.........................         94.5         95.0         94.5         95.0         95.0         95.0
----------------------------------------------------------------------------------------------------------------

    (b) For purposes of determining the required minimum nominal full 
load efficiency of an electric motor that has a horsepower or kilowatt 
rating between two horsepowers or kilowattages listed consecutively in 
paragraph (a) of this section, each such motor shall be deemed to have a 
horsepower or kilowatt rating that is listed in paragraph (a) of this 
section. The rating that the motor is deemed to have shall be determined 
as follows:
    (1) A horsepower at or above the midpoint between the two 
consecutive horsepowers shall be rounded up to the higher of the two 
horsepowers;
    (2) A horsepower below the midpoint between the two consecutive 
horsepowers shall be rounded down to the lower of the two horsepowers, 
or
    (3) A kilowatt rating shall be directly converted from kilowatts to 
horsepower using the formula, 1 kilowatt = (1 / 0.746) horsepower, 
without calculating beyond three significant decimal places, and the 
resulting horsepower shall be rounded in accordance with paragraphs 
(b)(1) or (b)(2) of this section, whichever applies.
    (c) This section does not apply to definite purpose motors, special 
purpose motors, and those motors exempted by the Secretary.